Goliath's Saunatel - Whirlpool

LOWER LVL - 308 17 Avenue SW Calgary AB T2S 0A8 · Aquatic Facility

Inspection summary

Goliath's Saunatel - Whirlpool has been inspected 20 times by Alberta Health Services (Environmental Public Health) since March 11, 2024. The most recent inspection, on October 8, 2026, recorded 2 infractions.

None of the 20 inspections on record were free of infractions. In the past 12 months there were 12 inspections with 21 infractions recorded. The higher-risk findings here relate to: Pool and spa water quality and Chemicals and toxic substances.

The number of infractions per inspection has stayed roughly the same over time.

What these findings mean

Health authorities word their findings differently, so we group them by what they mean for the people using the facility. Higher-risk findings are the ones that could directly cause illness or injury, such as water that is not properly treated.

  • Pool and spa water qualityHigher risk

    For pools, spas and splash pads, inspectors test disinfectant levels, pH and water clarity, and check safety equipment. Water that is not properly treated can spread skin, ear and stomach infections.

    Recorded 12 times across 11 separate inspections, most recently on September 3, 2026. For example: Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?

  • Chemicals and toxic substancesHigher risk

    Pool chemicals such as chlorine and acid must be labelled, stored apart from each other and handled safely. Mixing them by mistake can release toxic gas, so storage and handling problems are treated seriously.

    Recorded 10 times across 10 separate inspections, most recently on October 8, 2026. For example: Is the chemical quality of the water in this pool satisfactory (Non-Critical)?

  • Food safety training and certificationLower risk

    Many jurisdictions require trained pool operators and certified lifeguards. These findings mean required training, certification or staffing records were missing at the time of inspection.

    Recorded 13 times across 13 separate inspections, most recently on October 8, 2026. For example: Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?

About this data

These results come from Alberta Health Services (Environmental Public Health), which inspects food premises and other public facilities in this area. We republish the authority's public disclosure data and refresh it regularly; the official record is the final word.

20 inspections

  1. Demand Inspection

    2 infractions

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • 1. Combined chlorine tested high, at 2.68 ppm. - Maintain the combined chlorine at the lowest possible level. Recommended below 1 ppm. - Add more fresh water to lower the combined chlorine level. - Ensure that patrons take shower before using the whirlpool.- Drain, clean and disinfect whirlpool regularly.2. Total alkalinity measured at 27 ppm. - Maintain Total alkalinity between 60-180 ppm.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • The anti-entrapment plan is incomplete. - Provide certificate of compliance for all the drain covers.*Could not locate at the time of inspection*
  2. Risk Management Inspection

    1 infraction

    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • The anti-entrapment plan is incomplete. - Provide certificate of compliance for all the drain covers.
  3. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample submitted to the Provincial Laboratory on Sept 3/26 was not processed due to missing time of collection. - Submit a resample.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • The anti-entrapment plan is incomplete. - Provide certificate of compliance for all the drain covers.
  4. Risk Management Inspection

    1 infraction

    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • The anti-entrapment plan is incomplete. - Provide certificate of compliance for all the drain covers.
  5. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample (26ES-227E00002) collected on August 14th, 2026, was rejected by the lab as the sample was received on a weekend (Aug 15th) without prior approval. Please resample the whirlpool as soon as possible.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • The anti-entrapment plan is incomplete. - Provide certificate of compliance for all the drain covers.
  6. Risk Management Inspection

    1 infraction

    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • The anti-entrapment plan is incomplete. - Provide certificate of compliance for all the drain covers.
  7. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample collected on April 3/26 was not processed as it was received during holidays.- Submit a resample.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • The anti-entrapment plan is incomplete. - Provide certificate of compliance for all the drain covers.
  8. Risk Management Inspection

    1 infraction

    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • The anti-entrapment plan is incomplete. - Provide certificate of compliance for all the drain covers.
  9. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample (26ES-050E00249) collected on Feb 19th, 2026, was rejected by the lab as the identification number on the requisition form did not match the number on the bottle. Please resample the whirlpool as soon as possible.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • The anti-entrapment plan is incomplete. - Provide certificate of compliance for all the drain covers.
  10. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample (26ES-003E00008) collected January 2, 2026, was rejected by the lab as a non-urgent sample was received during the weekend/a holiday without approval (Received January 3, 2026). Please submit another water sample for the hot tub.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • The anti-entrapment plan is incomplete. - Provide certificate of compliance for all the drain covers.
  11. Risk Management Inspection

    1 infraction

    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • The anti-entrapment plan is incomplete. - Provide certificate of compliance for all the drain covers.
  12. Monitoring Inspection

    4 infractions

    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • Manual pH testing was bellow 6.5.- Maintain pH between 6.8-7.6
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • pH readings for automated system's (7.2) and manual (below 6.5) were not consistent. - Manual and automated readings must provide consistent results.- Calibrate the automated system and clean/change probes if needed.
    • 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
      • A cover from an inlet was missing. - Reattach the cover to prevent physical entrapment on a pipe opening.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • The anti-entrapment plan has some missing information. - Review and update the anti-entrapment form.
  13. Risk Management Inspection

    1 infraction

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Inspection on July 18, 2024: Total Alkalinity measured 47ppm. Adjust to 60-180ppm.Repeat violation:Total alkalinity last inspection was measured to be 36 ppm. This inspection it was measured to be 16 ppm.Upon reviewing the testing method with staff, it was determined that improper methodology was being conducted. Titration was occurring without mixing reagent drops into the solution. COMPLETE THE FOLLOWING: - Make the necessary adjustments to maintain the total alkalinity between 60 mg/L and 180 mg/L- Ensure that all testing methods are conducted properly to ensure accurate results.
  14. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample collected on May 1st, 2025, came back unsatisfactory as an elevated HPC of 320CFU/mL was detected.Please re-sample the whirlpool.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Inspection on July 18, 2024: Total Alkalinity measured 47ppm. Adjust to 60-180ppm.Repeat violation:Total alkalinity last inspection was measured to be 36 ppm. This inspection it was measured to be 16 ppm.Upon reviewing the testing method with staff, it was determined that improper methodology was being conducted. Titration was occurring without mixing reagent drops into the solution. COMPLETE THE FOLLOWING: - Make the necessary adjustments to maintain the total alkalinity between 60 mg/L and 180 mg/L- Ensure that all testing methods are conducted properly to ensure accurate results.
  15. Risk Management Inspection

    1 infraction

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Inspection on July 18, 2024: Total Alkalinity measured 47ppm. Adjust to 60-180ppm.Repeat violation:Total alkalinity last inspection was measured to be 36 ppm. This inspection it was measured to be 16 ppm.Upon reviewing the testing method with staff, it was determined that improper methodology was being conducted. Titration was occurring without mixing reagent drops into the solution. COMPLETE THE FOLLOWING: - Make the necessary adjustments to maintain the total alkalinity between 60 mg/L and 180 mg/L- Ensure that all testing methods are conducted properly to ensure accurate results.
  16. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample collected on April 18th, 2025, was rejected by the lab as a non-urgent sample was received during the weekend/a holiday without approval (Received April 18th, 2025). Please submit another sample for the hot tub.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Inspection on July 18, 2024: Total Alkalinity measured 47ppm. Adjust to 60-180ppm.Repeat violation:Total alkalinity last inspection was measured to be 36 ppm. This inspection it was measured to be 16 ppm.Upon reviewing the testing method with staff, it was determined that improper methodology was being conducted. Titration was occurring without mixing reagent drops into the solution. COMPLETE THE FOLLOWING: - Make the necessary adjustments to maintain the total alkalinity between 60 mg/L and 180 mg/L- Ensure that all testing methods are conducted properly to ensure accurate results.
  17. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample collected on January 07th, 2025, was rejected as it was received at the lab more than 24 hours after collection.Please re-sample.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Inspection on July 18, 2024: Total Alkalinity measured 47ppm. Adjust to 60-180ppm.Repeat violation:Total alkalinity last inspection was measured to be 36 ppm. This inspection it was measured to be 16 ppm.Upon reviewing the testing method with staff, it was determined that improper methodology was being conducted. Titration was occurring without mixing reagent drops into the solution. COMPLETE THE FOLLOWING: - Make the necessary adjustments to maintain the total alkalinity between 60 mg/L and 180 mg/L- Ensure that all testing methods are conducted properly to ensure accurate results.
  18. Demand Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Water sample taken Jan 3, 2025 - Pseudomonas isolated.-Treat and resample
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Inspection on July 18, 2024: Total Alkalinity measured 47ppm. Adjust to 60-180ppm.Repeat violation:Total alkalinity last inspection was measured to be 36 ppm. This inspection it was measured to be 16 ppm.Upon reviewing the testing method with staff, it was determined that improper methodology was being conducted. Titration was occurring without mixing reagent drops into the solution. COMPLETE THE FOLLOWING: - Make the necessary adjustments to maintain the total alkalinity between 60 mg/L and 180 mg/L- Ensure that all testing methods are conducted properly to ensure accurate results.
  19. Monitoring Inspection

    1 infraction

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Inspection on July 18, 2024: Total Alkalinity measured 47ppm. Adjust to 60-180ppm.Repeat violation:Total alkalinity last inspection was measured to be 36 ppm. This inspection it was measured to be 16 ppm.Upon reviewing the testing method with staff, it was determined that improper methodology was being conducted. Titration was occurring without mixing reagent drops into the solution. COMPLETE THE FOLLOWING: - Make the necessary adjustments to maintain the total alkalinity between 60 mg/L and 180 mg/L- Ensure that all testing methods are conducted properly to ensure accurate results.
  20. Demand Inspection

    3 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Pseudomonas isolated from water sample taken Mar 8, 2024.-Treat and resample
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • **Repeat Infraction** VIOLATION: Total alkalinity last inspection was measured to be 36 ppm. This inspection it was measured to be 16 ppm.Upon reviewing the testing method with staff, it was determined that improper methodology was being conducted. Titration was occurring without mixing reagent drops into the solution. COMPLETE THE FOLLOWING: - Make the necessary adjustments to maintain the total alkalinity between 60 mg/L and 180 mg/L- Ensure that all testing methods are conducted properly to ensure accurate results.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • ON-GOING VIOLATION: - Written policies and plans are not available. COMPLETE THE FOLLOWING: - Develop written policies and plans in accordance with Sections 10 to 14 of the Pool Standards.