Canalta High River - Pool
1512 13 Avenue SE High River AB T1V 2B1 · Aquatic Facility
25 inspections
- Monitoring Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- 11/10. The flow rate for the pool was 65GPM and the turnover period was 5 hours. All pools built after 2006 must have a turnover of 4 hours or less. The flow rate was increased to 82GPM and the turnover period was 4.03 hours.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- 9/11. The bacterial water sample submitted on September 9, 2025, was unsatisfactory. - TC absent. - HPC1480 CFU/mL. Treat pool as necessary and resample.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The bacterial water sample submitted on August 18th, 2025, was unsatisfactory. TC: AbsentHPC: 9000 CFU/mLPool operator stated that they had an issue with the disinfection on the August 18th. This has been addressed.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The bacterial water sample submitted August 5, 2025 had an HPC count of 120 CFU/mL. - Pool chemistry to be balanced and a satisfactory water sample submitted.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The bacterial water sample submitted on July 3 was unsatisfactory. - HPC was 110 CFU/mLOperator stated that the filter was clogged. Filter was backwashed. Water chemistry was balanced and a resample will be submitted.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Monitoring Inspection
0 infractions
- Risk Management Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- 12/17. New floating weirs were obtained and flow was adjusted. Two out of the three skimmers had proper skimming action. The floating weir for the skimmer by the emergency exit was still floating too high.  10/31. The flow to the skimmers adjusted. The floating weirs are still too high. 10/18. The floating weirs for the skimmers located closest to the doors were floating too high. The floating weirs need to be lowered in order to allow for proper skimming action to occur.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- 1) The bacteriological water sample submitted on December 23, 2024 was unsatisfactory. - The heterotrophic plate count was 57,000CFU/mL. 2) The bacteriological water sample submitted on December 30, 2024 was unsatisfactory. - The heterotrophic plate count was 800CFU/mL. Treat the pool as necessary, balance water chemistry, and resample.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- 12/17. New floating weirs were obtained and flow was adjusted. Two out of the three skimmers had proper skimming action. The floating weir for the skimmer by the emergency exit was still floating too high.  10/31. The flow to the skimmers adjusted. The floating weirs are still too high. 10/18. The floating weirs for the skimmers located closest to the doors were floating too high. The floating weirs need to be lowered in order to allow for proper skimming action to occur.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- 1) The bacteriological water sample submitted on December 23, 2024 was unsatisfactory. - The heterotrophic plate count was 57,000CFU/mL. 2) The bacteriological water sample submitted on December 30, 2024 was unsatisfactory. - The heterotrophic plate count was 800CFU/mL. Treat the pool as necessary, balance water chemistry, and resample.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- 12/17. New floating weirs were obtained and flow was adjusted. Two out of the three skimmers had proper skimming action. The floating weir for the skimmer by the emergency exit was still floating too high.  10/31. The flow to the skimmers adjusted. The floating weirs are still too high. 10/18. The floating weirs for the skimmers located closest to the doors were floating too high. The floating weirs need to be lowered in order to allow for proper skimming action to occur.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The bacteriological water sample submitted on December 23, 2024 was unsatisfactory. - The heterotrophic plate count was 57,000CFU/mL. Treat the pool as necessary, balance water chemistry, and resample.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- 12/17. New floating weirs were obtained and flow was adjusted. Two out of the three skimmers had proper skimming action. The floating weir for the skimmer by the emergency exit was still floating too high.  10/31. The flow to the skimmers adjusted. The floating weirs are still too high. 10/18. The floating weirs for the skimmers located closest to the doors were floating too high. The floating weirs need to be lowered in order to allow for proper skimming action to occur.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- 12/17. New floating weirs were obtained and flow was adjusted. Two out of the three skimmers had proper skimming action. The floating weir for the skimmer by the emergency exit was still floating too high.  10/31. The flow to the skimmers adjusted. The floating weirs are still too high. 10/18. The floating weirs for the skimmers located closest to the doors were floating too high. The floating weirs need to be lowered in order to allow for proper skimming action to occur.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Risk Management Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- 10/31. The flow to the skimmers adjusted. The floating weirs are still too high. 10/18. The floating weirs for the skimmers located closest to the doors were floating too high. The floating weirs need to be lowered in order to allow for proper skimming action to occur.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Monitoring Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The floating weirs for the skimmers located closest to the doors were floating too high. The floating weirs need to be lowered in order to allow for proper skimming action to occur.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Risk Management Inspection
0 infractions
- Monitoring Inspection
1 infraction
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- There was a build-up of algae at the bottom of the basin of the pool near the emergency exit and near the slide.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- A bacteriological water sample was submitted on May 7th, 2024. The sample was unsatisfactory.- HPC 370 cfu/mL- TC absentPlease treat the pool and resample.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
0 infractions
- Monitoring Inspection
2 infractions
- 06. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Critical)?
- The floating weir in the skimmers near the emergency exit and the slide were floating too high and not allowing for proper skimming action.Repair/replace the floating weirs to ensure proper skimming action.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- There was a build-up of algae at the bottom of the pool basin near the slide and emergency exit.
- 06. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Critical)?
- Monitoring Inspection
0 infractions
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- A water sample was submitted on Sept 12 that was unsatisfactory. - High in HPC: 1010 CFUEnsure water chemistry is balanced and resample.
- 06. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Critical)?
- The floating weir in the skimmer near the emergency exit is floating too high and not allowing for proper skimming action.Repair/replace the floating weir to ensure proper skimming action.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?