- Risk Management Inspection
0 infractions
- Monitoring Inspection
2 infractions
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Free chlorine was measured at 0.01 ppmFree chlorine is required to be at least 1.0 ppm for a swimming pool (temperature less than or equal to 30 C). Alternatively, free chlorine can be at least:a) 0.5 ppm if able to consistently maintain an ORP value of no less than 700 mV, orb) 0.3 ppm if able to consistently maintain an ORP value of no less than 770 mV, a pH of no more than 7.3 and when supplemental disinfection is used.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Total Alkalinity was measured at 44 ppm.The required operating range is 60 to 180 ppm.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Monitoring Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The basin was overfilled with the water level above the top of the skimmer. The basin was not adequately skimming. Please drain so the water level is about halfway above the skimmer opening
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
0 infractions
- Risk Management Inspection
2 infractions
- 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
- Main Drains in the basin are expired and must be replaced before the basin can reopen. Basin is drained and undergoing maintenance. Refer to installation concerns with replacement covers noted in the anti-entrapment compliance plan (version 24-05) completed by Automated Aquatics.
- 18. Have plans for construction, renovations or alteration for the pool been submitted for written approval?
- Construction/renovation plans have not been received.
- 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
- Demand Inspection
1 infraction
- 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
- Main Drains in the basin are expired and must be replaced before the basin can reopen. Basin is drained and undergoing maintenance. Refer to installation concerns with replacement covers noted in the anti-entrapment compliance plan (version 24-05) completed by Automated Aquatics.
- 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
- Risk Management Inspection
1 infraction
- 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
- Main Drains in the basin are expired and must be replaced before the basin can reopen. Basin is drained and undergoing maintenance. Refer to installation concerns with replacement covers noted in the anti-entrapment compliance plan (version 24-05) completed by Automated Aquatics.
- 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The microbiological water sample submitted on 22/11/2024 was unsatisfactory: HPC >100 CFU/mL. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
- 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
- Main Drains in the basin are expired and must be replaced before the basin can reopen. Basin is drained and undergoing maintenance. Refer to installation concerns with replacement covers noted in the anti-entrapment compliance plan (version 24-05) completed by Automated Aquatics.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
1 infraction
- 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
- Main Drains in the basin are expired and must be replaced before the basin can reopen. Basin is drained and undergoing maintenance. Refer to installation concerns with replacement covers noted in the anti-entrapment compliance plan (version 24-05) completed by Automated Aquatics.
- 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
- Risk Management Inspection
0 infractions
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The microbiological samples collected2024-05-02 Accession #: WE-24-0042562 was unsatisfactory- HPC 3130 cfu/ml.Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Combined Chlorine: 1.88ppmKeep the combined chlorine at minimum. Ideally it should be maintained under 1ppm.Alkalinity: 52ppmMaintain Alkalinity between 60-180ppm.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The microbiological samples collected2024-05-02 Accession #: WE-24-0042562 was unsatisfactory- HPC 3130 cfu/ml.Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Alkalinity: 42ppmMaintain Alkalinity between 60-180ppm.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Flow meter for the slide was not functional. Flow rate for the slide could not be taken.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Monitoring Inspection
2 infractions
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Combined Chlorine: 1.88ppmKeep the combined chlorine at minimum. Ideally it should be maintained under 1ppm.Alkalinity: 52ppmMaintain Alkalinity between 60-180ppm.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Filtration rate does not comply with the manufactures specifications. The flow rate was higher than the maximum flow listed of 73.65 GPM.Adjust the flow rate between 42.5USGPM to 73.65 USGPM.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
2 infractions
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Broken gutter covers were noted. Replace the covers.Plans in place to shut down from Dec 18-20, 2023 for repairs.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- Daily visual checks of main drain covers were not being done and recorded. Discussed with operator onsite and advise to do a visual check daily and keep record with other chemical parameters.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Demand Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The microbiological water sample result submitted on 2nd April 2024 [Accession #: WE-24-0030656] was unsatisfactory. HPC ;4320CFU/ml.Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Broken gutter covers were noted. Replace the covers.Plans in place to shut down from Dec 18-20, 2023 for repairs.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- Daily visual checks of main drain covers were not being done and recorded. Discussed with operator onsite and advise to do a visual check daily and keep record with other chemical parameters.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
2 infractions
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Broken gutter covers were noted. Replace the covers.Plans in place to shut down from Dec 18-20, 2023 for repairs.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- Daily visual checks of main drain covers were not being done and recorded. Discussed with operator onsite and advise to do a visual check daily and keep record with other chemical parameters.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Demand Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The microbiological water sample result submitted on 2023-11-30 [Accession #: WE-23-0128573] was unsatisfactory. HPC 260 CFU/mL. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Broken gutter covers were noted. Replace the covers.Plans in place to shut down from Dec 18-20, 2023 for repairs.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- Daily visual checks of main drain covers were not being done and recorded. Discussed with operator onsite and advise to do a visual check daily and keep record with other chemical parameters.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
2 infractions
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Broken gutter covers were noted. Replace the covers.Plans in place to shut down from Dec 18-20, 2023 for repairs.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- Daily visual checks of main drain covers were not being done and recorded. Discussed with operator onsite and advise to do a visual check daily and keep record with other chemical parameters.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Risk Management Inspection
5 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The sample WE-23-0124617 submitted on 21-November-2023, was unsatisfactory; HPC >57000 CFU/ml.Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
- 06. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Critical)?
- There was leakage in the pump. The pool was closed at the time of inspection.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Jet pump was not tagged to allow safe operations. Tag the jet pump to allow safe operation and prevent exceedance of Flow rate.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Broken gutter covers were noted. Replace the covers.Plans in place to shut down from Dec 18-20, 2023 for repairs.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- Daily visual checks of main drain covers were not being done and recorded. Discussed with operator onsite and advise to do a visual check daily and keep record with other chemical parameters.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The sample WE-23-0124617 submitted on 21-November-2023, was unsatisfactory; HPC >57000 CFU/ml.Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Violation brought forward from previous inspection report.The majority of the drainage gutters had been repaired. There were still a couple broken gutter covers and the operator was awaiting more materials to finish repairs. Rusting was observed on the slide staircase.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Monitoring Inspection
2 infractions
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Alkalinity was measured at 0.00ppm. Ensure alkalinity is maintained between 60-180ppm for bather comfort.Operator addressed the issue during insepction onsite.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Violation brought forward from previous inspection report.The majority of the drainage gutters had been repaired. There were still a couple broken gutter covers and the operator was awaiting more materials to finish repairs. Rusting was observed on the slide staircase.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?