Lions Wading Pool - Wading Pool
9906 104 Street Fort Saskatchewan AB T8L 2E8 · Aquatic Facility
11 inspections
- Risk Management Inspection
0 infractions
- Risk Management Inspection
2 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Could not determine a reading for the left flow meter. Based on the flow rate of only the right flow meter, the wading pool had a turnover period of 3.03 hours. Repair/replace the left flow meter and ensure the wading pool has a turnover period of 2 hours or less.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Cyanuric acid measured 3ppm. Cyanuric acid was increased to 20ppm to prevent chlorine dissipation.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Monitoring Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The automated chemical feeder was not working properly and was only pulling sodium bisulfate resulting in a very low pH. The automated readings indicated a pH level of 3.34 and manual testing of the pH level resulted in a under range result. Repair the automatic feeder and ensure pH levels are between 6.8 and 7.6.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Results of water sample collected September 2, 2025 resulted in a Heterotrophic plate count of 1250 CFU/mL.Pool closing for season, will resample and have inspection prior to operating next season.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Monitoring Inspection
0 infractions
- Demand Inspection
1 infraction
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Low free chlorine. Ensure FC is adjusted immediately.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
0 infractions
- Demand Inspection
1 infraction
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Low free chlorine. Ensure FC is adjusted immediately.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
1 infraction
- 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
- Outstanding from a previous inspection:1-Wooden plank on the deck placed over piping going into the wading pool was noted off the ground and presents a tripping hazard- please ensure the wooden plank is secured to the ground and that it does not lift when walking over it. 2-Flow meters are not working. They need to be adjusted so they provide an accurate reading.
- 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
- Demand Inspection
1 infraction
- 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
- Outstanding from a previous inspection:1-Wooden plank on the deck placed over piping going into the wading pool was noted off the ground and presents a tripping hazard- please ensure the wooden plank is secured to the ground and that it does not lift when walking over it. 2-Flow meters are not working. They need to be adjusted so they provide an accurate reading.
- 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
- Monitoring Inspection
2 infractions
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- pH was noted at 7.7Discrepancies noted between reading of pH at automatic controller and manual water testing results.Ensure the pH is maintained between 6.8 and 7.6.
- 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
- 1-Wooden plank on the deck placed over piping going into the wading pool was noted off the ground and presents a tripping hazard- please ensure the wooden plank is secured to the ground and that it does not lift when walking over it. 2-Flow meters are not working. They need to be adjusted so they provide an accurate reading.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?