Redwater Swimming Pool - Main Pool
5223 49 Avenue Redwater AB T0A 2W0 · Aquatic Facility
9 inspections
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The sample 26EN-160E00918 has an HPC of 450 CFU/mL. This can indicate a failure of the disinfection system. Ensure the pool chemistry is checked and another sample sent in next week.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Monitoring Inspection
0 infractions
- Monitoring Inspection
0 infractions
- Monitoring Inspection
0 infractions
- Risk Management Inspection
0 infractions
- Risk Management Inspection
0 infractions
- Demand Inspection
2 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- In water sample WE-23-0084350 there were total coliforms present and an HPC of 760 CFU/mL. Both of these results indicate a failure of the disinfection system. Ensure the pool chemistry is rebalanced and the water re-sampled on Manday Aug 14.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- The FAC is 0.02 ppm, the pH is less than 6.5, and the cyanuric acid is 11 ppm. This conditions are not conducive to maintaining adequate disinfection of the pool water. Ensure the FAC is above 0.5 ppm, the pH is between 6.8 and 7.6, and the cyanuric acid is between 25 and 50 ppm.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Monitoring Inspection
1 infraction
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- The FAC is 0.02 ppm, the pH is less than 6.5, and the cyanuric acid is 11 ppm. This conditions are not conducive to maintaining adequate disinfection of the pool water. Ensure the FAC is above 0.5 ppm, the pH is between 6.8 and 7.6, and the cyanuric acid is between 25 and 50 ppm.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- HPC at 320 CFU/mL
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?