Skip to content
Loading map…

Blackstone Mountain Lodge - Whirlpool B

170 Kananaskis Way Canmore AB T1W 0A8 · Aquatic Facility

6 inspections

  1. Risk Management Inspection

    0 infractions

  2. Monitoring Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Flow rate according to flow meter was 92gpm, which exceeds the maximum flow rate for the filter of 88gpm. Corrected during inspection; flow rate adjusted to 88gpm.
  3. Demand Inspection

    4 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample taken on December 2, 2024 had a plate count of 140cfu/ml. Treat whirlpool to remove contamination. Resample.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • No flow rate was able to be determined as the flow meter was not functional. - Repair or replace the flow meter to ensure adequate filtration and turnover rates are being met.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The left skimmer was missing its weir. - Install a floating weir to ensure proper flow through the skimmers.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Jet drain covers were replaced in May 2023. Anti-entrapment plans have not been updated. - Please update anti-entrapment plans to include the next expiry dates.
  4. Demand Inspection

    4 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample from Aug 6th, 2024, was not processed by the lab due to missing date/time information on the form. - Operators were informed to submit a re-sample.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • No flow rate was able to be determined as the flow meter was not functional. - Repair or replace the flow meter to ensure adequate filtration and turnover rates are being met.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The left skimmer was missing its weir. - Install a floating weir to ensure proper flow through the skimmers.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Jet drain covers were replaced in May 2023. Anti-entrapment plans have not been updated. - Please update anti-entrapment plans to include the next expiry dates.
  5. Demand Inspection

    4 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample from October 3rd came back with an HPC count of 130CFU/ml. Operators are to treat and re-sample.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • No flow rate was able to be determined as the flow meter was not functional. - Repair or replace the flow meter to ensure adequate filtration and turnover rates are being met.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The left skimmer was missing its weir. - Install a floating weir to ensure proper flow through the skimmers.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Jet drain covers were replaced in May 2023. Anti-entrapment plans have not been updated. - Please update anti-entrapment plans to include the next expiry dates.
  6. Monitoring Inspection

    3 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • No flow rate was able to be determined as the flow meter was not functional. - Repair or replace the flow meter to ensure adequate filtration and turnover rates are being met.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The left skimmer was missing its weir. - Install a floating weir to ensure proper flow through the skimmers.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?