Co-operative Aquatic Centre - Leisure Pool/Slide
5116 50 Avenue Rocky Mountain House AB T4T 1B2 · Aquatic Facility
Inspection summary
Co-operative Aquatic Centre - Leisure Pool/Slide has been inspected 12 times by Alberta Health Services (Environmental Public Health) since December 11, 2023. The most recent inspection, on February 23, 2026, recorded 1 infraction.
None of the 12 inspections on record were free of infractions. In the past 12 months there was 1 inspection with 1 infraction recorded. The higher-risk findings here relate to: Pool and spa water quality.
Recent inspections have recorded fewer infractions than earlier ones, so the record is improving.
What these findings mean
Health authorities word their findings differently, so we group them by what they mean for the people using the facility. Higher-risk findings are the ones that could directly cause illness or injury, such as water that is not properly treated.
Pool and spa water qualityHigher risk
For pools, spas and splash pads, inspectors test disinfectant levels, pH and water clarity, and check safety equipment. Water that is not properly treated can spread skin, ear and stomach infections.
Recorded 17 times across 12 separate inspections, most recently on February 23, 2026. For example:
Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
Food safety training and certificationLower risk
Many jurisdictions require trained pool operators and certified lifeguards. These findings mean required training, certification or staffing records were missing at the time of inspection.
Recorded 6 times across 6 separate inspections, most recently on August 9, 2024. For example:
Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
About this data
These results come from Alberta Health Services (Environmental Public Health), which inspects food premises and other public facilities in this area. We republish the authority's public disclosure data and refresh it regularly; the official record is the final word.
12 inspections
- Risk Management Inspection
1 infraction
- 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
- Repeat ViolationPlease send the appropriate pictures, documents, and dates of install and expiry to complete the anti-entrapment requirements.At the time of this inspection, main drain covers have been replaced, certification has been dated and signed. However, PHI is waiting for additional information to ensure anti-entrapment plans meet current regulations.  Old ViolationAt the time of the inspection and anti-entrapment plan review, the main drain covers were that are installed do not meet the maximum flow requirements as per the manufacturer's specifications.At the time of the inspection and anti-entrapment plan review, the main drain covers were that are installed do not meet the maximum flow requirements as per the manufacturer's specifications and therefor do not meet the anti-entrapment requirements of the Pool Regulation (AR 204/2014) and the Pool Standard, July 2014 (Amended January 2018).
- 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
- Monitoring Inspection
1 infraction
- 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
- Repeat ViolationPlease send the appropriate pictures, documents, and dates of install and expiry to complete the anti-entrapment requirements.At the time of this inspection, main drain covers have been replaced, certification has been dated and signed. However, PHI is waiting for additional information to ensure anti-entrapment plans meet current regulations.  Old ViolationAt the time of the inspection and anti-entrapment plan review, the main drain covers were that are installed do not meet the maximum flow requirements as per the manufacturer's specifications.At the time of the inspection and anti-entrapment plan review, the main drain covers were that are installed do not meet the maximum flow requirements as per the manufacturer's specifications and therefor do not meet the anti-entrapment requirements of the Pool Regulation (AR 204/2014) and the Pool Standard, July 2014 (Amended January 2018).
- 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- HPC counts showing 110, operator contacted to resubmit water sample.
- 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
- Repeat ViolationPlease send the appropriate pictures, documents, and dates of install and expiry to complete the anti-entrapment requirements.At the time of this inspection, main drain covers have been replaced, certification has been dated and signed. However, PHI is waiting for additional information to ensure anti-entrapment plans meet current regulations.  Old ViolationAt the time of the inspection and anti-entrapment plan review, the main drain covers were that are installed do not meet the maximum flow requirements as per the manufacturer's specifications.At the time of the inspection and anti-entrapment plan review, the main drain covers were that are installed do not meet the maximum flow requirements as per the manufacturer's specifications and therefor do not meet the anti-entrapment requirements of the Pool Regulation (AR 204/2014) and the Pool Standard, July 2014 (Amended January 2018).
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Monitoring Inspection
1 infraction
- 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
- Repeat ViolationPlease send the appropriate pictures, documents, and dates of install and expiry to complete the anti-entrapment requirements.At the time of this inspection, main drain covers have been replaced, certification has been dated and signed. However, PHI is waiting for additional information to ensure anti-entrapment plans meet current regulations.  Old ViolationAt the time of the inspection and anti-entrapment plan review, the main drain covers were that are installed do not meet the maximum flow requirements as per the manufacturer's specifications.At the time of the inspection and anti-entrapment plan review, the main drain covers were that are installed do not meet the maximum flow requirements as per the manufacturer's specifications and therefor do not meet the anti-entrapment requirements of the Pool Regulation (AR 204/2014) and the Pool Standard, July 2014 (Amended January 2018).
- 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
- Risk Management Inspection
2 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Total Coliforms by enzyme substrate present in biological water sample.
- 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
- At the time of this inspection, main drain covers have been replaced, certification has been dated and signed. However, PHI is waiting for additional information to ensure anti-entrapment plans meet current regulations.  Old ViolationAt the time of the inspection and anti-entrapment plan review, the main drain covers were that are installed do not meet the maximum flow requirements as per the manufacturer's specifications.At the time of the inspection and anti-entrapment plan review, the main drain covers were that are installed do not meet the maximum flow requirements as per the manufacturer's specifications and therefor do not meet the anti-entrapment requirements of the Pool Regulation (AR 204/2014) and the Pool Standard, July 2014 (Amended January 2018).
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Monitoring Inspection
1 infraction
- 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
- At the time of this inspection, main drain covers have been replaced, certification has been dated and signed. However, PHI is waiting for additional information to ensure anti-entrapment plans meet current regulations.  Old ViolationAt the time of the inspection and anti-entrapment plan review, the main drain covers were that are installed do not meet the maximum flow requirements as per the manufacturer's specifications.At the time of the inspection and anti-entrapment plan review, the main drain covers were that are installed do not meet the maximum flow requirements as per the manufacturer's specifications and therefor do not meet the anti-entrapment requirements of the Pool Regulation (AR 204/2014) and the Pool Standard, July 2014 (Amended January 2018).
- 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
- Demand Inspection
3 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- TC present in preliminary sample collected Aug. 7.
- 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
- At the time of the inspection and anti-entrapment plan review, the main drain covers were that are installed do not meet the maximum flow requirements as per the manufacturer's specifications.At the time of the inspection and anti-entrapment plan review, the main drain covers were that are installed do not meet the maximum flow requirements as per the manufacturer's specifications and therefor do not meet the anti-entrapment requirements of the Pool Regulation (AR 204/2014) and the Pool Standard, July 2014 (Amended January 2018).At the time of the inspection the clarity of the pool water was acceptable. A certified pool operator has been identified and was preset on site and the pool had just undergone a complete maintenance and repair.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Pool operator has mentioned pools will be drained sometime in September/October when facility renovations will take place. Covers retrofitted to proper anti entrapment flow rates will be installed. Ongoing ViolationAt the time of the inspection an anti-entrapment plan was developed and implemented at the facility; However, this plan noted that the specified maximum flow rates for the main drain outlet covers were not sufficient to meet or exceed the maximum flow rate of the system. ***Please ensure that the manufacturer's specified flow rate on the main drain outlet covers is sufficient to address the maximum flow rate of the system or secondary anti-entrapment is in place.***
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
2 infractions
- 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
- At the time of the inspection and anti-entrapment plan review, the main drain covers were that are installed do not meet the maximum flow requirements as per the manufacturer's specifications.At the time of the inspection and anti-entrapment plan review, the main drain covers were that are installed do not meet the maximum flow requirements as per the manufacturer's specifications and therefor do not meet the anti-entrapment requirements of the Pool Regulation (AR 204/2014) and the Pool Standard, July 2014 (Amended January 2018).At the time of the inspection the clarity of the pool water was acceptable. A certified pool operator has been identified and was preset on site and the pool had just undergone a complete maintenance and repair.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Pool operator has mentioned pools will be drained sometime in September/October when facility renovations will take place. Covers retrofitted to proper anti entrapment flow rates will be installed. Ongoing ViolationAt the time of the inspection an anti-entrapment plan was developed and implemented at the facility; However, this plan noted that the specified maximum flow rates for the main drain outlet covers were not sufficient to meet or exceed the maximum flow rate of the system. ***Please ensure that the manufacturer's specified flow rate on the main drain outlet covers is sufficient to address the maximum flow rate of the system or secondary anti-entrapment is in place.***
- 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
- Risk Management Inspection
3 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Lab report with negative water sample taken July 10 showing positive TC by enzyme substrate present.
- 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
- At the time of the inspection and anti-entrapment plan review, the main drain covers were that are installed do not meet the maximum flow requirements as per the manufacturer's specifications.At the time of the inspection and anti-entrapment plan review, the main drain covers were that are installed do not meet the maximum flow requirements as per the manufacturer's specifications and therefor do not meet the anti-entrapment requirements of the Pool Regulation (AR 204/2014) and the Pool Standard, July 2014 (Amended January 2018).At the time of the inspection the clarity of the pool water was acceptable. A certified pool operator has been identified and was preset on site and the pool had just undergone a complete maintenance and repair.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Pool operator has mentioned pools will be drained sometime in September/October when facility renovations will take place. Covers retrofitted to proper anti entrapment flow rates will be installed. Ongoing ViolationAt the time of the inspection an anti-entrapment plan was developed and implemented at the facility; However, this plan noted that the specified maximum flow rates for the main drain outlet covers were not sufficient to meet or exceed the maximum flow rate of the system. ***Please ensure that the manufacturer's specified flow rate on the main drain outlet covers is sufficient to address the maximum flow rate of the system or secondary anti-entrapment is in place.***
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Monitoring Inspection
2 infractions
- 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
- At the time of the inspection and anti-entrapment plan review, the main drain covers were that are installed do not meet the maximum flow requirements as per the manufacturer's specifications.At the time of the inspection and anti-entrapment plan review, the main drain covers were that are installed do not meet the maximum flow requirements as per the manufacturer's specifications and therefor do not meet the anti-entrapment requirements of the Pool Regulation (AR 204/2014) and the Pool Standard, July 2014 (Amended January 2018).At the time of the inspection the clarity of the pool water was acceptable. A certified pool operator has been identified and was preset on site and the pool had just undergone a complete maintenance and repair.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Pool operator has mentioned pools will be drained sometime in September/October when facility renovations will take place. Covers retrofitted to proper anti entrapment flow rates will be installed. Ongoing ViolationAt the time of the inspection an anti-entrapment plan was developed and implemented at the facility; However, this plan noted that the specified maximum flow rates for the main drain outlet covers were not sufficient to meet or exceed the maximum flow rate of the system. ***Please ensure that the manufacturer's specified flow rate on the main drain outlet covers is sufficient to address the maximum flow rate of the system or secondary anti-entrapment is in place.***
- 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
- Risk Management Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Heterophic plate count of 220 cfu/ml onMay 15 2024 water sample taken by Rachel B
- 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
- At the time of the inspection and anti-entrapment plan review, the main drain covers were that are installed do not meet the maximum flow requirements as per the manufacturer's specifications.At the time of the inspection and anti-entrapment plan review, the main drain covers were that are installed do not meet the maximum flow requirements as per the manufacturer's specifications and therefor do not meet the anti-entrapment requirements of the Pool Regulation (AR 204/2014) and the Pool Standard, July 2014 (Amended January 2018).At the time of the inspection the clarity of the pool water was acceptable. A certified pool operator has been identified and was preset on site and the pool had just undergone a complete maintenance and repair.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- At the time of the inspection an anti-entrapment plan was developed and implemented at the facility; However, this plan noted that the specified maximum flow rates for the main drain outlet covers were not sufficient to meet or exceed the maximum flow rate of the system. ***Please ensure that the manufacturer's specified flow rate on the main drain outlet covers is sufficient to address the maximum flow rate of the system or secondary anti-entrapment is in place.***
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Monitoring Inspection
2 infractions
- 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
- At the time of the inspection and anti-entrapment plan review, the main drain covers were that are installed do not meet the maximum flow requirements as per the manufacturer's specifications.At the time of the inspection and anti-entrapment plan review, the main drain covers were that are installed do not meet the maximum flow requirements as per the manufacturer's specifications and therefor do not meet the anti-entrapment requirements of the Pool Regulation (AR 204/2014) and the Pool Standard, July 2014 (Amended January 2018).At the time of the inspection the clarity of the pool water was acceptable. A certified pool operator has been identified and was preset on site and the pool had just undergone a complete maintenance and repair.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- At the time of the inspection an anti-entrapment plan was developed and implemented at the facility; However, this plan noted that the specified maximum flow rates for the main drain outlet covers were not sufficient to meet or exceed the maximum flow rate of the system. ***Please ensure that the manufacturer's specified flow rate on the main drain outlet covers is sufficient to address the maximum flow rate of the system or secondary anti-entrapment is in place.***
- 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
Nearby inspected facilities
- Co-operative Aquatic Centre - Common Area
5116 50 Avenue Rocky Mountain House AB T4T 1B2
5 inspections
- Co-operative Aquatic Centre - Whirlpool
5116 50 Avenue Rocky Mountain House AB T4T 1B2
8 inspections
- Co-operative Aquatic Centre - Swimming Pool
5116 50 Avenue Rocky Mountain House AB T4T 1B2
10 inspections
- Rocky Mountain House Pioneer Center 15636
4939 52 Street Rocky Mountain House AB T4T 1T1
1 inspection
- Travelin Gypsy's
1 - 5016 50 Avenue Rocky Mountain House AB T4T 1A2
1 inspection
- Lazy A Studios Sugar And Mane
C - 5016 50 Avenue Rocky Mountain House AB T4T 1A4
2 inspections
- Lavish Lash Studio
4 - 5016 50 Avenue Rocky Mountain House AB T4T 1B2
1 inspection
- Nice Nails Ltd.
5016 50 Avenue Rocky Mountain House AB T4T 1W9
8 inspections