Hilton Garden Inn Calgary Airport - Whirlpool

2335 Pegasus Road NE Calgary AB T2E 8C3 · Aquatic Facility

Inspection summary

Hilton Garden Inn Calgary Airport - Whirlpool has been inspected 5 times by Alberta Health Services (Environmental Public Health) since March 19, 2026. The most recent inspection, on May 29, 2026, recorded 1 infraction.

None of the 5 inspections on record were free of infractions. In the past 12 months there were 5 inspections with 9 infractions recorded. The higher-risk findings here relate to: Pool and spa water quality and Chemicals and toxic substances.

The number of infractions per inspection has stayed roughly the same over time.

What these findings mean

Health authorities word their findings differently, so we group them by what they mean for the people using the facility. Higher-risk findings are the ones that could directly cause illness or injury, such as water that is not properly treated.

  • Pool and spa water qualityHigher risk

    For pools, spas and splash pads, inspectors test disinfectant levels, pH and water clarity, and check safety equipment. Water that is not properly treated can spread skin, ear and stomach infections.

    Recorded 8 times across 5 separate inspections, most recently on May 29, 2026. For example: Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?

  • Chemicals and toxic substancesHigher risk

    Pool chemicals such as chlorine and acid must be labelled, stored apart from each other and handled safely. Mixing them by mistake can release toxic gas, so storage and handling problems are treated seriously.

    Recorded once on March 19, 2026. For example: Is the chemical quality of the water in this pool satisfactory (Critical)?

About this data

These results come from Alberta Health Services (Environmental Public Health), which inspects food premises and other public facilities in this area. We republish the authority's public disclosure data and refresh it regularly; the official record is the final word.

5 inspections

  1. Risk Management Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The turnover for the pool was calculated at 22.6 minutes.Requirement: A pool constructed prior to 2006 may go over the required turnover of 15 minutes if the chemistry and biological requirements can be maintained. Minimum flow rate calculated at 61.7 GPM for 15-minute turnover.
  2. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The water sample collected on April 8, 2026, was not tested because there was no identification number on the bottle.**UNSATISFACTORY (2026-05-13). The water sample collected on May 6, 2026, was not tested because there was no identification number on the bottle.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The turnover for the pool was calculated at 22.6 minutes.Requirement: A pool constructed prior to 2006 may go over the required turnover of 15 minutes if the chemistry and biological requirements can be maintained. Minimum flow rate calculated at 61.7 GPM for 15-minute turnover.
  3. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The water sample collected on April 8, 2026, was not tested because there was no identification number on the bottle.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The turnover for the pool was calculated at 22.6 minutes.Requirement: A pool constructed prior to 2006 may go over the required turnover of 15 minutes if the chemistry and biological requirements can be maintained. Minimum flow rate calculated at 61.7 GPM for 15-minute turnover.
  4. Initial Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The turnover for the pool was calculated at 22.6 minutes.Requirement: A pool constructed prior to 2006 may go over the required turnover of 15 minutes if the chemistry and biological requirements can be maintained. Minimum flow rate calculated at 61.7 GPM for 15-minute turnover.
  5. Demand Inspection

    3 infractions

    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • 0.34 ppm of free available chlorine was measured in the whirlpool.Requirement: Ensure that Free Available Chlorine is maintained at a minimum of 2.0ppm.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • 1) The automated controller for the whirlpool was not working, as it was reading 0.4ppm chlorine but was not automatically adjusting the chlorine concentration in the whirlpool.Requirement: Repair the automated controller.2) The turnover for the pool was calculated at 22.6 minutes.Requirement: A pool constructed prior to 2006 may go over the required turnover of 15 minutes if the chemistry and biological requirements can be maintained. Minimum flow rate calculated at 61.7 GPM for 15-minute turnover.
    • 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
      • There was no clock visible from the whirlpool. Requirement: Ensure that there is a functional clock that can be easily viewed when sitting in the whirlpool.