Best Western Premier Calgary Plaza Hotel & Conference Centre - Whirlpool
1316 33 Street NE Calgary AB T2A 6B6 · Aquatic Facility
9 inspections
- Demand Inspection
2 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- 1. Water sample collected on January 15, 2026 was present for total coliforms.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- 1. The combined chlorine measured 2.37ppm. The Operator stated fresh water is added daily.COMPLETE THE FOLLOWING:1. Ensure the combined chlorine is maintained as low as possible (recommended is less than 1.00ppm).
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
2 infractions
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- 1. The combined chlorine measured 2.37ppm. The Operator stated fresh water is added daily.COMPLETE THE FOLLOWING:1. Ensure the combined chlorine is maintained as low as possible (recommended is less than 1.00ppm).
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- 1. The anti-entrapment plan for the recirculation pump appeared inaccurate and incomplete. COMPLETE THE FOLLOWING:1. Review plumbing schematics and ensure they are correct.2. Please update and complete the anti-entrapment forms for the recirculation pump and jet pump.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Monitoring Inspection
6 infractions
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- 1. When the whirlpool jets were turned on, there was a significant amount of foaming and noticeable chlorine odour indicating a high amount of combined chlorine in the basin.COMPLETE THE FOLLOWING:1. Reduce the combined chlorine to the lowest level possible. It is recommended to add more fresh water to the basin more often.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- **CORRECTED**1. Mechanical room: The valve for the main drain was fully opened. The valve was adjusted to 30% during the inspection.COMPLETE THE FOLLOWING:1. Valves from main drains should be opened no more than 30% to increase flow of water through the skimmers as the top portion of pool water contains the highest amount of contaminants.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- 1. The flow metre read 51 GPM. The calculated minimum flow rate for the pool is 60 GPM. - Discussed with the Operator and they will be switching the jet pump (2-horsepower) with the recirculation pump (1.5-horsepower) to obtain the previous flow rate. The facility used to have the 2-horsepower pump for the recirculation system.COMPLETE THE FOLLOWING:1. Ensure the flow rate is maintained between 60 - 61 GPM for adequate circulation and disinfection.
- 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
- 1. Gaps observed between the wall drain covers and basin wall. - The manufacturer instructions state that "after installation of fittings, if a gap exists between the pool finish and base of cover it must be filled in to avoid finger or other entrapment"COMPLETE THE FOLLOWING:1. Fill gap between the pool finish and cover to prevent entrapment hazards.
- 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
- 1. There were 2 screws missing from one of the inlet covers on the basin floor. COMPLETE THE FOLLOWING:1. Replace the missing screws on inlet cover.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- 1. There was no anti-entrapment plan for the jet pump.2. The anti-entrapment plan for the recirculation pump appeared inaccurate and incomplete. COMPLETE THE FOLLOWING:1. Review plumbing schematics and ensure they are correct.2. Please update and complete the anti-entrapment forms for the recirculation pump and jet pump.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
0 infractions
- Risk Management Inspection
1 infraction
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Whirlpool missing some tiles.-Please fix to ensure good repair.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Monitoring Inspection
3 infractions
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Total Alkalinity was over 180 milligrams per litre.-Please reduce and maintain total alkalinity between 60 - 180 milligrams per litre.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Whirlpool missing some tiles.-Please fix to ensure good repair.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- The whirlpool's water alkalinity was not tested and documented weekly as required.-Please maintain regular water alkalinity testing and documentation as required.*Outstanding violation since 2023.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
4 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Dec. 28, 2023 sample had pseudomonas isolated. LVM for Dan (sampler) to treat and resample. Lab accepts pool sample again on Tuesday January 2nd, 2024.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Sample collected on 2024-01-02 was not processed because there was no identification number on the bottle submitted.-Please resample and ensure proper sampling protocol is followed.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The whirlpool turnover rate was not adequate, calculated at 18 minutes. For a whirlpool with water volume less than 4 cubic meters, the turnover rate should be within 15 minutes.-Please adjust and maintain the whirlpool circulation rate at 60 GPM for adequate turnover period/rate.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- The whirlpool's water alkalinity was not tested and documented weekly as required.-Please maintain regular water alkalinity testing and documentation as required.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
3 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Dec. 28, 2023 sample had pseudomonas isolated. LVM for Dan (sampler) to treat and resample. Lab accepts pool sample again on Tuesday January 2nd, 2024.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The whirlpool turnover rate was not adequate, calculated at 18 minutes. For a whirlpool with water volume less than 4 cubic meters, the turnover rate should be within 15 minutes.-Please adjust and maintain the whirlpool circulation rate at 60 GPM for adequate turnover period/rate.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- The whirlpool's water alkalinity was not tested and documented weekly as required.-Please maintain regular water alkalinity testing and documentation as required.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Monitoring Inspection
2 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The whirlpool turnover rate was not adequate, calculated at 18 minutes. For a whirlpool with water volume less than 4 cubic meters, the turnover rate should be within 15 minutes.-Please adjust and maintain the whirlpool circulation rate at 60 GPM for adequate turnover period/rate.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- The whirlpool's water alkalinity was not tested and documented weekly as required.-Please maintain regular water alkalinity testing and documentation as required.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?