Comfort Inn & Suites - Swimming Pool

4611 Macleod Trail SW Calgary AB T2G 0A6 · Aquatic Facility

21 inspections

  1. Demand Inspection

    3 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample submitted had an HPC value of 5,360 CFU/mL. Please submit a re-sample.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The automated monitoring system’s chemical readings were inconsistent with manual testing. Automated reading for pH was 7.9 and then 8.0 and manual testing was 7.5.- System did not appear to be injecting acid.- Clean the probes and calibrate the system so it is providing consistent reading with manual testing.
    • 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
      • The flow meter for the slide was not functioning.- Repair or replace the flow meter so it shows flow rate of the slide system.
  2. Demand Inspection

    3 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample collected on April 10, 2026 had HPC of 3060.Advised to re-sample.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The automated monitoring system’s chemical readings were inconsistent with manual testing. Automated reading for pH was 7.9 and then 8.0 and manual testing was 7.5.- System did not appear to be injecting acid.- Clean the probes and calibrate the system so it is providing consistent reading with manual testing.
    • 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
      • The flow meter for the slide was not functioning.- Repair or replace the flow meter so it shows flow rate of the slide system.
  3. Risk Management Inspection

    2 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The automated monitoring system’s chemical readings were inconsistent with manual testing. Automated reading for pH was 7.9 and then 8.0 and manual testing was 7.5.- System did not appear to be injecting acid.- Clean the probes and calibrate the system so it is providing consistent reading with manual testing.
    • 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
      • The flow meter for the slide was not functioning.- Repair or replace the flow meter so it shows flow rate of the slide system.
  4. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample collected on March 27, 2026 had HPC of 4120.Advised to re-sample.
    • 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
      • The flow meter for the slide was not functioning.- Repair or replace the flow meter so it shows flow rate of the slide system.
  5. Demand Inspection

    3 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample collected on March 27, 2026 had HPC of 4120.Advised to re-sample.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The automated monitoring system’s chemical readings were inconsistent with manual testing. Automated reading for pH was 7.9 and then 8.0 and manual testing was 7.5.- System did not appear to be injecting acid.- Clean the probes and calibrate the system so it is providing consistent reading with manual testing.
    • 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
      • The flow meter for the slide was not functioning.- Repair or replace the flow meter so it shows flow rate of the slide system.
  6. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample collected on March 13, 2026 had HPC 470 cfu/ml. Advised to treat the pool and submit a re-sample. Water sample collected on March 6, 2026 had HPC 2600 cfu/ml. Advised to resample.
    • 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
      • The flow meter for the slide was not functioning.- Repair or replace the flow meter so it shows flow rate of the slide system.
  7. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample collected on March 6, 2026 had HPC 2600 cfu/ml. Advised to resample.
    • 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
      • The flow meter for the slide was not functioning.- Repair or replace the flow meter so it shows flow rate of the slide system.
  8. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample collected on December 12, 2025 was not processed as it was received at the lab on December 13, 2025 (a Saturday).
    • 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
      • The flow meter for the slide was not functioning.- Repair or replace the flow meter so it shows flow rate of the slide system.
  9. Demand Inspection

    3 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The biological water sample collected on Nov 07, had a HPC count of 15,000 CFU/ml.
    • 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
      • The flow meter for the slide was not functioning.- Repair or replace the flow meter so it shows flow rate of the slide system.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • No anti-entrapment plan was available.- Provide the anti-entrapment plan for review.
  10. Monitoring Inspection

    2 infractions

    • 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
      • The flow meter for the slide was not functioning.- Repair or replace the flow meter so it shows flow rate of the slide system.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • No anti-entrapment plan was available.- Provide the anti-entrapment plan for review.
  11. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The biological water sample collected on Jan 03, had a HPC count of 520 CFU/ml.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • REPEAT VIOLATION: - Result of the manual test (pH 7.1) is not consistent with the automated reading (pH 7.2). COMPLETE THE FOLLOWING:- Repair/recalibrate/replace. Ensure the results are consistent.
  12. Risk Management Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • REPEAT VIOLATION: - Result of the manual test (pH 7.1) is not consistent with the automated reading (pH 7.2). COMPLETE THE FOLLOWING:- Repair/recalibrate/replace. Ensure the results are consistent.
  13. Demand Inspection

    3 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • The sample collected on April 30, 2024 had total coliforms present.Close the pool, complete proper cleaning and treatment. Rebalance the chemistry and send in a re-sample. Sample must come back satisfactory before pool can re-open.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Updated Apr 29, 2024Sample collected Apr 25, 2024 had HPC >57000 CFU/mL.-Treat and re-sample-----------The sample collected on April 18, 2024 had an HPC count of >57000 CFU/ml.Treat and resample.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • REPEAT VIOLATION: - Result of the manual test (pH 7.1) is not consistent with the automated reading (pH 7.2). COMPLETE THE FOLLOWING:- Repair/recalibrate/replace. Ensure the results are consistent.
  14. Demand Inspection

    3 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • The sample collected on April 30, 2024 had total coliforms present.Close the pool, complete proper cleaning and treatment. Rebalance the chemistry and send in a re-sample. Sample must come back satisfactory before pool can re-open.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Updated Apr 29, 2024Sample collected Apr 25, 2024 had HPC >57000 CFU/mL.-Treat and re-sample-----------The sample collected on April 18, 2024 had an HPC count of >57000 CFU/ml.Treat and resample.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • REPEAT VIOLATION: - Result of the manual test (pH 7.1) is not consistent with the automated reading (pH 7.2). COMPLETE THE FOLLOWING:- Repair/recalibrate/replace. Ensure the results are consistent.
  15. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Updated Apr 29, 2024Sample collected Apr 25, 2024 had HPC >57000 CFU/mL.-Treat and re-sample-----------The sample collected on April 18, 2024 had an HPC count of >57000 CFU/ml.Treat and resample.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • REPEAT VIOLATION: - Result of the manual test (pH 7.1) is not consistent with the automated reading (pH 7.2). COMPLETE THE FOLLOWING:- Repair/recalibrate/replace. Ensure the results are consistent.
  16. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The sample collected on April 18, 2024 had an HPC count of >57000 CFU/ml.Treat and resample.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • REPEAT VIOLATION: - Result of the manual test (pH 7.1) is not consistent with the automated reading (pH 7.2). COMPLETE THE FOLLOWING:- Repair/recalibrate/replace. Ensure the results are consistent.
  17. Monitoring Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • REPEAT VIOLATION: - Result of the manual test (pH 7.1) is not consistent with the automated reading (pH 7.2). COMPLETE THE FOLLOWING:- Repair/recalibrate/replace. Ensure the results are consistent.
  18. Risk Management Inspection

    3 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • REPEAT VIOLATION: - Result of the manual test (pH 7.1) is not consistent with the automated reading (pH 7.3). COMPLETE THE FOLLOWING:- Repair/recalibrate/replace. Ensure the results are consistent.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • REPEAT VIOLATIONS: 1. Pool chemistry testing results are not recorded daily. Every Sunday the log is blank (as of January 2022). Other sporadic days are also blank. The pool is open for use on Sundays. 2. The inspection results for the submerged suction outlet covers are not recorded daily. Every Sunday the log is blank (as of January 2022). Other sporadic days are also blank. COMPLETE THE FOLLOWING: 1. The pool chemistry must be tested on days when the pool is open for public use. Ensure the results are recorded daily. 2. The submerged suction outlet covers must be inspected prior to the pool opening daily. Ensure the results are recorded daily.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • VIOLATION: - An anti-entrapment plan has been submitted, but clarification is still required. COMPLETE THE FOLLOWING: - Provide additional information regarding the anti-entrapment plan. Refer to the email previous sent.
  19. Demand Inspection

    4 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The water sample collected on February 1, 2024 had a HPC count of 940cfu/ml.-Resample
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • REPEAT VIOLATION: - Result of the manual test (pH 7.1) is not consistent with the automated reading (pH 7.3). COMPLETE THE FOLLOWING:- Repair/recalibrate/replace. Ensure the results are consistent.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • REPEAT VIOLATIONS: 1. Pool chemistry testing results are not recorded daily. Every Sunday the log is blank (as of January 2022). Other sporadic days are also blank. The pool is open for use on Sundays. 2. The inspection results for the submerged suction outlet covers are not recorded daily. Every Sunday the log is blank (as of January 2022). Other sporadic days are also blank. COMPLETE THE FOLLOWING: 1. The pool chemistry must be tested on days when the pool is open for public use. Ensure the results are recorded daily. 2. The submerged suction outlet covers must be inspected prior to the pool opening daily. Ensure the results are recorded daily.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • VIOLATION: - An anti-entrapment plan has been submitted, but clarification is still required. COMPLETE THE FOLLOWING: - Provide additional information regarding the anti-entrapment plan. Refer to the email previous sent.
  20. Risk Management Inspection

    3 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • REPEAT VIOLATION: - Result of the manual test (pH 7.1) is not consistent with the automated reading (pH 7.3). COMPLETE THE FOLLOWING:- Repair/recalibrate/replace. Ensure the results are consistent.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • REPEAT VIOLATIONS: 1. Pool chemistry testing results are not recorded daily. Every Sunday the log is blank (as of January 2022). Other sporadic days are also blank. The pool is open for use on Sundays. 2. The inspection results for the submerged suction outlet covers are not recorded daily. Every Sunday the log is blank (as of January 2022). Other sporadic days are also blank. COMPLETE THE FOLLOWING: 1. The pool chemistry must be tested on days when the pool is open for public use. Ensure the results are recorded daily. 2. The submerged suction outlet covers must be inspected prior to the pool opening daily. Ensure the results are recorded daily.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • VIOLATION: - An anti-entrapment plan has been submitted, but clarification is still required. COMPLETE THE FOLLOWING: - Provide additional information regarding the anti-entrapment plan. Refer to the email previous sent.
  21. Demand Inspection

    4 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Sample collected and analyzed on 2023-12-14 shows the presence of HPC >57,000 cfu/ml.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • REPEAT VIOLATION: - Result of the manual test (pH 7.1) is not consistent with the automated reading (pH 7.3). COMPLETE THE FOLLOWING:- Repair/recalibrate/replace. Ensure the results are consistent.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • REPEAT VIOLATIONS: 1. Pool chemistry testing results are not recorded daily. Every Sunday the log is blank (as of January 2022). Other sporadic days are also blank. The pool is open for use on Sundays. 2. The inspection results for the submerged suction outlet covers are not recorded daily. Every Sunday the log is blank (as of January 2022). Other sporadic days are also blank. COMPLETE THE FOLLOWING: 1. The pool chemistry must be tested on days when the pool is open for public use. Ensure the results are recorded daily. 2. The submerged suction outlet covers must be inspected prior to the pool opening daily. Ensure the results are recorded daily.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • VIOLATION: - An anti-entrapment plan has been submitted, but clarification is still required. COMPLETE THE FOLLOWING: - Provide additional information regarding the anti-entrapment plan. Refer to the email previous sent.