Fairway Estates Condominium Corporation - Whirlpool

5040 53 Street Sylvan Lake AB T4S 0A1 · Aquatic Facility

13 inspections

  1. Monitoring Inspection

    0 infractions

  2. Risk Management Inspection

    1 infraction

    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • The circulation plan has been completed, needs a date adjustment and resubmission. The hydro jet plan has not yet been provided.Please have both plans completed and resubmitted.
  3. Monitoring Inspection

    2 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Flow rate was reading 44.6 GPM. This exceeds the limit for the high-rate sand filter. The maximum rate of filtration allowed in accordance with section 3.3.1(b) of the Pool Standards states: The maximum rate of filtration for a high rate sand filter must not be:b) greater than 8.5 litres per second per square meter (12.5 US gallons per minute per square foot) for a whirlpool. Based on this requirement the existing filter must be run no greater than 2.2 sq ft x 12.5 US gallons = 27.5 GPM. Have the flow rate reduced to ensure the max rate of filtration is not exceeded.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • The circulation plan has been completed, needs a date adjustment and resubmission. The hydro jet plan has not yet been provided.Please have both plans completed and resubmitted.
  4. Monitoring Inspection

    5 infractions

    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • Free available chlorine was tested and found to be 1.13 ppm. Operator raised the chlorine to 2.0 ppm. pH 7.3
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Total Alkalinity was found to be out of range. TA was lowered to 64 ppm. Please ensure the total alkalinity is kept between 60 - 180 ppm in accordance with the Public Swimming Pools Regulation and Pool Standards Section 4.5.1
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Flow rate was reading 46.3 GPM. This exceeds the limit for the high rate sand filter. The maximum rate of filtration allowed in accordance with section 3.3.1(b) of the Pool Standards states: The maximum rate of filtration for a high rate sand filter must not be:b) greater than 8.5 litres per second per square meter (12.5 US gallons per minute per square foot) for a whirlpool. Based on this requirement the existing filter must be run no greater than 2.2 sq ft x 12.5 US gallons = 27.5 GPM. Have the flow rate reduced to ensure the max rate of filtration is not exceeded.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • Operator was provided a template that includes all records that are required, but the following are still not being recorded: 1. time of readings and observations - this section is being left blank. Sec. 5.1(a) of the Pool Standards2. steam room temperature - blank for the month of November. Unknown how long the steam room has been out of service. Sec. 5.1(j)3. quantity of chemicals used. Sec. 5.1(h)4. automated pH reading is not being recorded. Sec. 5.1(c)5. water temperature. Sec. 5.1(d)
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Anti-entrapment plan present does not include both pumps that service the pool. Plan must also include information on both types of covers in the pool. The plan that is present does not appear to have the cover plate information for the make and model that are installed. Please submit updated plans that accounts for both pumps, all covers and all other required information.
  5. Monitoring Inspection

    3 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Flow rate was reading at 45.6 GPM. High rate sand filter specifications is max design flow of 44 GPM.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • Records were missing the following information: 1. time of readings and observations2. steam room temperature3. quantity of chemicals when added4. pH readings: there is one pH reading being recorded, it was unclear if this was the manual test reading or the automated reading. Both are required. 5. water temperature
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Anti-entrapment plan present does not include both pumps that service the pool. Plan must also include information on both types of covers in the pool. Please submit an updated plan that accounts for both pumps and all cover plate information.
  6. Risk Management Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Operator indicated by phone that the new ORP reader had arrived and was installed. ORP reading 703, pH reading 8.36. Operator indicated the sensors are no longer accurate and cannot be calibrated. A new system has been ordered.
  7. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • HPC count at 460 in sample collected Feb. 13.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Operator indicated by phone that the new ORP reader had arrived and was installed. ORP reading 703, pH reading 8.36. Operator indicated the sensors are no longer accurate and cannot be calibrated. A new system has been ordered.
  8. Risk Management Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Operator indicated by phone that the new ORP reader had arrived and was installed. ORP reading 703, pH reading 8.36. Operator indicated the sensors are no longer accurate and cannot be calibrated. A new system has been ordered.
  9. Demand Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Sample results from Dec. 5 collection were as follows: TC: absentPA: isolatedHPC: <10
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Operator indicated by phone that the new ORP reader had arrived and was installed. ORP reading 703, pH reading 8.36. Operator indicated the sensors are no longer accurate and cannot be calibrated. A new system has been ordered.
  10. Risk Management Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Operator indicated by phone that the new ORP reader had arrived and was installed. ORP reading 703, pH reading 8.36. Operator indicated the sensors are no longer accurate and cannot be calibrated. A new system has been ordered.
  11. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • HPC was at 750 in sample collected Oct. 3.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Operator indicated by phone that the new ORP reader had arrived and was installed. ORP reading 703, pH reading 8.36. Operator indicated the sensors are no longer accurate and cannot be calibrated. A new system has been ordered.
  12. Risk Management Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Operator indicated by phone that the new ORP reader had arrived and was installed. ORP reading 703, pH reading 8.36. Operator indicated the sensors are no longer accurate and cannot be calibrated. A new system has been ordered.
  13. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Results from sample collected Aug. 22 had the following:TC absentPA not isolatedHPC 120
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Operator indicated by phone that the new ORP reader had arrived and was installed. ORP reading 703, pH reading 8.36. Operator indicated the sensors are no longer accurate and cannot be calibrated. A new system has been ordered.