Lodges At Canmore Phase I (Wolf Lodge) - Swimming Pool
107 Montane Road Canmore AB T1W 3J2 · Aquatic Facility
8 inspections
- Risk Management Inspection
2 infractions
- 16. Are proper testing, monitoring, and other records being properly maintained?
- Cyanuric acid level is currently not being measured as ran out of the chemicals needed for testing. Obtain chemicals needed to test cyanuric acid level and ensure it is tested at least once a week, particularly after cyanuric acid is added.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Anti-entrapment plan needs to be updated as new main drain covers were installed since the plan was written as well a new circulation pump was installed and some of the required questions on the plan were left blank.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- Demand Inspection
4 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample taken on June 5/26 was not tested as it was dropped off after the lab had closed for the weekend. New sample to be submitted as soon as possible this week.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- No water sample was submitted the week of May 25/26. A water sample is required to be submitted each week.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- Cyanuric acid level is currently not being measured as ran out of the chemicals needed for testing. Obtain chemicals needed to test cyanuric acid level and ensure it is tested at least once a week, particularly after cyanuric acid is added.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Anti-entrapment plan needs to be updated as new main drain covers were installed since the plan was written as well a new circulation pump was installed and some of the required questions on the plan were left blank.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample from Thursday September 25th, 2025, had an HPC of 140 CFU/ml. - Operators were informed to treat and re-sample.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- Cyanuric acid level is currently not being measured as ran out of the chemicals needed for testing. Obtain chemicals needed to test cyanuric acid level and ensure it is tested at least once a week, particularly after cyanuric acid is added.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Anti-entrapment plan needs to be updated as new main drain covers were installed since the plan was written as well a new circulation pump was installed and some of the required questions on the plan were left blank.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- May 15, 2025 water sample was not tested as there was not time of collection on the requisition form. Resample to be submitted.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- Cyanuric acid level is currently not being measured as ran out of the chemicals needed for testing. Obtain chemicals needed to test cyanuric acid level and ensure it is tested at least once a week, particularly after cyanuric acid is added.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Anti-entrapment plan needs to be updated as new main drain covers were installed since the plan was written as well a new circulation pump was installed and some of the required questions on the plan were left blank.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- December 27, 2024 water sample was not tested. Resample to be submitted.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- Cyanuric acid level is currently not being measured as ran out of the chemicals needed for testing. Obtain chemicals needed to test cyanuric acid level and ensure it is tested at least once a week, particularly after cyanuric acid is added.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Anti-entrapment plan needs to be updated as new main drain covers were installed since the plan was written as well a new circulation pump was installed and some of the required questions on the plan were left blank.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
2 infractions
- 16. Are proper testing, monitoring, and other records being properly maintained?
- Cyanuric acid level is currently not being measured as ran out of the chemicals needed for testing. Obtain chemicals needed to test cyanuric acid level and ensure it is tested at least once a week, particularly after cyanuric acid is added.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Anti-entrapment plan needs to be updated as new main drain covers were installed since the plan was written as well a new circulation pump was installed and some of the required questions on the plan were left blank.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- Monitoring Inspection
4 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- No water sample was submitted the week of December 2-6, 2024.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Cyanuric acid level was measured at 56ppm. Backwash was done to remove some water from the pool and fresh water added. When cyanuric acid level re-measured was at 49ppm.Cyanuric acid level is be kept at 50ppm or less.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- Cyanuric acid level is currently not being measured as ran out of the chemicals needed for testing. Obtain chemicals needed to test cyanuric acid level and ensure it is tested at least once a week, particularly after cyanuric acid is added.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Anti-entrapment plan needs to be updated as new main drain covers were installed since the plan was written as well a new circulation pump was installed and some of the required questions on the plan were left blank.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Monitoring Inspection
4 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Flow rate was too high for the filters (was about 567-625gpm). Flow rate to be between 553 to 558gpm. Adjusted to 558gpm during inspection.
- 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
- There is a small water leak from the pipe above the acid/chlorine feeds. Please repair the leak.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- One of the floating weirs was missing. Please replace.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Anti-entrapment plan needs to be updated as new main drain covers were installed since the plan was written.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?