The Westin Calgary Airport - Whirlpool
671 Aero Drive NE Calgary AB T2E 7Y5 · Aquatic Facility
Inspection summary
The Westin Calgary Airport - Whirlpool has been inspected 32 times by Alberta Health Services (Environmental Public Health) since December 31, 2023. The most recent inspection, on September 8, 2026, recorded 3 infractions.
None of the 32 inspections on record were free of infractions. In the past 12 months there were 14 inspections with 52 infractions recorded. The higher-risk findings here relate to: Pool and spa water quality and Chemicals and toxic substances.
The number of infractions per inspection has stayed roughly the same over time.
What these findings mean
Health authorities word their findings differently, so we group them by what they mean for the people using the facility. Higher-risk findings are the ones that could directly cause illness or injury, such as water that is not properly treated.
Pool and spa water qualityHigher risk
For pools, spas and splash pads, inspectors test disinfectant levels, pH and water clarity, and check safety equipment. Water that is not properly treated can spread skin, ear and stomach infections.
Recorded 51 times across 30 separate inspections, most recently on September 8, 2026. For example:
Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
Chemicals and toxic substancesHigher risk
Pool chemicals such as chlorine and acid must be labelled, stored apart from each other and handled safely. Mixing them by mistake can release toxic gas, so storage and handling problems are treated seriously.
Recorded 27 times across 27 separate inspections, most recently on September 8, 2026. For example:
Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
Permits, records and postingLower risk
Operating permits, water-test logs, posted bather rules and emergency procedures. Daily test logs are how operators show the water was checked and treated between inspections.
Recorded 32 times across 32 separate inspections, most recently on September 8, 2026. For example:
Are proper testing, monitoring, and other records being properly maintained?
About this data
These results come from Alberta Health Services (Environmental Public Health), which inspects food premises and other public facilities in this area. We republish the authority's public disclosure data and refresh it regularly; the official record is the final word.
32 inspections
- Risk Management Inspection
3 infractions
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The combined chlorines in the whirlpool were measured to be 1.06 ppm.REQUIREMENT: Ensure that the combined chlorines are maintained at the lowest level possible.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- According to the whirlpool's flow meter, the current flow of ~60 USGPM is too slow to meet the minimum turnover period of 20 minutes.REQUIREMENT: Maintain the flow between the minimum and maximum flow rates specified.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- The whirlpool operating records were incomplete. The following was not being recorded:- Quantities of all chemicals used.REQUIREMENT: Ensure the above operating records are being maintained on a daily basis.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
4 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- **UNSATISFACTORY WATER SAMPLE TEST RESULT**The water sample collected on August 13, 2026, was unsatisfactory with the presence of Pseudomonas aeruginosa.The water sample collected on August 21, 2026, was unsatisfactory with the presence of Pseudomonas aeruginosa.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The combined chlorines in the whirlpool were measured to be 1.06 ppm.REQUIREMENT: Ensure that the combined chlorines are maintained at the lowest level possible.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- According to the whirlpool's flow meter, the current flow of ~60 USGPM is too slow to meet the minimum turnover period of 20 minutes.REQUIREMENT: Maintain the flow between the minimum and maximum flow rates specified.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- The whirlpool operating records were incomplete. The following was not being recorded:- Quantities of all chemicals used.REQUIREMENT: Ensure the above operating records are being maintained on a daily basis.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
4 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- The water sample collected on August 13, 2026, was unsatisfactory with the presence of Pseudomonas aeruginosa.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The combined chlorines in the whirlpool were measured to be 1.06 ppm.REQUIREMENT: Ensure that the combined chlorines are maintained at the lowest level possible.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- According to the whirlpool's flow meter, the current flow of ~60 USGPM is too slow to meet the minimum turnover period of 20 minutes.REQUIREMENT: Maintain the flow between the minimum and maximum flow rates specified.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- The whirlpool operating records were incomplete. The following was not being recorded:- Quantities of all chemicals used.REQUIREMENT: Ensure the above operating records are being maintained on a daily basis.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
3 infractions
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The combined chlorines in the whirlpool were measured to be 1.06 ppm.REQUIREMENT: Ensure that the combined chlorines are maintained at the lowest level possible.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- According to the whirlpool's flow meter, the current flow of ~60 USGPM is too slow to meet the minimum turnover period of 20 minutes.REQUIREMENT: Maintain the flow between the minimum and maximum flow rates specified.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- The whirlpool operating records were incomplete. The following was not being recorded:- Quantities of all chemicals used.REQUIREMENT: Ensure the above operating records are being maintained on a daily basis.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
5 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Water sample (26ES-183E00027) collected on July 02, 2026, tested positive for Pseudomonas aeruginosa.Please clean, treat and resample.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample (26ES-183E00027) collected on July 02, 2026, tested positive for Heterotrophic Plate Count (250 CFU/100mlPlease treat and resample.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The combined chlorines in the whirlpool were measured to be 1.06 ppm.REQUIREMENT: Ensure that the combined chlorines are maintained at the lowest level possible.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- According to the whirlpool's flow meter, the current flow of ~60 USGPM is too slow to meet the minimum turnover period of 20 minutes.REQUIREMENT: Maintain the flow between the minimum and maximum flow rates specified.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- The whirlpool operating records were incomplete. The following was not being recorded:- Quantities of all chemicals used.REQUIREMENT: Ensure the above operating records are being maintained on a daily basis.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
3 infractions
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The combined chlorines in the whirlpool were measured to be 1.06 ppm.REQUIREMENT: Ensure that the combined chlorines are maintained at the lowest level possible.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- According to the whirlpool's flow meter, the current flow of ~60 USGPM is too slow to meet the minimum turnover period of 20 minutes.REQUIREMENT: Maintain the flow between the minimum and maximum flow rates specified.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- The whirlpool operating records were incomplete. The following was not being recorded:- Quantities of all chemicals used.REQUIREMENT: Ensure the above operating records are being maintained on a daily basis.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
4 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample collected on March 23, 2026, was not tested because the sample was received more than 24 hours after collection.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The combined chlorines in the whirlpool were measured to be 1.06 ppm.REQUIREMENT: Ensure that the combined chlorines are maintained at the lowest level possible.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- According to the whirlpool's flow meter, the current flow of ~60 USGPM is too slow to meet the minimum turnover period of 20 minutes.REQUIREMENT: Maintain the flow between the minimum and maximum flow rates specified.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- The whirlpool operating records were incomplete. The following was not being recorded:- Quantities of all chemicals used.REQUIREMENT: Ensure the above operating records are being maintained on a daily basis.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
4 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample collected on March 23, 2026, was not tested because the sample was received more than 24 hours after collection.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The combined chlorines in the whirlpool were measured to be 1.06 ppm.REQUIREMENT: Ensure that the combined chlorines are maintained at the lowest level possible.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- According to the whirlpool's flow meter, the current flow of ~60 USGPM is too slow to meet the minimum turnover period of 20 minutes.REQUIREMENT: Maintain the flow between the minimum and maximum flow rates specified.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- The whirlpool operating records were incomplete. The following was not being recorded:- Quantities of all chemicals used.REQUIREMENT: Ensure the above operating records are being maintained on a daily basis.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
3 infractions
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The combined chlorines in the whirlpool were measured to be 1.06 ppm.REQUIREMENT: Ensure that the combined chlorines are maintained at the lowest level possible.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- According to the whirlpool's flow meter, the current flow of ~60 USGPM is too slow to meet the minimum turnover period of 20 minutes.REQUIREMENT: Maintain the flow between the minimum and maximum flow rates specified.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- The whirlpool operating records were incomplete. The following was not being recorded:- Quantities of all chemicals used.REQUIREMENT: Ensure the above operating records are being maintained on a daily basis.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
4 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample (26ES-055E00643) collected on February 24, 2026, was cancelled as the date of collection was not clearly legible.Please submit another water sample.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The combined chlorines in the whirlpool were measured to be 1.06 ppm.REQUIREMENT: Ensure that the combined chlorines are maintained at the lowest level possible.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- According to the whirlpool's flow meter, the current flow of ~60 USGPM is too slow to meet the minimum turnover period of 20 minutes.REQUIREMENT: Maintain the flow between the minimum and maximum flow rates specified.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- The whirlpool operating records were incomplete. The following was not being recorded:- Quantities of all chemicals used.REQUIREMENT: Ensure the above operating records are being maintained on a daily basis.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
3 infractions
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The combined chlorines in the whirlpool were measured to be 1.06 ppm.REQUIREMENT: Ensure that the combined chlorines are maintained at the lowest level possible.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- According to the whirlpool's flow meter, the current flow of ~60 USGPM is too slow to meet the minimum turnover period of 20 minutes.REQUIREMENT: Maintain the flow between the minimum and maximum flow rates specified.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- The whirlpool operating records were incomplete. The following was not being recorded:- Quantities of all chemicals used.REQUIREMENT: Ensure the above operating records are being maintained on a daily basis.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
4 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Water sample (26ES-037E00169) collected on February 6, 2026, came back unsatisfactory as Pseudomonas aeruginosa was present.Please treat the water, chemically balance and resample the whirlpool as soon as possible.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The combined chlorines in the whirlpool were measured to be 1.06 ppm.REQUIREMENT: Ensure that the combined chlorines are maintained at the lowest level possible.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- According to the whirlpool's flow meter, the current flow of ~60 USGPM is too slow to meet the minimum turnover period of 20 minutes.REQUIREMENT: Maintain the flow between the minimum and maximum flow rates specified.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- The whirlpool operating records were incomplete. The following was not being recorded:- Quantities of all chemicals used.REQUIREMENT: Ensure the above operating records are being maintained on a daily basis.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
3 infractions
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The combined chlorines in the whirlpool were measured to be 1.06 ppm.REQUIREMENT: Ensure that the combined chlorines are maintained at the lowest level possible.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- According to the whirlpool's flow meter, the current flow of ~60 USGPM is too slow to meet the minimum turnover period of 20 minutes.REQUIREMENT: Maintain the flow between the minimum and maximum flow rates specified.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- The whirlpool operating records were incomplete. The following was not being recorded:- Quantities of all chemicals used.REQUIREMENT: Ensure the above operating records are being maintained on a daily basis.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
5 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- The water sample that was collected on October 17, 2025, was unsatisfactory with the following results: Presence of Pseudomonas aeruginosa.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample that was collected on October 17, 2025, was unsatisfactory with the following results: Presence of Pseudomonas aeruginosa, HPC of 2,330 CFU/mL.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The combined chlorines in the whirlpool were measured to be 1.06 ppm.REQUIREMENT: Ensure that the combined chlorines are maintained at the lowest level possible.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- According to the whirlpool's flow meter, the current flow of ~60 USGPM is too slow to meet the minimum turnover period of 20 minutes.REQUIREMENT: Maintain the flow between the minimum and maximum flow rates specified.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- The whirlpool operating records were incomplete. The following was not being recorded:- Quantities of all chemicals used.REQUIREMENT: Ensure the above operating records are being maintained on a daily basis.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
3 infractions
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The combined chlorines in the whirlpool were measured to be 1.06 ppm.REQUIREMENT: Ensure that the combined chlorines are maintained at the lowest level possible.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- According to the whirlpool's flow meter, the current flow of ~60 USGPM is too slow to meet the minimum turnover period of 20 minutes.REQUIREMENT: Maintain the flow between the minimum and maximum flow rates specified.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- The whirlpool operating records were incomplete. The following was not being recorded:- Quantities of all chemicals used.REQUIREMENT: Ensure the above operating records are being maintained on a daily basis.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
4 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample collected on August 29, 2025, was unsatisfactory with an HPC of 350 CFU/mL.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The combined chlorines in the whirlpool were measured to be 1.06 ppm.REQUIREMENT: Ensure that the combined chlorines are maintained at the lowest level possible.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- According to the whirlpool's flow meter, the current flow of ~60 USGPM is too slow to meet the minimum turnover period of 20 minutes.REQUIREMENT: Maintain the flow between the minimum and maximum flow rates specified.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- The whirlpool operating records were incomplete. The following was not being recorded:- Quantities of all chemicals used.REQUIREMENT: Ensure the above operating records are being maintained on a daily basis.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
3 infractions
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The combined chlorines in the whirlpool were measured to be 1.06 ppm.REQUIREMENT: Ensure that the combined chlorines are maintained at the lowest level possible.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- According to the whirlpool's flow meter, the current flow of ~60 USGPM is too slow to meet the minimum turnover period of 20 minutes.REQUIREMENT: Maintain the flow between the minimum and maximum flow rates specified.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- The whirlpool operating records were incomplete. The following was not being recorded:- Quantities of all chemicals used.REQUIREMENT: Ensure the above operating records are being maintained on a daily basis.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
5 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- The water sample collected on July 11, 2025, was unsatisfactory with the presence of Pseudomonas aeruginosa. The whirlpool must be treated, and another water sample must be submitted for further re-assessment. Instructions were provided to the hotel manager and the pool operator for treating the whirlpool.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample collected on July 4, 2025, was not tested due to the date of collection not indicated on the requisition form. Send another sample immediately.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The combined chlorines in the whirlpool were measured to be 1.06 ppm.REQUIREMENT: Ensure that the combined chlorines are maintained at the lowest level possible.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- According to the whirlpool's flow meter, the current flow of ~60 USGPM is too slow to meet the minimum turnover period of 20 minutes.REQUIREMENT: Maintain the flow between the minimum and maximum flow rates specified.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- The whirlpool operating records were incomplete. The following was not being recorded:- Quantities of all chemicals used.REQUIREMENT: Ensure the above operating records are being maintained on a daily basis.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
4 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample collected on July 4, 2025, was not tested due to the date of collection not indicated on the requisition form. Send another sample immediately.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The combined chlorines in the whirlpool were measured to be 1.06 ppm.REQUIREMENT: Ensure that the combined chlorines are maintained at the lowest level possible.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- According to the whirlpool's flow meter, the current flow of ~60 USGPM is too slow to meet the minimum turnover period of 20 minutes.REQUIREMENT: Maintain the flow between the minimum and maximum flow rates specified.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- The whirlpool operating records were incomplete. The following was not being recorded:- Quantities of all chemicals used.REQUIREMENT: Ensure the above operating records are being maintained on a daily basis.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
3 infractions
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The combined chlorines in the whirlpool were measured to be 1.06 ppm.REQUIREMENT: Ensure that the combined chlorines are maintained at the lowest level possible.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- According to the whirlpool's flow meter, the current flow of ~60 USGPM is too slow to meet the minimum turnover period of 20 minutes.REQUIREMENT: Maintain the flow between the minimum and maximum flow rates specified.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- The whirlpool operating records were incomplete. The following was not being recorded:- Quantities of all chemicals used.REQUIREMENT: Ensure the above operating records are being maintained on a daily basis.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
4 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- The water sample collected on April 25, 2025, was unsatisfactory with total coliforms present. Please submit another water sample immediately.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The combined chlorines in the whirlpool were measured to be 1.06 ppm.REQUIREMENT: Ensure that the combined chlorines are maintained at the lowest level possible.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- According to the whirlpool's flow meter, the current flow of ~60 USGPM is too slow to meet the minimum turnover period of 20 minutes.REQUIREMENT: Maintain the flow between the minimum and maximum flow rates specified.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- The whirlpool operating records were incomplete. The following was not being recorded:- Quantities of all chemicals used.REQUIREMENT: Ensure the above operating records are being maintained on a daily basis.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
3 infractions
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The combined chlorines in the whirlpool were measured to be 1.06 ppm.REQUIREMENT: Ensure that the combined chlorines are maintained at the lowest level possible.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- According to the whirlpool's flow meter, the current flow of ~60 USGPM is too slow to meet the minimum turnover period of 20 minutes.REQUIREMENT: Maintain the flow between the minimum and maximum flow rates specified.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- The whirlpool operating records were incomplete. The following was not being recorded:- Quantities of all chemicals used.REQUIREMENT: Ensure the above operating records are being maintained on a daily basis.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
4 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- The water sample collected on April 4, 2025, had Pseudomonas aeruginosa isolated. Instructions provided to the operator on how to treat the whirlpool and submit another water sample immediately.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The combined chlorines in the whirlpool were measured to be 1.06 ppm.REQUIREMENT: Ensure that the combined chlorines are maintained at the lowest level possible.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- According to the whirlpool's flow meter, the current flow of ~60 USGPM is too slow to meet the minimum turnover period of 20 minutes.REQUIREMENT: Maintain the flow between the minimum and maximum flow rates specified.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- The whirlpool operating records were incomplete. The following was not being recorded:- Quantities of all chemicals used.REQUIREMENT: Ensure the above operating records are being maintained on a daily basis.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
3 infractions
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The combined chlorines in the whirlpool were measured to be 1.06 ppm.REQUIREMENT: Ensure that the combined chlorines are maintained at the lowest level possible.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- According to the whirlpool's flow meter, the current flow of ~60 USGPM is too slow to meet the minimum turnover period of 20 minutes.REQUIREMENT: Maintain the flow between the minimum and maximum flow rates specified.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- The whirlpool operating records were incomplete. The following was not being recorded:- Quantities of all chemicals used.REQUIREMENT: Ensure the above operating records are being maintained on a daily basis.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
5 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Water sample - collected February 28, 2025 tested positive for Pseudomonas aeruginosa. HPC 60CFU/Action Required /TakenWhirlpool must be treated and cleaned as per AHS guidance document. Guidance document was sent via email. Resample must be taken after full treatment and cleaning have been completed.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Resample submitted March 7 as a result of a positive water sample for Pseudomonas on February 28 was not tested due to incorrect information on requisition form.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The combined chlorines in the whirlpool were measured to be 1.06 ppm.REQUIREMENT: Ensure that the combined chlorines are maintained at the lowest level possible.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- According to the whirlpool's flow meter, the current flow of ~60 USGPM is too slow to meet the minimum turnover period of 20 minutes.REQUIREMENT: Maintain the flow between the minimum and maximum flow rates specified.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- The whirlpool operating records were incomplete. The following was not being recorded:- Quantities of all chemicals used.REQUIREMENT: Ensure the above operating records are being maintained on a daily basis.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
4 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Water sample - collected February 28, 2025 tested positive for Pseudomonas aeruginosa. HPC 60CFU/Action Required /TakenWhirlpool must be treated and cleaned as per AHS guidance document. Guidance document was sent via email. Resample must be taken after full treatment and cleaning have been completed.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The combined chlorines in the whirlpool were measured to be 1.06 ppm.REQUIREMENT: Ensure that the combined chlorines are maintained at the lowest level possible.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- According to the whirlpool's flow meter, the current flow of ~60 USGPM is too slow to meet the minimum turnover period of 20 minutes.REQUIREMENT: Maintain the flow between the minimum and maximum flow rates specified.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- The whirlpool operating records were incomplete. The following was not being recorded:- Quantities of all chemicals used.REQUIREMENT: Ensure the above operating records are being maintained on a daily basis.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Monitoring Inspection
3 infractions
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The combined chlorines in the whirlpool were measured to be 1.06 ppm.REQUIREMENT: Ensure that the combined chlorines are maintained at the lowest level possible.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- According to the whirlpool's flow meter, the current flow of ~60 USGPM is too slow to meet the minimum turnover period of 20 minutes.REQUIREMENT: Maintain the flow between the minimum and maximum flow rates specified.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- The whirlpool operating records were incomplete. The following was not being recorded:- Quantities of all chemicals used.REQUIREMENT: Ensure the above operating records are being maintained on a daily basis.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
1 infraction
- 16. Are proper testing, monitoring, and other records being properly maintained?
- The whirlpool operating records were incomplete. The following was not being recorded:- Automated controller set points and readings for ORP, chlorine and pH- Quantities and dates of all chemicals used.REQUIREMENT: Ensure the above operating records are being maintained on a daily basis.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample collected on May 03, 2024, had an HPC count of 110 CFU/mL.REQUIREMENT: Review the water chemistry and treat the water. Send in a re-sample once the water treatments are complete and the water chemistry is re-balanced.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- The whirlpool operating records were incomplete. The following was not being recorded:- Automated controller set points and readings for ORP, chlorine and pH- Quantities and dates of all chemicals used.REQUIREMENT: Ensure the above operating records are being maintained on a daily basis.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Monitoring Inspection
1 infraction
- 16. Are proper testing, monitoring, and other records being properly maintained?
- The whirlpool operating records were incomplete. The following was not being recorded:- Automated controller set points and readings for ORP, chlorine and pH- Quantities and dates of all chemicals used.REQUIREMENT: Ensure the above operating records are being maintained on a daily basis.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- Demand Inspection
3 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- The water sample collected on February 23, 2024, had pseudomonas isolated in the sample.REQUIREMENT: Begin treatment for the whirlpool immediately and send a re-sample for the whirlpool after you complete necessary treatments. Indicate on the requisition form that the sample is a ‘resample’.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The flow meter for the whirlpool was broken. There was no reading from the flow meter despite the recirculation system operating.REQUIREMENT: Repair or replace the flow meter. Ensure the flow is maintained between the minimum and maximum flow rate.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- The whirlpool operating records were incomplete. The following was not being recorded:- Water Clarity- Water Temperature- Automated controller set points and readings for ORP, chlorine and pH- Quantities and dates of all chemicals used.- Equipment maintenance (e.g. filter PSI)- make and model, purchase and expiry date of suction outlet covers, and manufacturers’ recommended flow rate.The time of water chemistry tests was not consistent, as some recording had been written down in non-chronological order.REQUIREMENT: Ensure the above operating records are being maintained on a daily basis.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
3 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Dec. 28th, 2023 sample had pseudomonas isolated. LVM for Arnold (Sampler) to treat and resample.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The flow meter for the whirlpool was broken. There was no reading from the flow meter despite the recirculation system operating.REQUIREMENT: Repair or replace the flow meter. Ensure the flow is maintained between the minimum and maximum flow rate.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- The whirlpool operating records were incomplete. The following was not being recorded:- Water Clarity- Water Temperature- Automated controller set points and readings for ORP, chlorine and pH- Quantities and dates of all chemicals used.- Equipment maintenance (e.g. filter PSI)- make and model, purchase and expiry date of suction outlet covers, and manufacturers’ recommended flow rate.The time of water chemistry tests was not consistent, as some recording had been written down in non-chronological order.REQUIREMENT: Ensure the above operating records are being maintained on a daily basis.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
Nearby inspected facilities
- The Westin Calgary Airport - Swimming Pool
671 Aero Drive NE Calgary AB T2E 7Y5
16 inspections
- The Westin Calgary Airport - Common Area
671 Aero Drive NE Calgary AB T2E 7Y5
3 inspections
- The Westin Calgary Airport - Main Kitchen
671 Aero Drive NE Calgary AB T2E 7Y5
2 inspections
- The Westin Calgary Airport - Banquet Kitchen
671 Aero Drive NE Calgary AB T2E 7Y5
1 inspection
- Ace Casinos Airport
40 Aero Crescent NE Calgary AB T2E 7Y5
4 inspections
- Take Flight Group
263 Aero Way NE Calgary AB T2E 6K2
1 inspection
- Park Inn Calgary Airport North
27 Freeport Crescent NE Calgary AB T3J 0T4
1 inspection
- Hotel 11 - Whirlpool
11 Freeport Crescent NE Calgary AB T3J 0T4
13 inspections