Evergreen Estates - Whirlpool
639 14 Avenue SW Calgary AB T2R 1H9 · Aquatic Facility
14 inspections
- Risk Management Inspection
1 infraction
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- The anti-entrapment plan is being updated as the maximum flow rate on the form of the system was exceeding the drain covers rating. The max flow was determined by the end of the pump curve, therefore it is recommended to install a flow meter and obtain an actual flow rate.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Monitoring Inspection
3 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Manual pH reading was 7.6 and the automated chemical reading was 7.3. - Clean the probes and calibrate as needed.
- 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
- The clock at the whirlpool was not operational. - Repair or replace so patrons can monitor their length of stay.No clock or other device for monitoring patron's length of stay in saunas and steam rooms. - Provide
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- The anti-entrapment plan and written response procedures were not available for review at the time of inspection.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample taken October 16, 2025 - rejected as the sample was received at the lab more than 24 hours after collection. Please re-sample.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The probe for the automatic feeder was in disrepair.**Please repair/replace probes to ensure adequate amount of chemicals are added to pool water
- 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
- The FAC was measured at 15ppm**Reduce the concentration of the FAC as the high concentration can cause discomfort to bathers.**Maintain FAC above 2ppm and below 10ppm
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample taken January 310th, 2025 - rejected as the sample was received at the lab more than 24 hours after collection. Please re-sample.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The probe for the automatic feeder was in disrepair.**Please repair/replace probes to ensure adequate amount of chemicals are added to pool water
- 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
- The FAC was measured at 15ppm**Reduce the concentration of the FAC as the high concentration can cause discomfort to bathers.**Maintain FAC above 2ppm and below 10ppm
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample taken Dec. 18, 2024 - 110 CFU/mL.-Resample
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The probe for the automatic feeder was in disrepair.**Please repair/replace probes to ensure adequate amount of chemicals are added to pool water
- 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
- The FAC was measured at 15ppm**Reduce the concentration of the FAC as the high concentration can cause discomfort to bathers.**Maintain FAC above 2ppm and below 10ppm
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
3 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Water sample taken July 26, 2024 - Pseudomonas isolated.-Treat and resampleID: 24ES-208E00112
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The probe for the automatic feeder was in disrepair.**Please repair/replace probes to ensure adequate amount of chemicals are added to pool water
- 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
- The FAC was measured at 15ppm**Reduce the concentration of the FAC as the high concentration can cause discomfort to bathers.**Maintain FAC above 2ppm and below 10ppm
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Monitoring Inspection
1 infraction
- 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
- White powder observed in the pool basin.-Ensure basin is closed to clients when chemicals are added
- 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
- Demand Inspection
3 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Water sample taken Jun 18, 2024 - Pseudomonas isolated.-Treat and resample
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The probe for the automatic feeder was in disrepair.**Please repair/replace probes to ensure adequate amount of chemicals are added to pool water
- 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
- The FAC was measured at 15ppm**Reduce the concentration of the FAC as the high concentration can cause discomfort to bathers.**Maintain FAC above 2ppm and below 10ppm
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
3 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Water sample was unsatisfactory. Pseudomonas was isolated.-Treat pool and then re-sample the water for bacteriological quality
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The probe for the automatic feeder was in disrepair.**Please repair/replace probes to ensure adequate amount of chemicals are added to pool water
- 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
- The FAC was measured at 15ppm**Reduce the concentration of the FAC as the high concentration can cause discomfort to bathers.**Maintain FAC above 2ppm and below 10ppm
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample not processed (no ID number on bottle).-Please bring in another sample this week
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The probe for the automatic feeder was in disrepair.**Please repair/replace probes to ensure adequate amount of chemicals are added to pool water
- 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
- The FAC was measured at 15ppm**Reduce the concentration of the FAC as the high concentration can cause discomfort to bathers.**Maintain FAC above 2ppm and below 10ppm
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
3 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Dec 28, 2023 water sample positive for Pseudomonas.- Treat and resample.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The probe for the automatic feeder was in disrepair.**Please repair/replace probes to ensure adequate amount of chemicals are added to pool water
- 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
- The FAC was measured at 15ppm**Reduce the concentration of the FAC as the high concentration can cause discomfort to bathers.**Maintain FAC above 2ppm and below 10ppm
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Sample received >24 hours after collection.-Resample
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The probe for the automatic feeder was in disrepair.**Please repair/replace probes to ensure adequate amount of chemicals are added to pool water
- 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
- The FAC was measured at 15ppm**Reduce the concentration of the FAC as the high concentration can cause discomfort to bathers.**Maintain FAC above 2ppm and below 10ppm
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
1 infraction
- 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
- No clock was available.-Install a clock
- 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
- Monitoring Inspection
2 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The probe for the automatic feeder was in disrepair.**Please repair/replace probes to ensure adequate amount of chemicals are added to pool water
- 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
- The FAC was measured at 15ppm**Reduce the concentration of the FAC as the high concentration can cause discomfort to bathers.**Maintain FAC above 2ppm and below 10ppm
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?