Genesis Place - Main Pool
800 East Lake Boulevard NE Airdrie AB T4A 2K9 · Aquatic Facility
28 inspections
- Risk Management Inspection
1 infraction
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Alkalinity was measured at 0 ppm. **Maintain Alkalinity between 60 - 180 ppm.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample submitted on June 16th was not processed due to incorrect date.**Resubmit sample to the lab
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Alkalinity was measured at 0 ppm. **Maintain Alkalinity between 60 - 180 ppm.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
1 infraction
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Alkalinity was measured at 0 ppm. **Maintain Alkalinity between 60 - 180 ppm.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample submitted on March 17th indicated an elevated HPC count of 120CFU/ml. **Resubmit sample.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Alkalinity was measured at 0 ppm. **Maintain Alkalinity between 60 - 180 ppm.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
1 infraction
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Alkalinity was measured at 0 ppm. **Maintain Alkalinity between 60 - 180 ppm.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample submitted on January 27, 2026, indicated presence of 560 CFU/ml of HPC. **Treat pool water and resubmit sample.Water sample submitted on Feb 3, 2026 was not processed because the bottle was missing the ID number. **Resubmit sample
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Alkalinity was measured at 0 ppm. **Maintain Alkalinity between 60 - 180 ppm.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample submitted on January 27, 2026, indicated presence of 560 CFU/ml of HPC. **Treat pool water and resubmit sample.Water sample submitted on Feb 3, 2026 was not processed because the bottle was missing the ID number. **Resubmit sample
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Alkalinity was measured at 0 ppm. **Maintain Alkalinity between 60 - 180 ppm.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The combined chlorine level was measured at 2.15ppm**It is recommended to maintain the combined chlorine level below 1.0ppm at all times.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample submitted on January 27, 2026, indicated presence of 560 CFU/ml of HPC. **Treat pool water and resubmit sample.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Alkalinity was measured at 0 ppm. **Maintain Alkalinity between 60 - 180 ppm.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The combined chlorine level was measured at 2.15ppm**It is recommended to maintain the combined chlorine level below 1.0ppm at all times.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Monitoring Inspection
2 infractions
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The combined chlorine level was measured at 2.15ppm**It is recommended to maintain the combined chlorine level below 1.0ppm at all times.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Alkalinity was measured at 0 ppm. **Maintain Alkalinity between 60 - 180 ppm.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Monitoring Inspection
1 infraction
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Alkalinity was measured at 26 ppm. **Maintain Alkalinity between 60 - 180 ppm.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Monitoring Inspection
1 infraction
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Alkalinity was measured at 26 ppm. **Maintain Alkalinity between 60 - 180 ppm.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
1 infraction
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Alkalinity was measured at 40 ppm. **Maintain Alkalinity between 60 - 180 ppm.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The most recent bacteriological water sample indicated an exceedance of heterotrophic bacteria (580 CFU/100mL).
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Alkalinity was measured at 40 ppm. **Maintain Alkalinity between 60 - 180 ppm.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Monitoring Inspection
1 infraction
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Alkalinity was measured at 40 ppm. **Maintain Alkalinity between 60 - 180 ppm.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- HPC level of the pool water sample submitted on November 5, 2024 was measured at 1040 CFU/ml Please treat pool water and resample.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Alkalinity was measured at 20 ppm. **Maintain Alkalinity between 60 - 180 ppm.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- HPC level of the pool water sample submitted on Oct 8, 2024 was measured at 6440 CFU/ml Please treat pool water and resample.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Alkalinity was measured at 20 ppm. **Maintain Alkalinity between 60 - 180 ppm.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- HPC level of the pool water sample submitted on Oct 1, 2024 was measured at 2620 CFU/ml Please treat pool water and resample.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Alkalinity was measured at 20 ppm. **Maintain Alkalinity between 60 - 180 ppm.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- HPC level of the pool water sample submitted on Sept 3rd, 2024, was measured at 920 CFU/ml.Please treat pool water and resample.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Alkalinity was measured at 20 ppm. **Maintain Alkalinity between 60 - 180 ppm.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Monitoring Inspection
1 infraction
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Alkalinity was measured at 20 ppm. **Maintain Alkalinity between 60 - 180 ppm.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- HPC level of the pool water sample submitted on March 22nd, 2024, was measured at 180 CFU/ml.Please treat pool water and resample.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Alkalinity was measured at 47 ppm. **Maintain Alkalinity between 60 - 180 ppm.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- HPC level of the pool water sample submitted on March 19th, 2024, was measured at 670 CFU/ml.Please treat pool water and resample.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Alkalinity was measured at 47 ppm. **Maintain Alkalinity between 60 - 180 ppm.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Monitoring Inspection
1 infraction
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Alkalinity was measured at 47 ppm. **Maintain Alkalinity between 60 - 180 ppm.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
1 infraction
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Alkalinity was measured at 54 ppm. **Maintain Alkalinity between 60 - 180 ppm.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- HPC level of the pool water sample submitted on Jan 23rd, 2024, was measured at 230 CFU/ml.Please treat pool water and resample.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Alkalinity was measured at 54 ppm. **Maintain Alkalinity between 60 - 180 ppm.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The flow meter for the main pool was not working.**Please ensure the flow meter is repaired so that it is in working order.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- HPC level of the pool water sample submitted on Jan 23rd, 2024, was measured at 230 CFU/ml.Please treat pool water and resample.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Alkalinity was measured at 54 ppm. **Maintain Alkalinity between 60 - 180 ppm.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The flow meter for the main pool was not working.**Please ensure the flow meter is repaired so that it is in working order.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- HPC level of the pool water sample submitted on Dec 19th, 2023, was measured at 230 CFU/ml.Please treat pool water and resample.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Alkalinity was measured at 54 ppm. **Maintain Alkalinity between 60 - 180 ppm.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The flow meter for the main pool was not working.**Please ensure the flow meter is repaired so that it is in working order.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Monitoring Inspection
2 infractions
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Alkalinity was measured at 54 ppm. **Maintain Alkalinity between 60 - 180 ppm.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The flow meter for the main pool was not working.**Please ensure the flow meter is repaired so that it is in working order.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
1 infraction
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Alkalinity was 50 ppm. Alkalinity is required to be between 60 - 180 ppm.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?