Country Inn & Suites - Swimming Pool

2481 39 Avenue NE Calgary AB T2E 8V8 · Aquatic Facility

13 inspections

  1. Demand Inspection

    5 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • The water sample collected on June 1, 2026, was unsatisfactory with the presence of Pseudomonas aeruginosa.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The water sample collected on June 1, 2026, was unsatisfactory with an HPC of 400 CFU/mL.
    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • The free chlorine was measured to be 0.80 ppm. Maintain the free chlorine at minimum above 2.0 ppm if the swimming pool is to be kept at temperatures above 30C.**OUTSTANDING (2025-07-15). The Free Available Chlorine (FAC) concentration was measured at 0.62 ppm at 30.5°C. For pools at or below 30°C, the FAC must be maintained to at least 1.0 ppm FAC. If the pool is maintained at a temperature above 30°C, the pool must be maintained to at least 2.0 ppm FAC.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow rate (68 GPM) was not within the required range (min. 71.55 GPM, max. 73.5 GPM). Please maintain the flow rate to at least 71.55 GPM to ensure that the required turnover period of 4 hours and below is achieved.
    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • The Anti-Entrapment Compliance Plan was reviewed. The main drain suction outlet cover was expired on November 25, 2024. Please replace the main outlet covers. If it has already been replaced, please provide a copy of a Certificate of Compliance for the new main drain covers.
  2. Risk Management Inspection

    3 infractions

    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • The free chlorine was measured to be 0.80 ppm. Maintain the free chlorine at minimum above 2.0 ppm if the swimming pool is to be kept at temperatures above 30C.**OUTSTANDING (2025-07-15). The Free Available Chlorine (FAC) concentration was measured at 0.62 ppm at 30.5°C. For pools at or below 30°C, the FAC must be maintained to at least 1.0 ppm FAC. If the pool is maintained at a temperature above 30°C, the pool must be maintained to at least 2.0 ppm FAC.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow rate (68 GPM) was not within the required range (min. 71.55 GPM, max. 73.5 GPM). Please maintain the flow rate to at least 71.55 GPM to ensure that the required turnover period of 4 hours and below is achieved.
    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • The Anti-Entrapment Compliance Plan was reviewed. The main drain suction outlet cover was expired on November 25, 2024. Please replace the main outlet covers. If it has already been replaced, please provide a copy of a Certificate of Compliance for the new main drain covers.
  3. Demand Inspection

    4 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The water sample collected on August 5, 2025, was unsatisfactory with an HPC of 1,030 CFU/mL. Please send another sample immediately for reassessment.
    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • The free chlorine was measured to be 0.80 ppm. Maintain the free chlorine at minimum above 2.0 ppm if the swimming pool is to be kept at temperatures above 30C.**OUTSTANDING (2025-07-15). The Free Available Chlorine (FAC) concentration was measured at 0.62 ppm at 30.5°C. For pools at or below 30°C, the FAC must be maintained to at least 1.0 ppm FAC. If the pool is maintained at a temperature above 30°C, the pool must be maintained to at least 2.0 ppm FAC.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow rate (68 GPM) was not within the required range (min. 71.55 GPM, max. 73.5 GPM). Please maintain the flow rate to at least 71.55 GPM to ensure that the required turnover period of 4 hours and below is achieved.
    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • The Anti-Entrapment Compliance Plan was reviewed. The main drain suction outlet cover was expired on November 25, 2024. Please replace the main outlet covers. If it has already been replaced, please provide a copy of a Certificate of Compliance for the new main drain covers.
  4. Monitoring Inspection

    3 infractions

    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • The free chlorine was measured to be 0.80 ppm. Maintain the free chlorine at minimum above 2.0 ppm if the swimming pool is to be kept at temperatures above 30C.**OUTSTANDING (2025-07-15). The Free Available Chlorine (FAC) concentration was measured at 0.62 ppm at 30.5°C. For pools at or below 30°C, the FAC must be maintained to at least 1.0 ppm FAC. If the pool is maintained at a temperature above 30°C, the pool must be maintained to at least 2.0 ppm FAC.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow rate (68 GPM) was not within the required range (min. 71.55 GPM, max. 73.5 GPM). Please maintain the flow rate to at least 71.55 GPM to ensure that the required turnover period of 4 hours and below is achieved.
    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • The Anti-Entrapment Compliance Plan was reviewed. The main drain suction outlet cover was expired on November 25, 2024. Please replace the main outlet covers. If it has already been replaced, please provide a copy of a Certificate of Compliance for the new main drain covers.
  5. Risk Management Inspection

    2 infractions

    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • The free chlorine was measured to be 0.80 ppm.REQUIREMENT: Maintain the free chlorine at minimum above 2.0 ppm if the swimming pool is to be kept at temperatures above 30C.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The Lectrantor Pool Pilot displayed a warning message of 'Low Amps - Cell?'. It appears that the cell is not receiving the proper amps.REQUIREMENT: Investigate the cause of this error and ensure that proper chlorine generation is occuring.
  6. Demand Inspection

    3 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Sample collected on June 3, 2025, was not tested as there was no identification number on the bottle.**Please re-sample.
    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • The free chlorine was measured to be 0.80 ppm.REQUIREMENT: Maintain the free chlorine at minimum above 2.0 ppm if the swimming pool is to be kept at temperatures above 30C.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The Lectrantor Pool Pilot displayed a warning message of 'Low Amps - Cell?'. It appears that the cell is not receiving the proper amps.REQUIREMENT: Investigate the cause of this error and ensure that proper chlorine generation is occuring.
  7. Demand Inspection

    3 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The sample collected on May 27, 2025, had a HPC count of 110 CFU/mL which is higher than the requirement (<=100 CFU/mL).**Please submit a new sample immediately.
    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • The free chlorine was measured to be 0.80 ppm.REQUIREMENT: Maintain the free chlorine at minimum above 2.0 ppm if the swimming pool is to be kept at temperatures above 30C.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The Lectrantor Pool Pilot displayed a warning message of 'Low Amps - Cell?'. It appears that the cell is not receiving the proper amps.REQUIREMENT: Investigate the cause of this error and ensure that proper chlorine generation is occuring.
  8. Risk Management Inspection

    2 infractions

    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • The free chlorine was measured to be 0.80 ppm.REQUIREMENT: Maintain the free chlorine at minimum above 2.0 ppm if the swimming pool is to be kept at temperatures above 30C.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The Lectrantor Pool Pilot displayed a warning message of 'Low Amps - Cell?'. It appears that the cell is not receiving the proper amps.REQUIREMENT: Investigate the cause of this error and ensure that proper chlorine generation is occuring.
  9. Demand Inspection

    3 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The water sample collected on April 1, 2025, had an HPC of 130 CFU/mL.
    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • The free chlorine was measured to be 0.80 ppm.REQUIREMENT: Maintain the free chlorine at minimum above 2.0 ppm if the swimming pool is to be kept at temperatures above 30C.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The Lectrantor Pool Pilot displayed a warning message of 'Low Amps - Cell?'. It appears that the cell is not receiving the proper amps.REQUIREMENT: Investigate the cause of this error and ensure that proper chlorine generation is occuring.
  10. Risk Management Inspection

    2 infractions

    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • The free chlorine was measured to be 0.80 ppm.REQUIREMENT: Maintain the free chlorine at minimum above 2.0 ppm if the swimming pool is to be kept at temperatures above 30C.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The Lectrantor Pool Pilot displayed a warning message of 'Low Amps - Cell?'. It appears that the cell is not receiving the proper amps.REQUIREMENT: Investigate the cause of this error and ensure that proper chlorine generation is occuring.
  11. Demand Inspection

    4 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The facility appears to be keeping the swimming pool at temperatures above 30C but is not indicating that on the water sample requisition form.REQUIREMENT: Water temperature must be checked daily - ensure the water sample form is properly filled out to verify for Pseudomonas in the water.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The bacteriological water sample submitted on December 27, 2024, had an HPC count of 320 CFU/ml. REQUIREMENT: Please collect and send a re-sample, ensure sample is not contaminated during the sampling procedures. Label as resample.
    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • The free chlorine was measured to be 0.80 ppm.REQUIREMENT: Maintain the free chlorine at minimum above 2.0 ppm if the swimming pool is to be kept at temperatures above 30C.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The Lectrantor Pool Pilot displayed a warning message of 'Low Amps - Cell?'. It appears that the cell is not receiving the proper amps.REQUIREMENT: Investigate the cause of this error and ensure that proper chlorine generation is occuring.
  12. Demand Inspection

    4 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The facility appears to be keeping the swimming pool at temperatures above 30C but is not indicating that on the water sample requisition form.REQUIREMENT: Water temperature must be checked daily - ensure the water sample form is properly filled out to verify for Pseudomonas in the water.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The bacteriological water sample submitted on August 27, 2024, had an HPC count of 1790 CFU/ml. REQUIREMENT: Please review the water chemistry and begin immediate treatment for the swimming pool; Collect and send a re-sample after you complete necessary treatments and when the water chemistry is balanced.
    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • The free chlorine was measured to be 0.80 ppm.REQUIREMENT: Maintain the free chlorine at minimum above 2.0 ppm if the swimming pool is to be kept at temperatures above 30C.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The Lectrantor Pool Pilot displayed a warning message of 'Low Amps - Cell?'. It appears that the cell is not receiving the proper amps.REQUIREMENT: Investigate the cause of this error and ensure that proper chlorine generation is occuring.
  13. Monitoring Inspection

    3 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The facility appears to be keeping the swimming pool at temperatures above 30C but is not indicating that on the water sample requisition form.REQUIREMENT: Water temperature must be checked daily - ensure the water sample form is properly filled out to verify for Pseudomonas in the water.
    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • The free chlorine was measured to be 0.80 ppm.REQUIREMENT: Maintain the free chlorine at minimum above 2.0 ppm if the swimming pool is to be kept at temperatures above 30C.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The Lectrantor Pool Pilot displayed a warning message of 'Low Amps - Cell?'. It appears that the cell is not receiving the proper amps.REQUIREMENT: Investigate the cause of this error and ensure that proper chlorine generation is occuring.