Canalta High River - Whirlpool
1512 13 Avenue SE High River AB T1V 2B1 · Aquatic Facility
17 inspections
- Monitoring Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- 11/10. The flow rate was measured at 70 GPM and the turnover was 24 minutes. All whirlpools with a volume larger than 4 cubic meters must have a turnover of 20 minutes or less. The flow rate was increased to 85GPM and the turnover was 20.04 minutes.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- 8/13. The bacterial water sample submitted on August 12th was not processed. - Identification label was not on the bottle.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- 6/19. The bacterial water sample submitted on June 17th was unsatisfactory. - TC: Absent- Psuedomonas aeruginosa: Not Isolated- HPC: 270 CFU/mLTreat as necessary and resample.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Monitoring Inspection
1 infraction
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- 5/6. The free chlorine was tested twice. The free chlorine was measured at 1.76ppm for both tests. The free chlorine was increased at the time of the inspection. Free chlorine was tested again and was measured at 6.14ppm.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The bacterial water sample that was submitted on January 20, 2025, was not processed. The identification label was not on the bottle.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
0 infractions
- Demand Inspection
2 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- The bacterial water sample submitted on December 30, 2024 for the whirlpool had isolated pseudomonas.- Satisfactory bacterial water result required. Treatment next steps emailed to operator.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The bacterial water sample submitted on December 30, 2024 for the whirlpool had an HPC count of 130 CFU/mL. - Satisfactory bacterial water result required. Treatment next steps emailed to operator due to pseudomonas exceedance.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
0 infractions
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- 12/5. The bacteriological water resample that was submitted on December 3rd, 2024 was unsatisfactory. HPC was 1290 CFU/mL. 11/28. The most recent bacteriological water sample indicated an HPC of 630CFU/mL
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- 10/31. The sand filter was looked assessed and a potential cause for the sand at the bottom of the whirlpool basin was a disconnected lateral pipe. The lateral was reconnected. Sand is still observed at the bottom of the whirlpool basin each morning. Monitor the sand filter to see if the issues persists. If the issues persists, have the filter assessed by a technician.  10/18. There was sand observed at the bottom of the hot tub basin. The filters had been backwashed recently. Have the filtration system looked at to ensure that it is operating properly.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The most recent bacteriological water sample indicated an HPC of 630CFU/mL
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- 10/31. The sand filter was looked assessed and a potential cause for the sand at the bottom of the whirlpool basin was a disconnected lateral pipe. The lateral was reconnected. Sand is still observed at the bottom of the whirlpool basin each morning. Monitor the sand filter to see if the issues persists. If the issues persists, have the filter assessed by a technician.  10/18. There was sand observed at the bottom of the hot tub basin. The filters had been backwashed recently. Have the filtration system looked at to ensure that it is operating properly.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- 10/31. The sand filter was looked assessed and a potential cause for the sand at the bottom of the whirlpool basin was a disconnected lateral pipe. The lateral was reconnected. Sand is still observed at the bottom of the whirlpool basin each morning. Monitor the sand filter to see if the issues persists. If the issues persists, have the filter assessed by a technician.  10/18. There was sand observed at the bottom of the hot tub basin. The filters had been backwashed recently. Have the filtration system looked at to ensure that it is operating properly.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Monitoring Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- There was sand observed at the bottom of the hot tub basin. The filters had been backwashed recently. Have the filtration system looked at to ensure that it is operating properly.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Monitoring Inspection
0 infractions
- Monitoring Inspection
0 infractions
- Monitoring Inspection
0 infractions