Canalta St. Paul - Whirlpool

5008 43 Street St. Paul AB T0A 3A2 · Aquatic Facility

13 inspections

  1. Risk Management Inspection

    0 infractions

  2. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample ID: 35EN-330E00723 had HPC of 430 cfu/100ml which could indicate a failure of the disinfection system. Please ensure another sample is submitted next week.9 April 2026 - HPC at 960 CFU/mL Operator indicated that the whirlpool is currently closed and would be undergoing cleaning and disinfection. Will follow up with a resample after water has been replaced.
  3. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample ID: 35EN-330E00723 had HPC of 430 cfu/100ml which could indicate a failure of the disinfection system. Please ensure another sample is submitted next week.
  4. Monitoring Inspection

    0 infractions

  5. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Sample 25EN-218E00174 has an HPC of 170 CFU/mL which could indicate possible contamination of the water. I spoke with the pool operator Dishant. He stated the water was cloudy. After collecting the sample the whirlpool was drained, cleaned and then refilled. The pool chemical parameters as of 8-Aug-2025 are satisfactory and a sample will be submitted as usual next week.
  6. Monitoring Inspection

    1 infraction

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Total Alkalinity is higher than 180 ppm. Higher Total Alkalinity increase pool PH and make pool water cloudy.Please adjust Total Alkalinity between the range 60 ppm to 180 ppm.*repeated violation 5/12/25
  7. Monitoring Inspection

    4 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • HPC > 57,000Operator indicated that the pool is currently being drained, scrubbed, disinfected and refilled as part of routine maintenance. Another water sample will be submitted ASAP.
    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • PH is at 6.6. Low PH causes eye irritation, dry skin and irritation to swimmers. It also corrodes metal surfaces and pool accessories.Please adjust PH between the range 6.8 to 7.6
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Total Alkalinity is higher than 180 ppm. Higher Total Alkalinity increase pool PH and make pool water cloudy.Please adjust Total Alkalinity between the range 60 ppm to 180 ppm.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Calculated turn over period is 21.8 min. High turnover period causes pollution build-up in pool.Please fix circulation system and ensure the turnover rate around 15 min.
  8. Monitoring Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • HPC > 57,000Operator indicated that the pool is currently being drained, scrubbed, disinfected and refilled as part of routine maintenance. Another water sample will be submitted ASAP.
    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • Chlorine at 0.73mg/LChlorine should be above 2mg/L for the hot tub.
  9. Monitoring Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • HPC > 57,000Operator indicated that the pool is currently being drained, scrubbed, disinfected and refilled as part of routine maintenance. Another water sample will be submitted ASAP.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Alkalinity was observed to be greater than 180mg/L. Ensure that this is lowered to ensure bather comfort and prevent skin irritation. It should be between 60-180mg/L
  10. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • HPC > 57,000Operator indicated that the pool is currently being drained, scrubbed, disinfected and refilled as part of routine maintenance. Another water sample will be submitted ASAP.
  11. Monitoring Inspection

    0 infractions

  12. Risk Management Inspection

    0 infractions

  13. Risk Management Inspection

    1 infraction

    • 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
      • Clock was unavailable and not visible from the whirlpool.