Redwater Swimming Pool - Wading Pool

5223 49 Avenue Redwater AB T0A 2W0 · Aquatic Facility

Inspection summary

Redwater Swimming Pool - Wading Pool has been inspected 7 times by Alberta Health Services (Environmental Public Health) since May 24, 2024. The most recent inspection, on August 26, 2026, found no infractions.

5 of 7 inspections on record found no infractions at all. In the past 12 months there were 4 inspections with 2 infractions recorded. The higher-risk findings here relate to: Pool and spa water quality.

The number of infractions per inspection has stayed roughly the same over time.

What these findings mean

Health authorities word their findings differently, so we group them by what they mean for the people using the facility. Higher-risk findings are the ones that could directly cause illness or injury, such as water that is not properly treated.

  • Pool and spa water qualityHigher risk

    For pools, spas and splash pads, inspectors test disinfectant levels, pH and water clarity, and check safety equipment. Water that is not properly treated can spread skin, ear and stomach infections.

    Recorded 3 times across 2 separate inspections, most recently on August 21, 2026. For example: Is the bacteriological quality of the water in this pool satisfactory (Critical)?

About this data

These results come from Alberta Health Services (Environmental Public Health), which inspects food premises and other public facilities in this area. We republish the authority's public disclosure data and refresh it regularly; the official record is the final word.

7 inspections

  1. Risk Management Inspection

    0 infractions

  2. Demand Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Sample 26EN-231E01338 has P. aeruginosa present. This can indicate a failure of the disinfection system. Ensure the wading pool is closed and shock chlorinated at 20 PPM free chlorine for 2 hours. Then the free chlorine can be brought down and the wading pool re-opened.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Sample 26EN-231E01338 has an HPC of 1450 CFU/mL. This can indicate a failure of the disinfection system. Since the pool is closing before another sample will be sent in and the wading pool is going to be shocked no other follow up is necessary.
  3. Monitoring Inspection

    0 infractions

  4. Risk Management Inspection

    0 infractions

  5. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample 25EN-231E00865 has an HPC of 360 CFU/ mL. This can indicate a failure of the disinfection system. Ensure the pool chemical parameters are acceptable.
  6. Monitoring Inspection

    0 infractions

  7. Monitoring Inspection

    0 infractions