Fairfield Inn & Suites by Marriott Airdrie - Whirlpool

911 Highland Park Cove NE Airdrie AB T4A 0R2 · Aquatic Facility

30 inspections

  1. Risk Management Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The TURNOVER RATE for the hot tub was calculated to be 21.9mins**Adjust flow rate to ensure that the water in the hot tub completes a full turnover/recirculation within 20mins.
  2. Demand Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Water sample submitted on June 29, 2026, showed positive isolation of Pseudomonas aeruginosa. **Please treat pool water and resample.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The TURNOVER RATE for the hot tub was calculated to be 21.9mins**Adjust flow rate to ensure that the water in the hot tub completes a full turnover/recirculation within 20mins.
  3. Monitoring Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The TURNOVER RATE for the hot tub was calculated to be 21.9mins**Adjust flow rate to ensure that the water in the hot tub completes a full turnover/recirculation within 20mins.
  4. Risk Management Inspection

    0 infractions

  5. Risk Management Inspection

    1 infraction

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Water sample collected on March 17, 2026, indicated presence of Pseudomonas aeruginosa.**Close hot tub**Complete thorough cleaning and treatment of pool and resubmit sample.
  6. Demand Inspection

    1 infraction

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Water sample collected on March 12, 2026, indicated presence of Pseudomonas aeruginosa.**Treat pool and Resubmit sample.
  7. Demand Inspection

    1 infraction

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Water sample collected on Jan 6, 2026, indicated presence of Total coliforms and Pseudomonas aeruginosa.**Treat pool and Resubmit sample.
  8. Risk Management Inspection

    0 infractions

  9. Demand Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • The most recent bacteriological water sample indicated a presence of total coliform bacteria.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The most recent bacteriological water sample indicated a heterotropic plate count of 140 CFU/mL.
  10. Risk Management Inspection

    0 infractions

  11. Demand Inspection

    1 infraction

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Water sample submitted on November 4, 2025, showed positive isolation of Pseudomonas aeruginosa. **Please treat pool water and resample.
  12. Risk Management Inspection

    0 infractions

  13. Demand Inspection

    1 infraction

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Water sample submitted on October 21, 2025, showed positive isolation of Pseudomonas aeruginosa. **Please treat pool water and resample.
  14. Risk Management Inspection

    0 infractions

  15. Demand Inspection

    1 infraction

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Sample collected on July 15, 2025 indicated presence of pseudomonas. **Please treat the pool and resample.
  16. Risk Management Inspection

    0 infractions

  17. Monitoring Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Flow rate exceeded max flow rate of 61GPM, flow meter was reading 70 GPM. Filtration rate was 14.3 GPM/sqft. Requirement:- Please adjust flow rate so it does not exceed the max flow rate for the filter.
  18. Demand Inspection

    4 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Water sample submitted on April 1, 2025, showed positive isolation of Pseudomonas aeruginosa. **Please treat pool water and resample.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample submitted on April 1, 2025, showed HPC count of 2800 CFU/ml. **Please treat pool water and resample.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The combine chlorine (CC) value of the pool water was measured at 2.74ppm.**It is recommended to maintain CC value below 1.0ppm
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • 1. There was no pool safety plan available for the pool.**Develop a pool safety plan.
  19. Monitoring Inspection

    2 infractions

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The combine chlorine (CC) value of the pool water was measured at 2.74ppm.**It is recommended to maintain CC value below 1.0ppm
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • 1. There was no pool safety plan available for the pool.**Develop a pool safety plan.
  20. Demand Inspection

    3 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Water sample submitted on December 31, 2024, showed positive isolation of Pseudomonas aeruginosa. **Please treat pool water and resample.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample submitted on December 31, 2024, showed HPC count of 9160 CFU/ml. **Please treat pool water and resample.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • 1. Flow rate on anti-entrapment plan was not properly calculated. **Please ensure plan is updated with maximum flow rate.2. The incident response plan available on site for water contamination incident was incomplete.**Modify current plan in place to show actions to be taken in the event of solid/diarrheal fecal, vomit or blood contamination.3. The sanitation plan available on site was incomplete. **Please modify plan to show frequency of cleaning, chemicals used and person responsible. Include a sanitation log that is completed to indicate cleaning is done.4. There was no pool safety plan available for the pool.**Develop a pool safety plan.
  21. Demand Inspection

    1 infraction

    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • 1. Flow rate on anti-entrapment plan was not properly calculated. **Please ensure plan is updated with maximum flow rate.2. The incident response plan available on site for water contamination incident was incomplete.**Modify current plan in place to show actions to be taken in the event of solid/diarrheal fecal, vomit or blood contamination.3. The sanitation plan available on site was incomplete. **Please modify plan to show frequency of cleaning, chemicals used and person responsible. Include a sanitation log that is completed to indicate cleaning is done.4. There was no pool safety plan available for the pool.**Develop a pool safety plan.
  22. Monitoring Inspection

    1 infraction

    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • 1. Flow rate on anti-entrapment plan was not properly calculated. **Please ensure plan is updated with maximum flow rate.2. The incident response plan available on site for water contamination incident was incomplete.**Modify current plan in place to show actions to be taken in the event of solid/diarrheal fecal, vomit or blood contamination.3. The sanitation plan available on site was incomplete. **Please modify plan to show frequency of cleaning, chemicals used and person responsible. Include a sanitation log that is completed to indicate cleaning is done.4. There was no pool safety plan available for the pool.**Develop a pool safety plan.
  23. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample submitted on August 20, 2024, showed HPC count of 110 CFU/ml.**Please treat pool water and resample.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • 1. Flow rate on anti-entrapment plan was not properly calculated. Please ensure plan is updated with maximum flow rate.2. No incident response plan was on-site for water contamination incidents. Please ensure there is a written policy for actions to take after contamination. 3. No sanitation plan was available for the pool.**Ensure sanitation plan is developed to indicate chemicals used for cleaning the pool and cleaning schedule
  24. Demand Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Sample collected on July 09, 2024 indicated presence of pseudomonas. **Please treat the pool and resample.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • 1. Flow rate on anti-entrapment plan was not properly calculated. Please ensure plan is updated with maximum flow rate.2. No incident response plan was on-site for water contamination incidents. Please ensure there is a written policy for actions to take after contamination. 3. No sanitation plan was available for the pool.**Ensure sanitation plan is developed to indicate chemicals used for cleaning the pool and cleaning schedule
  25. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample collected on May 07, 2024 indicate high levels of HPC - 240 CFU/ml. **Please treat pool water and resample.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • 1. Flow rate on anti-entrapment plan was not properly calculated. Please ensure plan is updated with maximum flow rate.2. No incident response plan was on-site for water contamination incidents. Please ensure there is a written policy for actions to take after contamination. 3. No sanitation plan was available for the pool.**Ensure sanitation plan is developed to indicate chemicals used for cleaning the pool and cleaning schedule
  26. Demand Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Total coliform was present in the pool sample submitted on March 05, 2024.**Please treat pool water and resample.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • 1. Flow rate on anti-entrapment plan was not properly calculated. Please ensure plan is updated with maximum flow rate.2. No incident response plan was on-site for water contamination incidents. Please ensure there is a written policy for actions to take after contamination. 3. No sanitation plan was available for the pool.**Ensure sanitation plan is developed to indicate chemicals used for cleaning the pool and cleaning schedule
  27. Monitoring Inspection

    1 infraction

    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • 1. Flow rate on anti-entrapment plan was not properly calculated. Please ensure plan is updated with maximum flow rate.2. No incident response plan was on-site for water contamination incidents. Please ensure there is a written policy for actions to take after contamination. 3. No sanitation plan was available for the pool.**Ensure sanitation plan is developed to indicate chemicals used for cleaning the pool and cleaning schedule
  28. Demand Inspection

    1 infraction

    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • 1. Flow rate on anti-entrapment plan was not properly calculated. Please ensure plan is updated with maximum flow rate.2. No incident response plan was on-site for water contamination incidents. Please ensure there is a written policy for actions to take after contamination.
  29. Demand Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Water sample submitted on October 10, 2023 show presence of Pseudomonas aeruginosa.**Please treat hot tub and resample water.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • 1. Flow rate on anti-entrapment plan was not properly calculated. Please ensure plan is updated with maximum flow rate.2. No incident response plan was on-site for water contamination incidents. Please ensure there is a written policy for actions to take after contamination.
  30. Demand Inspection

    1 infraction

    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • 1. Flow rate on anti-entrapment plan was not properly calculated. Please ensure plan is updated with maximum flow rate.2. No incident response plan was on-site for water contamination incidents. Please ensure there is a written policy for actions to take after contamination.