Genesis Place - Diving Pool

800 East Lake Boulevard NE Airdrie AB T4A 2K9 · Aquatic Facility

19 inspections

  1. Risk Management Inspection

    1 infraction

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • ***ONGOING VIOLATION***Total Alkalinity was measured at 44 ppm. - Maintain Alkalinity between 60 - 180 ppm.
  2. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample was not processed due to incorrect date.Please resubmit sample to the lab
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • ***ONGOING VIOLATION***Total Alkalinity was measured at 44 ppm. - Maintain Alkalinity between 60 - 180 ppm.
  3. Risk Management Inspection

    1 infraction

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • ***ONGOING VIOLATION***Total Alkalinity was measured at 44 ppm. - Maintain Alkalinity between 60 - 180 ppm.
  4. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample submitted on March 31st indicated an elevated HPC count of 120CFU/ml. **Resubmit sample.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • ***ONGOING VIOLATION***Total Alkalinity was measured at 44 ppm. - Maintain Alkalinity between 60 - 180 ppm.
  5. Risk Management Inspection

    1 infraction

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • ***ONGOING VIOLATION***Total Alkalinity was measured at 44 ppm. - Maintain Alkalinity between 60 - 180 ppm.
  6. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample submitted on Feb 3, 2026 was not processed because the bottle was missing the ID number. **Resubmit sample
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • ***ONGOING VIOLATION***Total Alkalinity was measured at 44 ppm. - Maintain Alkalinity between 60 - 180 ppm.
  7. Monitoring Inspection

    1 infraction

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • ***ONGOING VIOLATION***Total Alkalinity was measured at 44 ppm. - Maintain Alkalinity between 60 - 180 ppm.
  8. Demand Inspection

    3 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample submitted on Oct 6th was not processed by the lab as sample had no identification number. **Resubmit sample.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • ***ONGOING VIOLATION***Total Alkalinity was measured at 28 ppm. - Maintain Alkalinity between 60 - 180 ppm.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The combined chlorine level was measured at 1.19ppm**It is recommended to maintain the combined chlorine level below 1.0ppm at all times.
  9. Monitoring Inspection

    2 infractions

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • ***ONGOING VIOLATION***Total Alkalinity was measured at 28 ppm. - Maintain Alkalinity between 60 - 180 ppm.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The combined chlorine level was measured at 1.19ppm**It is recommended to maintain the combined chlorine level below 1.0ppm at all times.
  10. Monitoring Inspection

    2 infractions

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • ***ONGOING VIOLATION***Total Alkalinity was measured at 28 ppm. - Maintain Alkalinity between 60 - 180 ppm.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The combined chlorine level was measured at 1.19ppm**It is recommended to maintain the combined chlorine level below 1.0ppm at all times.
  11. Monitoring Inspection

    1 infraction

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • ***ONGOING VIOLATION***Total Alkalinity was measured at 36 ppm. - Maintain Alkalinity between 60 - 180 ppm.
  12. Monitoring Inspection

    2 infractions

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • ***ONGOING VIOLATION***Total Alkalinity was measured at 39 ppm. - Maintain Alkalinity between 60 - 180 ppm.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Combined chlorine was recorded at 3.68 ppm.- Combined chlorine should be maintained at the lowest level possible.-It is recommended to keep combined chlorine value below 1.0ppm
  13. Demand Inspection

    1 infraction

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Alkalinity was measured at 39 ppm. **Maintain Alkalinity between 60 - 180 ppm.
  14. Demand Inspection

    1 infraction

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Alkalinity was measured at 39 ppm. **Maintain Alkalinity between 60 - 180 ppm.
  15. Monitoring Inspection

    1 infraction

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Alkalinity was measured at 39 ppm. **Maintain Alkalinity between 60 - 180 ppm.
  16. Risk Management Inspection

    0 infractions

  17. Risk Management Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow meter for the dive pool was not working.**Please ensure the flow meter is repaired so that it is in working order.
  18. Monitoring Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow meter for the dive pool was not working.**Please ensure the flow meter is repaired so that it is in working order.
  19. Demand Inspection

    0 infractions