Holiday Inn Airport - Whirlpool

1250 Mckinnon Drive NE Calgary AB T2E 7T7 · Aquatic Facility

8 inspections

  1. Risk Management Inspection

    0 infractions

  2. Risk Management Inspection

    1 infraction

    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • 1. The anti-entrapment plans for the jet pump and recirculation pump are missing information.**November 20, 2025: anti-entrapment plans completed and submitted for review.COMPLETE THE FOLLOWING:1. Ensure anti-entrapment plans are complete and accurate. Please provide supporting documentation such as plumbing diagram, diagram of sump, photos of measurements between drain covers, flow metres.
  3. Risk Management Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • 1. The last bacteriological water sample on file was submitted June 11, 2024. During the inspection the Operator stated they drop off weekly samples every Tuesday.**November 18, 2025: Spoke with the General Manager to inform them of sampling history and was informed weekly samples are dropped off but was not sure what information was being provided on the requisition form.**November 21, 2025: sample will be taken on Monday, November 24 due to timing of inspection being late in the afternoon and the lab closing.COMPLETE THE FOLLOWING:1. Ensure the requisition forms are completed properly and include the access number to ensure the sample is linked to the facility's file.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • 1. The anti-entrapment plans for the jet pump and recirculation pump are missing information.**November 20, 2025: anti-entrapment plans completed and submitted for review.COMPLETE THE FOLLOWING:1. Ensure anti-entrapment plans are complete and accurate. Please provide supporting documentation such as plumbing diagram, diagram of sump, photos of measurements between drain covers, flow metres.
  4. Risk Management Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • 1. The last bacteriological water sample on file was submitted June 11, 2024. During the inspection the Operator stated they drop off weekly samples every Tuesday.**November 18, 2025: Spoke with the General Manager to inform them of sampling history and was informed weekly samples are dropped off but was not sure what information was being provided on the requisition form.COMPLETE THE FOLLOWING:1. Ensure the requisition forms are completed properly and include the access number to ensure the sample is linked to the facility's file.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • 1. The anti-entrapment plans for the jet pump and recirculation pump are missing information.**November 20, 2025: anti-entrapment plans completed and submitted for review. COMPLETE THE FOLLOWING:1. Ensure anti-entrapment plans are complete and accurate. Please provide supporting documentation such as plumbing diagram, diagram of sump, photos of measurements between drain covers, flow metres.
  5. Monitoring Inspection

    5 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • 1. The last bacteriological water sample on file was submitted June 11, 2024. During the inspection the Operator stated they drop off weekly samples every Tuesday.**November 18, 2025: Spoke with the General Manager to inform them of sampling history and was informed weekly samples are dropped off but was not sure what information was being provided on the requisition form.COMPLETE THE FOLLOWING:1. Ensure the requisition forms are completed properly and include the access number to ensure the sample is linked to the facility's file.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • **CORRECTED**1. Main drain valve was opend more than 20%. Valve closed to 20% during the inspection to increase flow of water through skimmers as the top portion of water contains the greatest amount of contaminants.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • 1. There was a significant amount of chemical buildup on the automated controller. The controller reding was pH 6.0 and manual tests measured the pH to be 7.38 during inspection.COMPLETE THE FOLLOWING:1. Please have the automated controllers serviced and re-calibrated to ensure they are operating correctly and getting accurate readings.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • 1. Water chemistry records were not properly completed. The water chemistry log sheet that was posted on the wall was dated November 17, 2025, and the results for Monday, Wednesday, Friday and Saturday were already filled out. The Operator stated they had not checked the water chemistry for the day. COMPLETE THE FOLLOWING:1. Ensure the pool water chemistry is checked daily and that chemistry log sheets are completed daily and are accurate.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • 1. The anti-entrapment plans for the jet pump and recirculation pump are missing information.COMPLETE THE FOLLOWING:1. Ensure anti-entrapment plans are complete and accurate. Please provide supporting documentation such as plumbing diagram, diagram of sump, photos of measurements between drain covers, flow metres.
  6. Monitoring Inspection

    1 infraction

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • 1. Combined chlorine was measured at 5.33 milligrams per litre during the inspection.-Please reduce and maintain the pool combined chlorine as low as possible to ensure bathers' comfort.2. Total alkalinity was measured at 35 milligrams per litre at the time of the inspection.-Please increase and maintain total alkalinity between 60-180 milligrams per litre to ensure pool water chemical balance and pH.
  7. Monitoring Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The chlorine injector tube was damaged at the time of the inspection.-Please repair the chlorine injector and ensure it is in good working condition at all times.The chlorine injector tube was replaced with a new one during the inspection.
  8. Monitoring Inspection

    3 infractions

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Pool alkalinity was measured at 53 milligrams per litre.Please maintain the pool alkalinity between 60 -180 milligrams per litre as required by the Pool Standards.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • Pool water chemical parameters not daily documented.-Please daily record water chemical parameters to ensure proper daily monitoring.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Anti-entrapment plans for the hot tub not available. Please complete anti-entrapment plans and send to the district inspector for assessment.