Riverwest Towers - Whirlpool
1088 6 Avenue SW Calgary AB T2P 5N3 · Aquatic Facility
2 inspections
- Monitoring Inspection
2 infractions
- 16. Are proper testing, monitoring, and other records being properly maintained?
- Total alkalinity is being recorded very low (15 ppm, 16 ppm, 20 ppm) but not corrective actions are being recorded. - Ensure that Total alkalinity is being tested accurately and adjusted as needed.- Total alkalinity must be maintained between 60-180 ppm.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Anti-entrapment form has some incorrect or missing information. - Verify the information on the form (verify jet flow, provide max flow rating of the drain covers, verify the new circ pump max flow rate. As per the form the max flow of the system might be exceeding the drain covers rating. Please verify the provide information on the form.)
- 16. Are proper testing, monitoring, and other records being properly maintained?
- Monitoring Inspection
0 infractions