Skip to content
Loading map…

Manluk Centre Wetaskiwin Regional Aquatic & Fitness - Competition Pool

4514 50 Avenue Wetaskiwin AB T9A 2E9 · Aquatic Facility

11 inspections

  1. Monitoring Inspection

    0 infractions

  2. Monitoring Inspection

    0 infractions

  3. Risk Management Inspection

    1 infraction

    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • PREVIOUSLY - PHI water test resultsFree Chlorine = 1.36 ppmpH = 6.5 Operator is aware of a potential readout problem with the pH probe and is waiting for the replacement probe to arrive. Operator double checking water chemistry with manual testing.Oct 16, 2025 - PHI contacted the operator and the pH is reported at 7.11 - this is satisfactory.
  4. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The water sample collected on Oct 1, 2025, had these results: - Total Coliforms - Absent - HPC - 270 CFU/mL ( <100 CFU/mL is allowable )This is an Unsatisfactory result.You will need to shock chlorinate the pool this evening, when no one is using the pool, re-balance the water chemistry in the morning and then you can re-open to the public.
    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • PHI water test resultsFree Chlorine = 1.36 ppmpH = 6.5 Operator is aware of a potential readout problem with the pH probe and is waiting for the replacement probe to arrive. Operator double checking water chemistry with manual testing.
  5. Monitoring Inspection

    1 infraction

    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • PHI water test resultsFree Chlorine = 1.36 ppmpH = 6.5 Operator is aware of a potential readout problem with the pH probe and is waiting for the replacement probe to arrive. Operator double checking water chemistry with manual testing.
  6. Monitoring Inspection

    0 infractions

  7. Monitoring Inspection

    0 infractions

  8. Monitoring Inspection

    0 infractions

  9. Monitoring Inspection

    0 infractions

  10. Monitoring Inspection

    0 infractions

  11. Monitoring Inspection

    1 infraction

    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • pH reading was 6.97 (satisfactory) Free chlorine reading was 0.23ppm (unsatisfactory).As this pool is operating at a pH of less than 7.5 and the ORP is greater than 770mv. This basin of water could operate with a free chlorine of 0.3ppm or greater. The chlorine reading was low because operator remembered that chlorine regulator was turned off earlier during inspection and needed to be turned back on.