Genesis Place - Main Pool

800 East Lake Boulevard NE Airdrie AB T4A 2K9 · Aquatic Facility

28 inspections

  1. Risk Management Inspection

    1 infraction

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Alkalinity was measured at 0 ppm. **Maintain Alkalinity between 60 - 180 ppm.
  2. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample submitted on June 16th was not processed due to incorrect date.**Resubmit sample to the lab
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Alkalinity was measured at 0 ppm. **Maintain Alkalinity between 60 - 180 ppm.
  3. Risk Management Inspection

    1 infraction

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Alkalinity was measured at 0 ppm. **Maintain Alkalinity between 60 - 180 ppm.
  4. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample submitted on March 17th indicated an elevated HPC count of 120CFU/ml. **Resubmit sample.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Alkalinity was measured at 0 ppm. **Maintain Alkalinity between 60 - 180 ppm.
  5. Risk Management Inspection

    1 infraction

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Alkalinity was measured at 0 ppm. **Maintain Alkalinity between 60 - 180 ppm.
  6. Risk Management Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample submitted on January 27, 2026, indicated presence of 560 CFU/ml of HPC. **Treat pool water and resubmit sample.Water sample submitted on Feb 3, 2026 was not processed because the bottle was missing the ID number. **Resubmit sample
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Alkalinity was measured at 0 ppm. **Maintain Alkalinity between 60 - 180 ppm.
  7. Demand Inspection

    3 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample submitted on January 27, 2026, indicated presence of 560 CFU/ml of HPC. **Treat pool water and resubmit sample.Water sample submitted on Feb 3, 2026 was not processed because the bottle was missing the ID number. **Resubmit sample
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Alkalinity was measured at 0 ppm. **Maintain Alkalinity between 60 - 180 ppm.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The combined chlorine level was measured at 2.15ppm**It is recommended to maintain the combined chlorine level below 1.0ppm at all times.
  8. Demand Inspection

    3 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample submitted on January 27, 2026, indicated presence of 560 CFU/ml of HPC. **Treat pool water and resubmit sample.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Alkalinity was measured at 0 ppm. **Maintain Alkalinity between 60 - 180 ppm.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The combined chlorine level was measured at 2.15ppm**It is recommended to maintain the combined chlorine level below 1.0ppm at all times.
  9. Monitoring Inspection

    2 infractions

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The combined chlorine level was measured at 2.15ppm**It is recommended to maintain the combined chlorine level below 1.0ppm at all times.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Alkalinity was measured at 0 ppm. **Maintain Alkalinity between 60 - 180 ppm.
  10. Monitoring Inspection

    1 infraction

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Alkalinity was measured at 26 ppm. **Maintain Alkalinity between 60 - 180 ppm.
  11. Monitoring Inspection

    1 infraction

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Alkalinity was measured at 26 ppm. **Maintain Alkalinity between 60 - 180 ppm.
  12. Risk Management Inspection

    1 infraction

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Alkalinity was measured at 40 ppm. **Maintain Alkalinity between 60 - 180 ppm.
  13. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The most recent bacteriological water sample indicated an exceedance of heterotrophic bacteria (580 CFU/100mL).
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Alkalinity was measured at 40 ppm. **Maintain Alkalinity between 60 - 180 ppm.
  14. Monitoring Inspection

    1 infraction

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Alkalinity was measured at 40 ppm. **Maintain Alkalinity between 60 - 180 ppm.
  15. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • HPC level of the pool water sample submitted on November 5, 2024 was measured at 1040 CFU/ml Please treat pool water and resample.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Alkalinity was measured at 20 ppm. **Maintain Alkalinity between 60 - 180 ppm.
  16. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • HPC level of the pool water sample submitted on Oct 8, 2024 was measured at 6440 CFU/ml Please treat pool water and resample.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Alkalinity was measured at 20 ppm. **Maintain Alkalinity between 60 - 180 ppm.
  17. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • HPC level of the pool water sample submitted on Oct 1, 2024 was measured at 2620 CFU/ml Please treat pool water and resample.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Alkalinity was measured at 20 ppm. **Maintain Alkalinity between 60 - 180 ppm.
  18. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • HPC level of the pool water sample submitted on Sept 3rd, 2024, was measured at 920 CFU/ml.Please treat pool water and resample.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Alkalinity was measured at 20 ppm. **Maintain Alkalinity between 60 - 180 ppm.
  19. Monitoring Inspection

    1 infraction

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Alkalinity was measured at 20 ppm. **Maintain Alkalinity between 60 - 180 ppm.
  20. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • HPC level of the pool water sample submitted on March 22nd, 2024, was measured at 180 CFU/ml.Please treat pool water and resample.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Alkalinity was measured at 47 ppm. **Maintain Alkalinity between 60 - 180 ppm.
  21. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • HPC level of the pool water sample submitted on March 19th, 2024, was measured at 670 CFU/ml.Please treat pool water and resample.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Alkalinity was measured at 47 ppm. **Maintain Alkalinity between 60 - 180 ppm.
  22. Monitoring Inspection

    1 infraction

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Alkalinity was measured at 47 ppm. **Maintain Alkalinity between 60 - 180 ppm.
  23. Risk Management Inspection

    1 infraction

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Alkalinity was measured at 54 ppm. **Maintain Alkalinity between 60 - 180 ppm.
  24. Risk Management Inspection

    3 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • HPC level of the pool water sample submitted on Jan 23rd, 2024, was measured at 230 CFU/ml.Please treat pool water and resample.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Alkalinity was measured at 54 ppm. **Maintain Alkalinity between 60 - 180 ppm.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow meter for the main pool was not working.**Please ensure the flow meter is repaired so that it is in working order.
  25. Demand Inspection

    3 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • HPC level of the pool water sample submitted on Jan 23rd, 2024, was measured at 230 CFU/ml.Please treat pool water and resample.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Alkalinity was measured at 54 ppm. **Maintain Alkalinity between 60 - 180 ppm.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow meter for the main pool was not working.**Please ensure the flow meter is repaired so that it is in working order.
  26. Demand Inspection

    3 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • HPC level of the pool water sample submitted on Dec 19th, 2023, was measured at 230 CFU/ml.Please treat pool water and resample.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Alkalinity was measured at 54 ppm. **Maintain Alkalinity between 60 - 180 ppm.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow meter for the main pool was not working.**Please ensure the flow meter is repaired so that it is in working order.
  27. Monitoring Inspection

    2 infractions

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Alkalinity was measured at 54 ppm. **Maintain Alkalinity between 60 - 180 ppm.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow meter for the main pool was not working.**Please ensure the flow meter is repaired so that it is in working order.
  28. Demand Inspection

    1 infraction

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Alkalinity was 50 ppm. Alkalinity is required to be between 60 - 180 ppm.