Genesis Place - Main Pool

800 East Lake Boulevard NE Airdrie AB T4A 2K9 · Aquatic Facility

Inspection summary

Genesis Place - Main Pool has been inspected 27 times by Alberta Health Services (Environmental Public Health) since November 23, 2023. The most recent inspection, on June 26, 2026, recorded 1 infraction.

None of the 27 inspections on record were free of infractions. In the past 12 months there were 9 inspections with 17 infractions recorded. The higher-risk findings here relate to: Chemicals and toxic substances and Pool and spa water quality.

The number of infractions per inspection has stayed roughly the same over time.

What these findings mean

Health authorities word their findings differently, so we group them by what they mean for the people using the facility. Higher-risk findings are the ones that could directly cause illness or injury, such as water that is not properly treated.

  • Chemicals and toxic substancesHigher risk

    Pool chemicals such as chlorine and acid must be labelled, stored apart from each other and handled safely. Mixing them by mistake can release toxic gas, so storage and handling problems are treated seriously.

    Recorded 30 times across 27 separate inspections, most recently on June 26, 2026. For example: Is the chemical quality of the water in this pool satisfactory (Non-Critical)?

  • Pool and spa water qualityHigher risk

    For pools, spas and splash pads, inspectors test disinfectant levels, pH and water clarity, and check safety equipment. Water that is not properly treated can spread skin, ear and stomach infections.

    Recorded 19 times across 16 separate inspections, most recently on June 17, 2026. For example: Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?

About this data

These results come from Alberta Health Services (Environmental Public Health), which inspects food premises and other public facilities in this area. We republish the authority's public disclosure data and refresh it regularly; the official record is the final word.

27 inspections

  1. Risk Management Inspection

    1 infraction

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Alkalinity was measured at 0 ppm. **Maintain Alkalinity between 60 - 180 ppm.
  2. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample submitted on June 16th was not processed due to incorrect date.**Resubmit sample to the lab
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Alkalinity was measured at 0 ppm. **Maintain Alkalinity between 60 - 180 ppm.
  3. Risk Management Inspection

    1 infraction

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Alkalinity was measured at 0 ppm. **Maintain Alkalinity between 60 - 180 ppm.
  4. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample submitted on March 17th indicated an elevated HPC count of 120CFU/ml. **Resubmit sample.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Alkalinity was measured at 0 ppm. **Maintain Alkalinity between 60 - 180 ppm.
  5. Risk Management Inspection

    1 infraction

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Alkalinity was measured at 0 ppm. **Maintain Alkalinity between 60 - 180 ppm.
  6. Risk Management Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample submitted on January 27, 2026, indicated presence of 560 CFU/ml of HPC. **Treat pool water and resubmit sample.Water sample submitted on Feb 3, 2026 was not processed because the bottle was missing the ID number. **Resubmit sample
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Alkalinity was measured at 0 ppm. **Maintain Alkalinity between 60 - 180 ppm.
  7. Demand Inspection

    3 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample submitted on January 27, 2026, indicated presence of 560 CFU/ml of HPC. **Treat pool water and resubmit sample.Water sample submitted on Feb 3, 2026 was not processed because the bottle was missing the ID number. **Resubmit sample
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Alkalinity was measured at 0 ppm. **Maintain Alkalinity between 60 - 180 ppm.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The combined chlorine level was measured at 2.15ppm**It is recommended to maintain the combined chlorine level below 1.0ppm at all times.
  8. Demand Inspection

    3 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample submitted on January 27, 2026, indicated presence of 560 CFU/ml of HPC. **Treat pool water and resubmit sample.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Alkalinity was measured at 0 ppm. **Maintain Alkalinity between 60 - 180 ppm.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The combined chlorine level was measured at 2.15ppm**It is recommended to maintain the combined chlorine level below 1.0ppm at all times.
  9. Monitoring Inspection

    2 infractions

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The combined chlorine level was measured at 2.15ppm**It is recommended to maintain the combined chlorine level below 1.0ppm at all times.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Alkalinity was measured at 0 ppm. **Maintain Alkalinity between 60 - 180 ppm.
  10. Monitoring Inspection

    1 infraction

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Alkalinity was measured at 26 ppm. **Maintain Alkalinity between 60 - 180 ppm.
  11. Monitoring Inspection

    1 infraction

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Alkalinity was measured at 26 ppm. **Maintain Alkalinity between 60 - 180 ppm.
  12. Risk Management Inspection

    1 infraction

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Alkalinity was measured at 40 ppm. **Maintain Alkalinity between 60 - 180 ppm.
  13. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The most recent bacteriological water sample indicated an exceedance of heterotrophic bacteria (580 CFU/100mL).
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Alkalinity was measured at 40 ppm. **Maintain Alkalinity between 60 - 180 ppm.
  14. Monitoring Inspection

    1 infraction

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Alkalinity was measured at 40 ppm. **Maintain Alkalinity between 60 - 180 ppm.
  15. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • HPC level of the pool water sample submitted on November 5, 2024 was measured at 1040 CFU/ml Please treat pool water and resample.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Alkalinity was measured at 20 ppm. **Maintain Alkalinity between 60 - 180 ppm.
  16. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • HPC level of the pool water sample submitted on Oct 8, 2024 was measured at 6440 CFU/ml Please treat pool water and resample.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Alkalinity was measured at 20 ppm. **Maintain Alkalinity between 60 - 180 ppm.
  17. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • HPC level of the pool water sample submitted on Oct 1, 2024 was measured at 2620 CFU/ml Please treat pool water and resample.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Alkalinity was measured at 20 ppm. **Maintain Alkalinity between 60 - 180 ppm.
  18. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • HPC level of the pool water sample submitted on Sept 3rd, 2024, was measured at 920 CFU/ml.Please treat pool water and resample.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Alkalinity was measured at 20 ppm. **Maintain Alkalinity between 60 - 180 ppm.
  19. Monitoring Inspection

    1 infraction

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Alkalinity was measured at 20 ppm. **Maintain Alkalinity between 60 - 180 ppm.
  20. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • HPC level of the pool water sample submitted on March 22nd, 2024, was measured at 180 CFU/ml.Please treat pool water and resample.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Alkalinity was measured at 47 ppm. **Maintain Alkalinity between 60 - 180 ppm.
  21. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • HPC level of the pool water sample submitted on March 19th, 2024, was measured at 670 CFU/ml.Please treat pool water and resample.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Alkalinity was measured at 47 ppm. **Maintain Alkalinity between 60 - 180 ppm.
  22. Monitoring Inspection

    1 infraction

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Alkalinity was measured at 47 ppm. **Maintain Alkalinity between 60 - 180 ppm.
  23. Risk Management Inspection

    1 infraction

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Alkalinity was measured at 54 ppm. **Maintain Alkalinity between 60 - 180 ppm.
  24. Risk Management Inspection

    3 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • HPC level of the pool water sample submitted on Jan 23rd, 2024, was measured at 230 CFU/ml.Please treat pool water and resample.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Alkalinity was measured at 54 ppm. **Maintain Alkalinity between 60 - 180 ppm.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow meter for the main pool was not working.**Please ensure the flow meter is repaired so that it is in working order.
  25. Demand Inspection

    3 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • HPC level of the pool water sample submitted on Jan 23rd, 2024, was measured at 230 CFU/ml.Please treat pool water and resample.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Alkalinity was measured at 54 ppm. **Maintain Alkalinity between 60 - 180 ppm.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow meter for the main pool was not working.**Please ensure the flow meter is repaired so that it is in working order.
  26. Demand Inspection

    3 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • HPC level of the pool water sample submitted on Dec 19th, 2023, was measured at 230 CFU/ml.Please treat pool water and resample.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Alkalinity was measured at 54 ppm. **Maintain Alkalinity between 60 - 180 ppm.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow meter for the main pool was not working.**Please ensure the flow meter is repaired so that it is in working order.
  27. Monitoring Inspection

    2 infractions

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Alkalinity was measured at 54 ppm. **Maintain Alkalinity between 60 - 180 ppm.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow meter for the main pool was not working.**Please ensure the flow meter is repaired so that it is in working order.

Nearby inspected facilities