Emerald Hills Leisure Centre - Whirlpool
3555 Emerald Drive Sherwood Park AB T8H 0W6 · Aquatic Facility
9 inspections
- Monitoring Inspection
0 infractions
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample result for sample collected December 29, 2025, had a heterotrophic plate count of greater than 57,000.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- The microbiological water result submitted for the whirlpool was unsatisfactory:Unsatisfactory Lab Test Result: Collection Date: 2025-08-28Location: Whirlpool** Total Coliform: PRESENT
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Monitoring Inspection
0 infractions
- Risk Management Inspection
0 infractions
- Monitoring Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Flow meter indicates flow rate is approximately 520gpm.The turnover is 23 minutes based on the flow rate.**Turnover rate required for the whirlpool is 20 minutes. The flow rate should be a minimum of 606 gpm to meet this turnover. Please check the system and adjust as needed.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Monitoring Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Two filters provided and are backwashed every other week on a rotating basis.Flow rate is approximately 460 gpm. Turnover rate is approximately 26 minutes.**Turnover rate for the whirlpool should 20 minutes. The flow rate should be 606 gpm to meet this turnover. Please check the system and adjust as needed.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?