18012 95 Avenue NW - Swimming Pool

18012 95 Avenue NW Edmonton AB T5T 5Z2 · Aquatic Facility

4 inspections

  1. Monitoring Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow rate was observed to be at 67 GPM.Pool Volume: 10300 GallonsFilter area: 3.1 sq ftThe filtration rate was calculated to be at 21.6 gpm/sq ft, which exceeds the maximum of 15 gpm/sq ft.Corrective Action:- The pool operator decreased the flow rate to 45 GPM during the inspection.- The filtration rate was calculated to be at 14.5 gpm/sq ft, which is below the maximum of 15 gpm/sq ft.
  2. Risk Management Inspection

    0 infractions

  3. Monitoring Inspection

    2 infractions

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Total alkalinity was 26ppm. Chemical added manually to increase thel alkalinity by the pool operator during the inspection.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Filtration rate was 26.98gpm/ft2. Lower the flow rate to 60gpm to ensure the filtration rate does not exceed the maximum of 20gpm/ft2 as per manufacturer's specifications.
  4. Monitoring Inspection

    0 infractions