Heritage Inn - Pool

1104 11 Avenue SE High River AB T1V 1P2 · Aquatic Facility

20 inspections

  1. Demand Inspection

    0 infractions

  2. Risk Management Inspection

    0 infractions

  3. Risk Management Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • 2/19. The heat exchanger had been replaced and there was a leak from one of the circulation pipes. Repair pipe leak.
  4. Risk Management Inspection

    3 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • 2/19. The heat exchanger had been replaced and there was a leak from one of the circulation pipes. Repair pipe leak.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • 2/19. 2. The flow meter was replaced and was operational. 1. Both skimmers were observed to be missing a skimmer or floating weir. Weirs ensures the skimmers operate as intended and maintain proper circulation and cleanliness of the pool water***Please replace the missing weir so there is adequate skimming of the surface water2. The flow meter reading was observed at 0.0 GPM at the time of inspection. This indicates that no measurable water is circulating through the pool’s filtration system.**Repair or replace the flow meter if it is found to be defective or obstructed.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • The corners of the basin near the bathrooms were observed separating from the wall. Please repair the basin to ensure that there is no gap between the basin cover and the wall as water can get in and create unsanitary conditions and damage the pool.**Please repair..
  5. Monitoring Inspection

    3 infractions

    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • Free chlorine levels were measured twice and found to be below the required minimum, testing at 0.25 ppm and 0.29 ppm. Increase the free chlorine concentration to at least 1 ppm to ensure effective disinfection of the pool water.**Please increase the chlorine to required minimum level
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • 1. Both skimmers were observed to be missing a skimmer or floating weir. Weirs ensures the skimmers operate as intended and maintain proper circulation and cleanliness of the pool water***Please replace the missing weir so there is adequate skimming of the surface water2. The flow meter reading was observed at 0.0 GPM at the time of inspection. This indicates that no measurable water is circulating through the pool’s filtration system.**Repair or replace the flow meter if it is found to be defective or obstructed.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • The corners of the basin near the bathrooms were observed separating from the wall. Please repair the basin to ensure that there is no gap between the basin cover and the wall as water can get in and create unsanitary conditions and damage the pool.**Please repair..
  6. Monitoring Inspection

    0 infractions

  7. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The bacterial water sample submitted on May 26th was unsatisfactory. - HPC was 360 CFU/mL. Ensure water chemistry is balanced. Treat as necessary and submit a resample.
  8. Risk Management Inspection

    0 infractions

  9. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • 4/30. The bacterial water sample submitted on April 29th was not processed. The date and time of collection was not provided on the requisition form. Another sample must be submitted.
  10. Monitoring Inspection

    0 infractions

  11. Risk Management Inspection

    0 infractions

  12. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • 2/28. The water sample submitted on February 25th, 2025 was unsatisfactory. - HPC 490 CFU/mL- TC absent.
  13. Risk Management Inspection

    0 infractions

  14. Risk Management Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • 9/18. Automatic controller was recallibrated. 9/11.1) The automatic controller readings for pH are not consistent with the manual tests. Recalibrate the pH probes to ensure that the manual test and automatic controller results are consistent. 2) The floating weir for the skimmer closest to the hot tub was missing. Replace the floating weir to ensure proper skimming action occurs.
  15. Risk Management Inspection

    2 infractions

    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • 9/11. The pH was measured at 8.28. The pH must be between 6.8 and 7.6. The acid container was empty, and acid was not being fed into the pool.Refill the acid container and ensure that the pH is between 6.8 and 7.6.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • 1) The automatic controller readings for pH are not consistent with the manual tests. Recalibrate the pH probes to ensure that the manual test and automatic controller results are consistent. 2) The floating weir for the skimmer closest to the hot tub was missing. Replace the floating weir to ensure proper skimming action occurs.
  16. Risk Management Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • 1) The automatic controller readings for pH are not consistent with the manual tests. Recalibrate the pH probes to ensure that the manual test and automatic controller results are consistent. 2) The floating weir for the skimmer closest to the hot tub was missing. Replace the floating weir to ensure proper skimming action occurs.
  17. Monitoring Inspection

    2 infractions

    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • 9/11. The pH was measured at 8.28. The pH must be between 6.8 and 7.6. The acid container was empty, and acid was not being fed into the pool.Refill the acid container and ensure that the pH is between 6.8 and 7.6.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • 1) The automatic controller readings for pH are not consistent with the manual tests. Recalibrate the pH probes to ensure that the manual test and automatic controller results are consistent. 2) The floating weir for the skimmer closest to the hot tub was missing. Replace the floating weir to ensure proper skimming action occurs.
  18. Monitoring Inspection

    0 infractions

  19. Monitoring Inspection

    0 infractions

  20. Monitoring Inspection

    0 infractions