Travelodge Edmonton West - Whirlpool
18320 Stony Plain Road NW Edmonton AB T5S 1A7 · Aquatic Facility
14 inspections
- Risk Management Inspection
0 infractions
- Monitoring Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The flow rate was observed to be at 52 GPM.Pool Volume: 1200 GallonsTurnover period: 23.1 minutesA flow rate of at least 60 GPM is required to meet the required turnover period of 20 minutes.(Note: Do not exceed 61.25 GPM in order to operate at or below the maximum allowed filtration rate of 12.5 GPM/sq ft)
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Risk Management Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Flow meter was not operational. Turnover period and filtration period could not be calculated
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Monitoring Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Flow meter was not operational. Turnover period and filtration period could not be calculated
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Risk Management Inspection
0 infractions
- Risk Management Inspection
3 infractions
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Total Alkalinity: 28ppm
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Alkalinity: 42ppmMaintain Alkalinity between 60-180ppm.Combined chlorine 4.26 ppm.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Accumulation of sand was noted in one of the corners of the basin. Vacuum the basin and maintain in a clean and sanitary condition.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
4 infractions
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Alkalinity: 42ppmMaintain Alkalinity between 60-180ppm.Combined chlorine 4.26 ppm.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Total Alkalinity: 28ppm
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Accumulation of sand was noted in one of the corners of the basin. Vacuum the basin and maintain in a clean and sanitary condition.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Anti-entrapment plan has not been updated.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
5 infractions
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- The retesting done after taking sample from the poolpH: 7.84 Water sample taken from the controller and tested.pH: OROperator tested water sample from the controllerpH: 7.98; Pool verbally closed during inspection until water chemistry is balanced.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Total Alkalinity: 28ppm
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- 1-Chemical automatic controller alarm was on.There was no water flow in the probs.2-Controller pH (7.1) is not consistent with manual pH (8.11, 7.84, 7.98 ). Service the controller to ensure controller and manual readings are consistent.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Accumulation of sand was noted in one of the corners of the basin. Vacuum the basin and maintain in a clean and sanitary condition.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Anti-entrapment plan has not been updated.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Monitoring Inspection
6 infractions
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- The retesting done after taking sample from the poolpH: 7.84 Water sample taken from the controller and tested.pH: OROperator tested water sample from the controllerpH: 7.98; Pool verbally closed during inspection until water chemistry is balanced.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Total Alkalinity: 28ppm
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- 1-Chemical automatic controller alarm was on.There was no water flow in the probs.2-Controller pH (7.1) is not consistent with manual pH (8.11, 7.84, 7.98 ). Service the controller to ensure controller and manual readings are consistent.
- 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
- Main drain convers had been expired in 13 Feb 2023. Provide documentation if main drain covers had already been replaced or replace the main drain covers. Pool must remain closed until main drain covers are replaced.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Accumulation of sand was noted in one of the corners of the basin. Vacuum the basin and maintain in a clean and sanitary condition.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Anti-entrapment plan has not been updated.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
1 infraction
- 16. Are proper testing, monitoring, and other records being properly maintained?
- Daily visual checks of main drain covers were not being done and recorded. Discussed with operator onsite and advise to do a visual check daily and keep record with other chemical parameters.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- Risk Management Inspection
2 infractions
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Skimmer cover was broken. Replace the cover.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- Daily visual checks of main drain covers were not being done and recorded. Discussed with operator onsite and advise to do a visual check daily and keep record with other chemical parameters.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Monitoring Inspection
3 infractions
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The combined chlorine was higher than the free chlorine. Take corrective action to increase the free chlorine and ensure free chlorine is higher than the combined chlorine.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Turn over period calculated as 30 minutes.FR: 39
- 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
- There was no clock available in whirlpool area for bathers to monitor their bathing time.A wall clock was installed during inspeciton.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
2 infractions
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The combined chlorine was higher than the free chlorine. Take corrective action to increase the free chlorine and ensure free chlorine is higher than the combined chlorine.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The float on the flow meter appeared to be stuck and the flow meter was not functional. Repair. Turnover period and filtration rate could not be calculated.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
3 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- The microbiological water sample submitted on [Date] was unsatisfactory: Pseudomonas aeruginosa isolated, Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The combined chlorine was higher than the free chlorine. Take corrective action to increase the free chlorine and ensure free chlorine is higher than the combined chlorine.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The float on the flow meter appeared to be stuck and the flow meter was not functional. Repair. Turnover period and filtration rate could not be calculated.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?