Service Plus Inns & Suites - Swimming Pool
3503 114 Avenue SE Calgary AB T2Z 3X2 · Aquatic Facility
Inspection summary
Service Plus Inns & Suites - Swimming Pool has been inspected 13 times by Alberta Health Services (Environmental Public Health) since November 28, 2023. The most recent inspection, on October 14, 2026, recorded 1 infraction.
2 of 13 inspections on record found no infractions at all. In the past 12 months there were 7 inspections with 10 infractions recorded. The higher-risk findings here relate to: Pool and spa water quality.
The number of infractions per inspection has stayed roughly the same over time.
What these findings mean
Health authorities word their findings differently, so we group them by what they mean for the people using the facility. Higher-risk findings are the ones that could directly cause illness or injury, such as water that is not properly treated.
Pool and spa water qualityHigher risk
For pools, spas and splash pads, inspectors test disinfectant levels, pH and water clarity, and check safety equipment. Water that is not properly treated can spread skin, ear and stomach infections.
Recorded 18 times across 11 separate inspections, most recently on October 14, 2026. For example:
Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
About this data
These results come from Alberta Health Services (Environmental Public Health), which inspects food premises and other public facilities in this area. We republish the authority's public disclosure data and refresh it regularly; the official record is the final word.
13 inspections
- Risk Management Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- 1. The flow metre for the recirculation pump was not operational.2. Based on the Tagelus TA-60D high rate sand filter surface area of 3.1 sq. ft., the maximum flow rate is 47gpm, and the required minimum flow rate for the swimming pool is 54gpm to achieve a recirculation rate of 4 hours. COMPLETE THE FOLLOWING:1. Please replace the flow metre.2. The minimum flow rate must not be greater than the maximum flow rate. Swimming pools built after November 30, 2006 are required to meet the 4 hour recirculation rate and the maximum rate of filtration must not be greater than 10 litres per second per square meter (15 USG/ min/ sq. ft.).
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample collected on May 7, 2026 had a Heterotrophic Plate Count of 320 CFU/mL.-treat and resample.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- 1. The flow metre for the recirculation pump was not operational.2. Based on the Tagelus TA-60D high rate sand filter surface area of 3.1 sq. ft., the maximum flow rate is 47gpm, and the required minimum flow rate for the swimming pool is 54gpm to achieve a recirculation rate of 4 hours. COMPLETE THE FOLLOWING:1. Please replace the flow metre.2. The minimum flow rate must not be greater than the maximum flow rate. Swimming pools built after November 30, 2006 are required to meet the 4 hour recirculation rate and the maximum rate of filtration must not be greater than 10 litres per second per square meter (15 USG/ min/ sq. ft.).
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- 1. The flow metre for the recirculation pump was not operational.2. Based on the Tagelus TA-60D high rate sand filter surface area of 3.1 sq. ft., the maximum flow rate is 47gpm, and the required minimum flow rate for the swimming pool is 54gpm to achieve a recirculation rate of 4 hours. COMPLETE THE FOLLOWING:1. Please replace the flow metre.2. The minimum flow rate must not be greater than the maximum flow rate. Swimming pools built after November 30, 2006 are required to meet the 4 hour recirculation rate and the maximum rate of filtration must not be greater than 10 litres per second per square meter (15 USG/ min/ sq. ft.).
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Sample not processed at the lab - Apr 2 collection date and dropped off Apr 3 (Stat holiday).-resample this week; ensure water chemistry is perfect this week or the 3rd consecutive unsatisfactory result will close the pool.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample collected on March 26, 2026 had a Heterotrophic Plate Count of 3800 CFU/mL.-treat and resample.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- 1. The flow metre for the recirculation pump was not operational.2. Based on the Tagelus TA-60D high rate sand filter surface area of 3.1 sq. ft., the maximum flow rate is 47gpm, and the required minimum flow rate for the swimming pool is 54gpm to achieve a recirculation rate of 4 hours. COMPLETE THE FOLLOWING:1. Please replace the flow metre.2. The minimum flow rate must not be greater than the maximum flow rate. Swimming pools built after November 30, 2006 are required to meet the 4 hour recirculation rate and the maximum rate of filtration must not be greater than 10 litres per second per square meter (15 USG/ min/ sq. ft.).
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Monitoring Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample collected on March 26, 2026 had a Heterotrophic Plate Count of 3800 CFU/mL.-treat and resample.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- 1. The flow metre for the recirculation pump was not operational.2. Based on the Tagelus TA-60D high rate sand filter surface area of 3.1 sq. ft., the maximum flow rate is 47gpm, and the required minimum flow rate for the swimming pool is 54gpm to achieve a recirculation rate of 4 hours. COMPLETE THE FOLLOWING:1. Please replace the flow metre.2. The minimum flow rate must not be greater than the maximum flow rate. Swimming pools built after November 30, 2006 are required to meet the 4 hour recirculation rate and the maximum rate of filtration must not be greater than 10 litres per second per square meter (15 USG/ min/ sq. ft.).
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample collected on March 26, 2026 had a Heterotrophic Plate Count of 3800 CFU/mL.-treat and resample.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
0 infractions
- Monitoring Inspection
0 infractions
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The sample collected on October 10, 2024 had an HPC count of 440 CFU/ml.Submit a resample.
- 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
- The flow meter for the swimming pool is not working.Replace the flow meter with a functioning one.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
1 infraction
- 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
- The flow meter for the swimming pool is not working.Replace the flow meter with a functioning one.
- 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The sample submitted on September 5, 2024 had an HPC count of 250 CFU/ml.Treat and resample the pool.
- 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
- The flow meter for the swimming pool is not working.Replace the flow meter with a functioning one.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The sample submitted on August 1, 2024 had an HPC count of 350 CFU/ml.Treat and resample the pool.
- 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
- The flow meter for the swimming pool is not working.Replace the flow meter with a functioning one.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Monitoring Inspection
1 infraction
- 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
- The flow meter for the swimming pool is not working.Replace the flow meter with a functioning one.
- 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
Nearby inspected facilities
- Service Plus Inns & Suites - Common
3503 114 Avenue SE Calgary AB T2Z 3X2
3 inspections
- Service Plus Inns & Suites - Food
3503 114 Avenue SE Calgary AB T2Z 3X2
3 inspections
- Service Plus Inns & Suites - Whirlpool
3503 114 Avenue SE Calgary AB T2Z 3X2
9 inspections
- Hero Canada
115 - 11505 35 Street SE Calgary AB T2Z 4B1
1 inspection
- Rally Pointe Volleyball Complex
11511 35 Street SE Calgary AB T2Z 4B1
1 inspection
- Deerfoot Inn & Casino - Corner Whirlpool
1000 - 11500 35 Street SE Calgary AB T2Z 3W4
8 inspections
- Deerfoot Inn & Casino - Center Whirlpool
1000 - 11500 35 Street SE Calgary AB T2Z 3W4
7 inspections
- Deerfoot Inn & Casino - Food
1000 - 11500 35 Street SE Calgary AB T2Z 3W4
10 inspections