Eau Claire Athletic Club - Hot Tub
101 3 Street SW Calgary AB T2P 4G6 · Aquatic Facility
13 inspections
- Risk Management Inspection
0 infractions
- Risk Management Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample (26ES-049E00730) collected on February 18th, 2026, was rejected by the lab as the time of collection was not recorded on the requisition form. Please resample as soon as possible.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample (26ES-049E00730) collected on February 18th, 2026, was rejected by the lab as the time of collection was not recorded on the requisition form. Please resample as soon as possible.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample (26ES-043E00042) collected on February 11th, 2026, came back unsatisfactory as the HPC was elevated (tested to be 120 CFU/mL). The maximum acceptable concentration is 100 CFU/mL.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample (26ES-043E00042) collected on February 11th, 2026, came back unsatisfactory as the HPC was elevated (tested to be 120 CFU/mL). The maximum acceptable concentration is 100 CFU/mL.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Water sample (25ES-225E00073) tested positive for Pseudomonas aeruginosa. Please close the pool and conduct the necessary treatments before reopening.Pseudomonas aeruginosa documentation was sent to the operator. Please submit another water sample for the hot tub.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Initial Inspection
0 infractions
- Demand Inspection
2 infractions
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The total alkalinity was tested to be 34mg/L.The total alkalinity is to be kept within 60mg/L and 180mg/L. Please adjust the total alkalinity.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- The temperature of the hot tub was measured to be 41.2C. The temperature was checked again at the end of the inspection and was measured to be 41.9C. Please reduce the hot tub temperature to a maximum of 40C and ensure the temperature regulator is working properly such that the temperature does not exceed 40C.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The flow rate exceeded the maximum flow allowed for the whirlpool. With the whirlpool built before November 2006, the maximum flow rate must not exceed the manufacturer's maximum flow rate. The maximum flow rate as per the manufacturer's specification is 100 GPM. Thus, please ensure to maintain the flow rate between 74.85 GPM and not exceeding 100 GPM.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The flow rate exceeded the maximum flow allowed for the whirlpool. With the whirlpool built before November 2006, the maximum flow rate must not exceed the manufacturer's maximum flow rate. The maximum flow rate as per the manufacturer's specification is 100 GPM. Thus, please ensure to maintain the flow rate between 74.85 GPM and not exceeding 100 GPM.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
5 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- A discrepancy was observed between the chlorine reading on automated controller and manual testing. Manual test (FC): 6.00ppm Automated test: 5.09mg/LPlease ensure the automated controller is calibrated properly and consistent with manual testing.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Skimmer baskets were missing from the hot tub. Please install.
- 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
- A clock was not visible from the hot tub. Please install a hot tub that can be easily seen from inside the hot tub.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- The skimmer system had a build-up of green algae, grime, and debris. Please clean and sanitize the skimmer system.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Anti-entrapment plan must be updated to reflect it the hydro-jet system and recirculation system are interconnected or independent. Please also confirm the new VGBA-2017 covers are installed as per the VGBA-2017 instructions. Diagrams or pictures of the sump depth are required.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample (25ES-184E00772) collected on July 3rd, 2025, was rejected by the lab as the identification sticker was not on the sample bottle. Please submit a new water sample for the hot tub.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?