Silhouette at Cranston - Whirlpool

30 Cranfield Link SE Calgary AB T3M 0C4 · Aquatic Facility

16 inspections

  1. Risk Management Inspection

    1 infraction

    • 11. Does the facility have a valid permit and does the facility operate in compliance with the conditions of that permit?
      • - Facility has not submitted an updated pool permit application. Please submit a new pool permit application. **Repeat Violation**The posted pool permit is not valid. Please re-apply for new pool permit to reflect change of ownership.
  2. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The water sample submitted on May 25, 2026, was rejected as the time of collection was not indicated., Please submit a new sample and ensure all details on the requisition form are included.
    • 11. Does the facility have a valid permit and does the facility operate in compliance with the conditions of that permit?
      • - Facility has not submitted an updated pool permit application. Please submit a new pool permit application. **Repeat Violation**The posted pool permit is not valid. Please re-apply for new pool permit to reflect change of ownership.
  3. Monitoring Inspection

    1 infraction

    • 11. Does the facility have a valid permit and does the facility operate in compliance with the conditions of that permit?
      • **Repeat Violation**The posted pool permit is not valid. Please re-apply for new pool permit to reflect change of ownership.
  4. Risk Management Inspection

    3 infractions

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The combined chlorines were not calculated as tCl was over range. - Please ensure that the combined chlorines as low as possible for maximum bather comfort.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • **Repeat Violation**Whirlpool facility changed the filter to a smaller size without notifying AHS. The surface area for the T60/60D is 3.1 according to its specifications. This provides the whirlpool with a max. flow rate of 38.75 gpm for whirlpools that were built after 2006. Currently the flow rate for the whirlpool is 60 gpm. Please consider changing the filter size in accordance to the maximum rate of filtration requirement for basins constructed after 2006. OR reduce the flow to 36, which is the minimum flow rate to meet the turnover period of 15 mins.
    • 11. Does the facility have a valid permit and does the facility operate in compliance with the conditions of that permit?
      • **Repeat Violation**The posted pool permit is not valid. Please re-apply for new pool permit to reflect change of ownership.
  5. Demand Inspection

    4 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Pseudomonas isolation in recent water sample collected and submitted January 19, 2026. Please treat the whirlpool and submit a re-sample.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The combined chlorines were not calculated as tCl was over range. - Please ensure that the combined chlorines as low as possible for maximum bather comfort.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • **Repeat Violation**Whirlpool facility changed the filter to a smaller size without notifying AHS. The surface area for the T60/60D is 3.1 according to its specifications. This provides the whirlpool with a max. flow rate of 38.75 gpm for whirlpools that were built after 2006. Currently the flow rate for the whirlpool is 60 gpm. Please consider changing the filter size in accordance to the maximum rate of filtration requirement for basins constructed after 2006. OR reduce the flow to 36, which is the minimum flow rate to meet the turnover period of 15 mins.
    • 11. Does the facility have a valid permit and does the facility operate in compliance with the conditions of that permit?
      • **Repeat Violation**The posted pool permit is not valid. Please re-apply for new pool permit to reflect change of ownership.
  6. Demand Inspection

    4 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Water sample submitted November 4, 2025, came back with pseudomonas isolated.Please treat and submit a resample.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The combined chlorines were not calculated as tCl was over range. - Please ensure that the combined chlorines as low as possible for maximum bather comfort.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • **Repeat Violation**Whirlpool facility changed the filter to a smaller size without notifying AHS. The surface area for the T60/60D is 3.1 according to its specifications. This provides the whirlpool with a max. flow rate of 38.75 gpm for whirlpools that were built after 2006. Currently the flow rate for the whirlpool is 60 gpm. Please consider changing the filter size in accordance to the maximum rate of filtration requirement for basins constructed after 2006. OR reduce the flow to 36, which is the minimum flow rate to meet the turnover period of 15 mins.
    • 11. Does the facility have a valid permit and does the facility operate in compliance with the conditions of that permit?
      • **Repeat Violation**The posted pool permit is not valid. Please re-apply for new pool permit to reflect change of ownership.
  7. Risk Management Inspection

    3 infractions

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The combined chlorines were not calculated as tCl was over range. - Please ensure that the combined chlorines as low as possible for maximum bather comfort.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • **Repeat Violation**Whirlpool facility changed the filter to a smaller size without notifying AHS. The surface area for the T60/60D is 3.1 according to its specifications. This provides the whirlpool with a max. flow rate of 38.75 gpm for whirlpools that were built after 2006. Currently the flow rate for the whirlpool is 60 gpm. Please consider changing the filter size in accordance to the maximum rate of filtration requirement for basins constructed after 2006. OR reduce the flow to 36, which is the minimum flow rate to meet the turnover period of 15 mins.
    • 11. Does the facility have a valid permit and does the facility operate in compliance with the conditions of that permit?
      • **Repeat Violation**The posted pool permit is not valid. Please re-apply for new pool permit to reflect change of ownership.
  8. Risk Management Inspection

    3 infractions

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The combined chlorines were not calculated as tCl was over range. - Please ensure that the combined chlorines as low as possible for maximum bather comfort.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • **Repeat Violation**Whirlpool facility changed the filter to a smaller size without notifying AHS. The surface area for the T60/60D is 3.1 according to its specifications. This provides the whirlpool with a max. flow rate of 38.75 gpm for whirlpools that were built after 2006. Currently the flow rate for the whirlpool is 60 gpm. Please consider changing the filter size in accordance to the maximum rate of filtration requirement for basins constructed after 2006. OR reduce the flow to 36, which is the minimum flow rate to meet the turnover period of 15 mins.
    • 11. Does the facility have a valid permit and does the facility operate in compliance with the conditions of that permit?
      • **Repeat Violation**The posted pool permit is not valid. Please re-apply for new pool permit to reflect change of ownership.
  9. Demand Inspection

    4 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample submitted collected on September 29, 2025, was not processed as it was received during a holiday without prior approval. - Submit a resample.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The combined chlorines were not calculated as tCl was over range. - Please ensure that the combined chlorines as low as possible for maximum bather comfort.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • **Repeat Violation**Whirlpool facility changed the filter to a smaller size without notifying AHS. The surface area for the T60/60D is 3.1 according to its specifications. This provides the whirlpool with a max. flow rate of 38.75 gpm for whirlpools that were built after 2006. Currently the flow rate for the whirlpool is 60 gpm. Please consider changing the filter size in accordance to the maximum rate of filtration requirement for basins constructed after 2006. OR reduce the flow to 36, which is the minimum flow rate to meet the turnover period of 15 mins.
    • 11. Does the facility have a valid permit and does the facility operate in compliance with the conditions of that permit?
      • **Repeat Violation**The posted pool permit is not valid. Please re-apply for new pool permit to reflect change of ownership.
  10. Demand Inspection

    3 infractions

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The combined chlorines were not calculated as tCl was over range. - Please ensure that the combined chlorines as low as possible for maximum bather comfort.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • **Repeat Violation**Whirlpool facility changed the filter to a smaller size without notifying AHS. The surface area for the T60/60D is 3.1 according to its specifications. This provides the whirlpool with a max. flow rate of 38.75 gpm for whirlpools that were built after 2006. Currently the flow rate for the whirlpool is 60 gpm. Please consider changing the filter size in accordance to the maximum rate of filtration requirement for basins constructed after 2006. OR reduce the flow to 36, which is the minimum flow rate to meet the turnover period of 15 mins.
    • 11. Does the facility have a valid permit and does the facility operate in compliance with the conditions of that permit?
      • **Repeat Violation**The posted pool permit is not valid. Please re-apply for new pool permit to reflect change of ownership.
  11. Demand Inspection

    3 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample submitted on June 30, 2025 was not processed as it was received during statutory holiday without prior approval. - Submit a resample.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Whirtpool facility changed the filter to a smaller size without notifying AHS. The surface area for the T60/60D is 3.1 according to its specifications. This provides the whirlpool with a max. flow rate of 38.75 gpm for whirlpools that were built after 2006. Currently the flow rate for the whirlpool is 60 gpm. Please consider changing the filter size in accordance to the maximum rate of filtration requirement for basins constructed after 2006.
    • 11. Does the facility have a valid permit and does the facility operate in compliance with the conditions of that permit?
      • The posted pool permit is not valid. Please re-apply for new pool permit to reflect change of ownership.
  12. Risk Management Inspection

    3 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Feb. 5, 2025 water sample was not processed as date and time of collection was not provided.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Whirtpool facility changed the filter to a smaller size without notifying AHS. The surface area for the T60/60D is 3.1 according to its specifications. This provides the whirlpool with a max. flow rate of 38.75 gpm for whirlpools that were built after 2006. Currently the flow rate for the whirlpool is 60 gpm. Please consider changing the filter size in accordance to the maximum rate of filtration requirement for basins constructed after 2006.
    • 11. Does the facility have a valid permit and does the facility operate in compliance with the conditions of that permit?
      • The posted pool permit is not valid. Please re-apply for new pool permit to reflect change of ownership.
  13. Demand Inspection

    3 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Feb. 5, 2025 water sample was not processed as date and time of collection was not provided.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Whirtpool facility changed the filter to a smaller size without notifying AHS. The surface area for the T60/60D is 3.1 according to its specifications. This provides the whirlpool with a max. flow rate of 38.75 gpm for whirlpools that were built after 2006. Currently the flow rate for the whirlpool is 60 gpm. Please consider changing the filter size in accordance to the maximum rate of filtration requirement for basins constructed after 2006.
    • 11. Does the facility have a valid permit and does the facility operate in compliance with the conditions of that permit?
      • The posted pool permit is not valid. Please re-apply for new pool permit to reflect change of ownership.
  14. Monitoring Inspection

    2 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Whirtpool facility changed the filter to a smaller size without notifying AHS. The surface area for the T60/60D is 3.1 according to its specifications. This provides the whirlpool with a max. flow rate of 38.75 gpm for whirlpools that were built after 2006. Currently the flow rate for the whirlpool is 60 gpm. Please consider changing the filter size in accordance to the maximum rate of filtration requirement for basins constructed after 2006.
    • 11. Does the facility have a valid permit and does the facility operate in compliance with the conditions of that permit?
      • The posted pool permit is not valid. Please re-apply for new pool permit to reflect change of ownership.
  15. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • May 13, 2024 sample was not processed. Collection date is later than the date of receipt. Spoke with Arlen to resample.
  16. Demand Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Sept. 26, 2023 water sample had p. aeruginosa isolated and 460 hpc. Left message for Arken (sampler) to treat and resample.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Sept. 26, 2023 water sample had p. aeruginosa isolated and 460 hpc. Left message for Arken (sampler) to treat and resample.