Tality East Village - Cold Plunge 1-2
150 - 606 Confluence Way SE Calgary AB T2G 0G1 · Aquatic Facility
6 inspections
- Risk Management Inspection
0 infractions
- Risk Management Inspection
1 infraction
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- 1) The combined chlorine (CC) for tub 1 was: 2.52ppm and 2.43ppm (second test). 2) The combined chlorine (CC) for tub 2 was: 2.44ppm. Please maintain the CC as low as possible to reduce bather irritation. It is recommended to keep the CC below 1.0ppm.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
5 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- The water sample collected from Tub 2 on June 10, 2026, had total coliforms present.-Treat and resample
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- The water sample collected from Tub 2 on June 4, 2026, had total coliforms present.-Treat and resample
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample collected from Tub 2 on June 4, 2026, had a heterotrophic plate count of 200 CFU/mL.-Resample
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- 1) The free chlorine residual reading in Tub 1 was 0.55 mg/L.2) The free chlorine residual reading in Tub 2 was 0.62 mg/L.-Maintain free chlorine above 1 mg/L. Recommended to aim for 3-5 mg/L
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The automated reader had an ORP reading of 815 mV, and the set point was at 810 mV, so no chlorine was being added to the system, and therefore not providing adequate chlorine levels.-Set the automated feeding system so that there is adequate chlorine in the system, and recalibrate/clean the probes if necessary/indicated by manufacturer's instructions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
2 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- The water sample collected from Tub 2 on June 4, 2026, had total coliforms present.-Treat and resample
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample collected from Tub 2 on June 4, 2026, had a heterotrophic plate count of 200 CFU/mL.-Resample
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Initial Inspection
0 infractions
- Demand Inspection
0 infractions