Service Plus Inns & Suites - Swimming Pool

3503 114 Avenue SE Calgary AB T2Z 3X2 · Aquatic Facility

14 inspections

  1. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The water sample collected on May 7, 2026 had a Heterotrophic Plate Count of 320 CFU/mL.-treat and resample.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • 1. The flow metre for the recirculation pump was not operational.2. Based on the Tagelus TA-60D high rate sand filter surface area of 3.1 sq. ft., the maximum flow rate is 47gpm, and the required minimum flow rate for the swimming pool is 54gpm to achieve a recirculation rate of 4 hours. COMPLETE THE FOLLOWING:1. Please replace the flow metre.2. The minimum flow rate must not be greater than the maximum flow rate. Swimming pools built after November 30, 2006 are required to meet the 4 hour recirculation rate and the maximum rate of filtration must not be greater than 10 litres per second per square meter (15 USG/ min/ sq. ft.).
  2. Risk Management Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • 1. The flow metre for the recirculation pump was not operational.2. Based on the Tagelus TA-60D high rate sand filter surface area of 3.1 sq. ft., the maximum flow rate is 47gpm, and the required minimum flow rate for the swimming pool is 54gpm to achieve a recirculation rate of 4 hours. COMPLETE THE FOLLOWING:1. Please replace the flow metre.2. The minimum flow rate must not be greater than the maximum flow rate. Swimming pools built after November 30, 2006 are required to meet the 4 hour recirculation rate and the maximum rate of filtration must not be greater than 10 litres per second per square meter (15 USG/ min/ sq. ft.).
  3. Demand Inspection

    3 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Sample not processed at the lab - Apr 2 collection date and dropped off Apr 3 (Stat holiday).-resample this week; ensure water chemistry is perfect this week or the 3rd consecutive unsatisfactory result will close the pool.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The water sample collected on March 26, 2026 had a Heterotrophic Plate Count of 3800 CFU/mL.-treat and resample.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • 1. The flow metre for the recirculation pump was not operational.2. Based on the Tagelus TA-60D high rate sand filter surface area of 3.1 sq. ft., the maximum flow rate is 47gpm, and the required minimum flow rate for the swimming pool is 54gpm to achieve a recirculation rate of 4 hours. COMPLETE THE FOLLOWING:1. Please replace the flow metre.2. The minimum flow rate must not be greater than the maximum flow rate. Swimming pools built after November 30, 2006 are required to meet the 4 hour recirculation rate and the maximum rate of filtration must not be greater than 10 litres per second per square meter (15 USG/ min/ sq. ft.).
  4. Monitoring Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The water sample collected on March 26, 2026 had a Heterotrophic Plate Count of 3800 CFU/mL.-treat and resample.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • 1. The flow metre for the recirculation pump was not operational.2. Based on the Tagelus TA-60D high rate sand filter surface area of 3.1 sq. ft., the maximum flow rate is 47gpm, and the required minimum flow rate for the swimming pool is 54gpm to achieve a recirculation rate of 4 hours. COMPLETE THE FOLLOWING:1. Please replace the flow metre.2. The minimum flow rate must not be greater than the maximum flow rate. Swimming pools built after November 30, 2006 are required to meet the 4 hour recirculation rate and the maximum rate of filtration must not be greater than 10 litres per second per square meter (15 USG/ min/ sq. ft.).
  5. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The water sample collected on March 26, 2026 had a Heterotrophic Plate Count of 3800 CFU/mL.-treat and resample.
  6. Risk Management Inspection

    0 infractions

  7. Monitoring Inspection

    0 infractions

  8. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The sample collected on October 10, 2024 had an HPC count of 440 CFU/ml.Submit a resample.
    • 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
      • The flow meter for the swimming pool is not working.Replace the flow meter with a functioning one.
  9. Risk Management Inspection

    1 infraction

    • 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
      • The flow meter for the swimming pool is not working.Replace the flow meter with a functioning one.
  10. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The sample submitted on September 5, 2024 had an HPC count of 250 CFU/ml.Treat and resample the pool.
    • 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
      • The flow meter for the swimming pool is not working.Replace the flow meter with a functioning one.
  11. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The sample submitted on August 1, 2024 had an HPC count of 350 CFU/ml.Treat and resample the pool.
    • 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
      • The flow meter for the swimming pool is not working.Replace the flow meter with a functioning one.
  12. Monitoring Inspection

    1 infraction

    • 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
      • The flow meter for the swimming pool is not working.Replace the flow meter with a functioning one.
  13. Risk Management Inspection

    0 infractions

  14. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The sample collected on July 13, 2023 had an HPC count of 2970 CFU/ml.Treat the pool and send in a resample.