Inspection summary

Hilton Garden Inn Edmonton International Airport - Hot Tub has been inspected 25 times by Alberta Health Services (Environmental Public Health) since January 25, 2024. The most recent inspection, on August 10, 2026, recorded 8 infractions.

6 of 25 inspections on record found no infractions at all. In the past 12 months there were 11 inspections with 35 infractions recorded. The higher-risk findings here relate to: Pool and spa water quality, Chemicals and toxic substances and Food temperature control.

The number of infractions per inspection has stayed roughly the same over time.

What these findings mean

Health authorities word their findings differently, so we group them by what they mean for the people using the facility. Higher-risk findings are the ones that could directly cause illness or injury, such as water that is not properly treated.

  • Pool and spa water qualityHigher risk

    For pools, spas and splash pads, inspectors test disinfectant levels, pH and water clarity, and check safety equipment. Water that is not properly treated can spread skin, ear and stomach infections.

    Recorded 48 times across 19 separate inspections, most recently on August 10, 2026. For example: Is the bacteriological quality of the water in this pool satisfactory (Critical)?

  • Chemicals and toxic substancesHigher risk

    Pool chemicals such as chlorine and acid must be labelled, stored apart from each other and handled safely. Mixing them by mistake can release toxic gas, so storage and handling problems are treated seriously.

    Recorded 11 times across 7 separate inspections, most recently on August 10, 2026. For example: Is the chemical quality of the water in this pool satisfactory (Critical)?

  • Food temperature controlHigher risk

    Inspectors check that anything that has to be kept at a set temperature, such as chilled or hot food, or equipment like sterilizers, stays in its safe range and that accurate thermometers are on hand. With food, temperature problems are one of the most common causes of food poisoning.

    Recorded 8 times across 8 separate inspections, most recently on August 10, 2026. For example: Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?

  • Permits, records and postingLower risk

    Operating permits, water-test logs, posted bather rules and emergency procedures. Daily test logs are how operators show the water was checked and treated between inspections.

    Recorded once on October 15, 2024. For example: Are proper testing, monitoring, and other records being properly maintained?

About this data

These results come from Alberta Health Services (Environmental Public Health), which inspects food premises and other public facilities in this area. We republish the authority's public disclosure data and refresh it regularly; the official record is the final word.

25 inspections

  1. Demand Inspection

    8 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Whirlpool has had several failed water samples with total coliforms present, Pseudomonas aeruginosa isolated and elevated Heterotrophic Plate Counts from February 18 to April 1, 2026. The whirlpool sample on April 1, 2026, showed the presence of total coliforms and the presence of Pseudomonas aeruginosa.Two (2) consecutive sets of satisfactory water samples are required
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Whirlpool has had several failed water samples with total coliforms present, Pseudomonas aeruginosa isolated and elevated Heterotrophic Plate Counts from February 18 to April 1, 2026. The whirlpool sample on April 1, 2026, showed the presence of total coliforms and the presence of Pseudomonas aeruginosa.Two (2) consecutive sets of satisfactory water samples are required
    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • FCL 4.34 ppm, TCL 4.57 ppm, and pH 7.71Maintenance staff admitted to manually adding granular chlorine and alkalinity increaser at approximately 9:00 AM the day of the inspection.The controller and probes appear to be malfunctioning. The display showed an ORP of 999mV and pH of 7.35. The readings were significantly different from the manual test.- Repair or replace the automated chemical controller and probes to ensure it accurately monitor free chlorine and pH- Ensure the pH is maintained between 6.8 to 7.6
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • ALK: Over Range (too high to read)Ensure that Alkalinity is maintained between 60-180ppm
    • 06. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Critical)?
      • The circulation system was turned off (the pump was not running). Consequently, recirculation and filtration rates could not be calculated.Ensure the circulation pump is fully operational and capable of maintaining the required recirculation rate.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • - Float weirs were missing from the skimmer baskets-The controller and probes appear to be malfunctioning. The display showed an ORP of 999 and pH of 7.35, different from manual test reading.Install missing float weirs in the whirlpool skimmers.Repair or replace the automated chemical controller and probes. Provide a technician's report confirming the system is calibrated and accurately monitoring Free Chlorine, and pH.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • Several tiles were missing around the main drain coversReplace missing tiles in the whirlpool basin around the main drain covers.
    • 15. Has an owner or owner's agent, if any, been identified and is the pool operated and maintained by a qualified pool operator?
      • The facility currently lacks a trained pool operator.A pool operator must be provided for the facility that is able to maintain the pool on day-to-day basis and meet the qualifications of having successfully completed a recognized pool operator education course. The pool operator must:- Provide proof of successful completion of the course.- Demonstrate to the Executive Officer the ability to perform daily operations, including correct water sample collection, accurate manual pool chemistry testing and record keeping.
  2. Demand Inspection

    8 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Whirlpool has had several failed water samples with total coliforms present, Pseudomonas aeruginosa isolated and elevated Heterotrophic Plate Counts from February 18 to April 1, 2026. The whirlpool sample on April 1, 2026, showed the presence of total coliforms and the presence of Pseudomonas aeruginosa.Two (2) consecutive sets of satisfactory water samples are required
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Whirlpool has had several failed water samples with total coliforms present, Pseudomonas aeruginosa isolated and elevated Heterotrophic Plate Counts from February 18 to April 1, 2026. The whirlpool sample on April 1, 2026, showed the presence of total coliforms and the presence of Pseudomonas aeruginosa.Two (2) consecutive sets of satisfactory water samples are required
    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • FCL 4.34 ppm, TCL 4.57 ppm, and pH 7.71Maintenance staff admitted to manually adding granular chlorine and alkalinity increaser at approximately 9:00 AM the day of the inspection.The controller and probes appear to be malfunctioning. The display showed an ORP of 999mV and pH of 7.35. The readings were significantly different from the manual test.- Repair or replace the automated chemical controller and probes to ensure it accurately monitor free chlorine and pH- Ensure the pH is maintained between 6.8 to 7.6
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • ALK: Over Range (too high to read)Ensure that Alkalinity is maintained between 60-180ppm
    • 06. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Critical)?
      • The circulation system was turned off (the pump was not running). Consequently, recirculation and filtration rates could not be calculated.Ensure the circulation pump is fully operational and capable of maintaining the required recirculation rate.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • - Float weirs were missing from the skimmer baskets-The controller and probes appear to be malfunctioning. The display showed an ORP of 999 and pH of 7.35, different from manual test reading.Install missing float weirs in the whirlpool skimmers.Repair or replace the automated chemical controller and probes. Provide a technician's report confirming the system is calibrated and accurately monitoring Free Chlorine, and pH.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • Several tiles were missing around the main drain coversReplace missing tiles in the whirlpool basin around the main drain covers.
    • 15. Has an owner or owner's agent, if any, been identified and is the pool operated and maintained by a qualified pool operator?
      • The facility currently lacks a trained pool operator.A pool operator must be provided for the facility that is able to maintain the pool on day-to-day basis and meet the qualifications of having successfully completed a recognized pool operator education course. The pool operator must:- Provide proof of successful completion of the course.- Demonstrate to the Executive Officer the ability to perform daily operations, including correct water sample collection, accurate manual pool chemistry testing and record keeping.
  3. Demand Inspection

    8 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Whirlpool has had several failed water samples with total coliforms present, Pseudomonas aeruginosa isolated and elevated Heterotrophic Plate Counts from February 18 to April 1, 2026. The whirlpool sample on April 1, 2026, showed the presence of total coliforms and the presence of Pseudomonas aeruginosa.Two (2) consecutive sets of satisfactory water samples are required
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Whirlpool has had several failed water samples with total coliforms present, Pseudomonas aeruginosa isolated and elevated Heterotrophic Plate Counts from February 18 to April 1, 2026. The whirlpool sample on April 1, 2026, showed the presence of total coliforms and the presence of Pseudomonas aeruginosa.Two (2) consecutive sets of satisfactory water samples are required
    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • FCL 4.34 ppm, TCL 4.57 ppm, and pH 7.71Maintenance staff admitted to manually adding granular chlorine and alkalinity increaser at approximately 9:00 AM the day of the inspection.The controller and probes appear to be malfunctioning. The display showed an ORP of 999mV and pH of 7.35. The readings were significantly different from the manual test.- Repair or replace the automated chemical controller and probes to ensure it accurately monitor free chlorine and pH- Ensure the pH is maintained between 6.8 to 7.6
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • ALK: Over Range (too high to read)Ensure that Alkalinity is maintained between 60-180ppm
    • 06. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Critical)?
      • The circulation system was turned off (the pump was not running). Consequently, recirculation and filtration rates could not be calculated.Ensure the circulation pump is fully operational and capable of maintaining the required recirculation rate.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • - Float weirs were missing from the skimmer baskets-The controller and probes appear to be malfunctioning. The display showed an ORP of 999 and pH of 7.35, different from manual test reading.Install missing float weirs in the whirlpool skimmers.Repair or replace the automated chemical controller and probes. Provide a technician's report confirming the system is calibrated and accurately monitoring Free Chlorine, and pH.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • Several tiles were missing around the main drain coversReplace missing tiles in the whirlpool basin around the main drain covers.
    • 15. Has an owner or owner's agent, if any, been identified and is the pool operated and maintained by a qualified pool operator?
      • The facility currently lacks a trained pool operator.A pool operator must be provided for the facility that is able to maintain the pool on day-to-day basis and meet the qualifications of having successfully completed a recognized pool operator education course. The pool operator must:- Provide proof of successful completion of the course.- Demonstrate to the Executive Officer the ability to perform daily operations, including correct water sample collection, accurate manual pool chemistry testing and record keeping.
  4. Demand Inspection

    4 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Pseudomonas and TC was present in a sample collected on February 2.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • HPC>57000 in a sample collected on Feb 2.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • - No skimming action, water level below the skimmer opening- The controller was not in good working order.
    • 15. Has an owner or owner's agent, if any, been identified and is the pool operated and maintained by a qualified pool operator?
      • The facility currently lacks a trained pool operator. Take immediate action to ensure the current operator enrolls in a certified pool operator training course. Please email proof of registration before the end of February 2026.
  5. Risk Management Inspection

    1 infraction

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • TC was present in a sample collected on February 2.
  6. Demand Inspection

    0 infractions

  7. Risk Management Inspection

    0 infractions

  8. Demand Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Total coliform and pseudomonas present in a sample collected on January 14/2026.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • HPC>57000 in a sample collected on January 14/2026.
  9. Demand Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Total coliform and pseudomonas present in a sample collected on January 14/2026.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • HPC>57000 in a sample collected on January 14/2026.
  10. Risk Management Inspection

    0 infractions

  11. Demand Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • TC and Pseudomonas isolated from a sample submitted in October 29.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • HPC > 57,000cfu isolated in a sample submitted in October 29.
  12. Risk Management Inspection

    0 infractions

  13. Risk Management Inspection

    4 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Consecutive failed samples with TC and Pseudomonas present in a sample submitted on September 24, 2025, and the week after.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Consecutive failed samples with HPC >57000 in a sample submitted on September 24 and the week after.
    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • - Reading from the controller: ORP-720mV and pH-7.31PHI Readings taken at 10am:**FCL = 0.55ppm, lowered than required- TCL = 0.85ppm- pH = 6.99- ALK - 157ppm- Readings taking from the probe cell/housing at 10:25am** FCL = 0.45ppm- ALK = 177.The readings were similar to those of the operator taken an hour earlier and also similar to those from the probe cell sample.ACTION REQUIRED:1) Ensure that FCL is maintained at least 2ppm
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Volume = 734galFlow rate = 68-70gpm- Adequate surface skimming was observed.- Turnover = 734gal/68gpm = 10.8 minutes**Filtration rate = 68gpm/4. 91sq.ft =13.8gpm/sq.ft. The filtration rate for a sand filter in a whirlpool shall not exceed 12.5gpm/sq.ftACTION REQUIRED:1) Please maintain your flow rate between 49 -60gpm to achieve compliance with both turnover and filtration rate requirements.
  14. Monitoring Inspection

    4 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Consecutive failed samples with TC and Pseudomonas present in a sample submitted on September 24, 2025, and the week after.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Consecutive failed samples with HPC >57000 in a sample submitted on September 24 and the week after.
    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • - Reading from the controller: ORP-720mV and pH-7.31PHI Readings taken at 10am:**FCL = 0.55ppm, lowered than required- TCL = 0.85ppm- pH = 6.99- ALK - 157ppm- Readings taking from the probe cell/housing at 10:25am** FCL = 0.45ppm- ALK = 177.The readings were similar to those of the operator taken an hour earlier and also similar to those from the probe cell sample.ACTION REQUIRED:1) Ensure that FCL is maintained at least 2ppm
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Volume = 734galFlow rate = 68-70gpm- Adequate surface skimming was observed.- Turnover = 734gal/68gpm = 10.8 minutes**Filtration rate = 68gpm/4. 91sq.ft =13.8gpm/sq.ft. The filtration rate for a sand filter in a whirlpool shall not exceed 12.5gpm/sq.ftACTION REQUIRED:1) Please maintain your flow rate between 49 -60gpm to achieve compliance with both turnover and filtration rate requirements.
  15. Demand Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • TC and Pseudomonas present in a sample submitted on September 24, 2025. Operator directed to shock chlorinate.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • HPC >57000 in a sample submitted on September 24
  16. Demand Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • TC and Pseudomonas present in a sample submitted on September 24, 2025. Operator directed to shock chlorinate.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • HPC >57000 in a sample submitted on September 24
  17. Demand Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • TC and Pseudomonas present in a sample submitted on September 24, 2025. Operator directed to shock chlorinate.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • HPC >57000 in a sample submitted on September 24
  18. Monitoring Inspection

    0 infractions

  19. Risk Management Inspection

    0 infractions

  20. Monitoring Inspection

    6 infractions

    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • Inspector's reading taking at 3pm:- FCL = 0ppm, TCL= 0ppm, pH = 6.96- Reading from the controller at 2:20pm: ORP=145mV and pH = 7,24.The inspector's readings were significantly different from those of the operator taking around 11am. **The operator was asked to conduct a manual test of the pool water using his test kit. The operator performed the test without zeroing/blanking the equipment. The pool operator was asked why he did not zero the equipment and he said, "that is how i do the testing". This explained why the operator's reading were different from those of the inspector.- The operator could not correct the chlorine issue in the pool at the time of the inspection because there was an active leak on the pipe/tube that feeds chlorine The operator voluntarily closed the poolACTION REQUIRED:1) Whirlpool to remain closed to the public until a re-inspection is completed2) Repair the leaking chlorine line3) Ensure that you maintain a free chlorine reading of 2ppm in the basin.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • - Alkalinity in the pool was measured at 33ppmACTION REQUIRED:1) Maintain alkalinity between 60-180ppm
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • **Flapper/floating weir was missing from one of the skimmers.- Pool volume is 734gal, filter surface area is 4.91sq.ft., flow rate was 63gpm- Turnover = 734gal/63gpm = 11.7 minutes**Filtration rate - 63gpm/4.91sq.ft = 12.8gpm/sq.ftACTION REQUIRED:1) Install the flappers or floater weir in the skimmer to maximize surface recirculation/skimming of the pool water.2) Please keep your flow rate between 49 - 61gpm. Running your whirlpool above 61gpm will take your filtration rate about the required 12.5gpm/sq.ft
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • - Water temperature was 37C** Missing tiles were noted in the basin, near the main drain covers. ACTION REQUIRED:1) Replace the missing tiles in the hot tub basin as soon as possible as this was cited at the beginning of 2024. The sharps edges from the missing tiles may cause bruising of bathers' skin.
    • 15. Has an owner or owner's agent, if any, been identified and is the pool operated and maintained by a qualified pool operator?
      • The operator's certificate had expired and there were some gaps in the operator's knowledge on basic pool test. The operator was asked to perform a pool chemistry test, and he performed the test without blanking the instrument. When asked why he did not blank the instrument and he said " that is how i have always done it and i was not aware that i supposed to blank the instrument"ACTION REQUIRED>1) Have the pool operator take a refresher of the pool operator course as soon as possible.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • **The operator keeps a daily records of pool chemistry test results, but the results are inaccurate because the test were not done correctly. The operator was not blanking the testing instrument prior to performing the test.**The test instrument itself appeared to have malfunctioned. When the operator tried to blank the machine, it kept showing error messagesACTION REQUIRED:1) Ensure that the testing machine is in good working order. if not, please repair or replace it.2) Ensure that operator is following proper procedure in performing pool chemistry test. Ensure that the manufacturer's instruction for use is available to the pool operator.
  21. Demand Inspection

    3 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Pseudomonas and HPC isolated in a water sample submitted on October 10, 2024Operator directed to treat the basin
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • **Flapper/floating weir was missing from one of the skimmers.ACTION REQUIRED:1) Install the flappers or floater weir in the skimmer to maximize surface recirculation/skimming of the pool water.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • - The pool water heating system had been repaired and pool water temperature was 39C.** Missing tiles were noted in the basin, near the main drain covers. The operator stated that they have purchased the tiles, and they will be installed before the end of February. ACTION REQUIRED:1) Replace the missing tiles in the hot tub basin. The sharps edges from the missing tiles may cause bruising of bathers' skin.
  22. Risk Management Inspection

    2 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • **Flapper/floating weir was missing from one of the skimmers.ACTION REQUIRED:1) Install the flappers or floater weir in the skimmer to maximize surface recirculation/skimming of the pool water.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • - The pool water heating system had been repaired and pool water temperature was 39C.** Missing tiles were noted in the basin, near the main drain covers. The operator stated that they have purchased the tiles, and they will be installed before the end of February. ACTION REQUIRED:1) Replace the missing tiles in the hot tub basin. The sharps edges from the missing tiles may cause bruising of bathers' skin.
  23. Demand Inspection

    3 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Pseudomonas isolated from a sample collected on September 4th.Operator directed to treat for pseudomonas and resample.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • **Flapper/floating weir was missing from one of the skimmers.ACTION REQUIRED:1) Install the flappers or floater weir in the skimmer to maximize surface recirculation/skimming of the pool water.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • - The pool water heating system had been repaired and pool water temperature was 39C.** Missing tiles were noted in the basin, near the main drain covers. The operator stated that they have purchased the tiles, and they will be installed before the end of February. ACTION REQUIRED:1) Replace the missing tiles in the hot tub basin. The sharps edges from the missing tiles may cause bruising of bathers' skin.
  24. Monitoring Inspection

    2 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • **Flapper/floating weir was missing from one of the skimmers.ACTION REQUIRED:1) Install the flappers or floater weir in the skimmer to maximize surface recirculation/skimming of the pool water.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • - The pool water heating system had been repaired and pool water temperature was 39C.** Missing tiles were noted in the basin, near the main drain covers. The operator stated that they have purchased the tiles, and they will be installed before the end of February. ACTION REQUIRED:1) Replace the missing tiles in the hot tub basin. The sharps edges from the missing tiles may cause bruising of bathers' skin.
  25. Demand Inspection

    3 infractions

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Total chlorine of the pool was out of range. PHI was unable to calculate the combined chlorine. The operator was advised to backwash the filter, drain, and refill the pool basing, and balance the pool chemistry. Please be advised to keep combined chlorine as low as possible.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • 1. The turnover rate of the whirlpool was calculated to be at 17.4 minutesPlease increase the flow rate of the pool and ensure that the turnover rate is maintained at or below 15 minutes. 2. One the pool filter plumbing line was observed to be leaking. Please repair the leaking plumbing line. 3. The filter pressure gauge was not in operational state. Please replace the filter pressure gauge.
    • 15. Has an owner or owner's agent, if any, been identified and is the pool operated and maintained by a qualified pool operator?
      • It was noted that the responsible person is not properly trained. Please ensure that pool operator is properly trained.