Movati Athletic - Women's Whirlpool
17020 Hiller Road SW Edmonton AB T6W 4H3 · Aquatic Facility
8 inspections
- Monitoring Inspection
0 infractions
- Risk Management Inspection
1 infraction
- 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
- Skimmers require cleaning.
- 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
- Monitoring Inspection
1 infraction
- 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
- Skimmers require cleaning.
- 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
- Risk Management Inspection
2 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Rate of filtration for the filtration system was 13.74 gpm/sq ft based on a filtration area of 7.06 sq ft (with flow rate 97 gpm), which exceeds the maximum allowed rate of filtration 12.5 gpm/sq ft. Note: the flow rate cannot exceed 88 gpm for proper rate of filtration (and should not be below 60 gpm).
- 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
- Skimmers require cleaning.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- the sample 24EN-282E00762 submitted on October 8, 2024, was unsatisfactory: HPC 370.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Rate of filtration for the filtration system was 13.74 gpm/sq ft based on a filtration area of 7.06 sq ft (with flow rate 97 gpm), which exceeds the maximum allowed rate of filtration 12.5 gpm/sq ft. Note: the flow rate cannot exceed 88 gpm for proper rate of filtration (and should not be below 60 gpm).
- 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
- Skimmers require cleaning.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
2 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Rate of filtration for the filtration system was 13.74 gpm/sq ft based on a filtration area of 7.06 sq ft (with flow rate 97 gpm), which exceeds the maximum allowed rate of filtration 12.5 gpm/sq ft. Note: the flow rate cannot exceed 88 gpm for proper rate of filtration (and should not be below 60 gpm).
- 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
- Skimmers require cleaning.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- the sample WE-24-0014506 submitted on February 13, 2024, was unsatisfactory: HPC 230.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Rate of filtration for the filtration system was 13.74 gpm/sq ft based on a filtration area of 7.06 sq ft (with flow rate 97 gpm), which exceeds the maximum allowed rate of filtration 12.5 gpm/sq ft. Note: the flow rate cannot exceed 88 gpm for proper rate of filtration (and should not be below 60 gpm).
- 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
- Skimmers require cleaning.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Monitoring Inspection
2 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Rate of filtration for the filtration system was 13.74 gpm/sq ft based on a filtration area of 7.06 sq ft (with flow rate 97 gpm), which exceeds the maximum allowed rate of filtration 12.5 gpm/sq ft. Note: the flow rate cannot exceed 88 gpm for proper rate of filtration (and should not be below 60 gpm).
- 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
- Skimmers require cleaning.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?