Moxy Banff - Swimming Pool
555 Banff Avenue Banff AB T1L 1B5 · Aquatic Facility
12 inspections
- Demand Inspection
0 infractions
- Demand Inspection
3 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Water sample from Monday May 25th, 2026, had Pseudomonas isolated. - Operators were informed to treat and re-sample.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Water sample from Monday May 25th, 2026, had total coliforms present. - Operators were informed to treat and re-sample.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample from Monday May 25th, 2026, had an HPC of 130 CFU/ml. Operators were informed to treat and re-sample.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
1 infraction
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Water sample from Monday May 25th, 2026, had total coliforms present. - Operators were informed to treat and re-sample.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample from Monday March 30th, 2026, was nor processed by the lab. Missing ID sticker on the bottle. - Operators were informed to submit a re-sample
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
0 infractions
- Monitoring Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Filtration rate was slightly high at 17.7 gpm/sqft. - Lower the flow rate so the filtration rate is less than 15 gpm/sqft.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample from Monday November 3rd, 2025, was not processed by the lab. No date was written on the form. -Operators were informed to submit a re-sample.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Filtration rate was slightly high at 17.7 gpm/sqft. - Lower the flow rate so the filtration rate is less than 15 gpm/sqft.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample from Monday April 14th, 2025, was not processed by the lab. Wrong date was written on the form. -Operators were informed to submit a re-sample.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Filtration rate was slightly high at 17.7 gpm/sqft. - Lower the flow rate so the filtration rate is less than 15 gpm/sqft.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Monitoring Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Filtration rate was slightly high at 17.7 gpm/sqft. - Lower the flow rate so the filtration rate is less than 15 gpm/sqft.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Monitoring Inspection
0 infractions
- Initial Inspection
1 infraction
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Free chlorine was measured as 1.16ppm. As pool was at 34C, free chlorine needs to be at least 2ppm. Controller ORP set point was increase during the inspection and when tested again the free chlorine level was 2.81ppm
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
1 infraction
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- The following statements are missing from the signage:Patrons must wash their hands using soap after using the washroom or changing diapers.Street footwear must not be worn in wet traffic areas.Patrons who are intoxicated will not be allowed to use the pool.No lifeguard on duty.Patrons should not swim alone.Also missing information as to the location of the fire alarm, telephone or other emergency devices (where applicable) and the permitted temperature range of the whirlpool.As well for the bather load, if going to leave as 7, need to indicate this is 7 per hour and have a method of tracking this or could put bather load of 14 (based on building code definition of bather load).
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?