Hampton Inn & Suites by Hilton Calgary South - Swimming Pool
2420 37 Avenue NE Calgary AB T2E 8S6 · Aquatic Facility
23 inspections
- Risk Management Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- **Outstanding **The automated feeder display for pH was not consistent with manual tests; the display for pH 7.04, whereas the inspector tested the pH at 7.44 (a >0.4ppm difference).**Please calibrate the probe. REQUIREMENT: Ensure the manual tests and automated feeder display readings are consistent with each other and investigate and correct any cause for the discrepancy between readings.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample collected on December 26, 2025, was not tested because the non-urgent sample was received during the weekend/holiday without approval.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- **Outstanding **The automated feeder display for pH was not consistent with manual tests; the display for pH 7.04, whereas the inspector tested the pH at 7.44 (a >0.4ppm difference).**Please calibrate the probe. REQUIREMENT: Ensure the manual tests and automated feeder display readings are consistent with each other and investigate and correct any cause for the discrepancy between readings.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- **Outstanding **The automated feeder display for pH was not consistent with manual tests; the display for pH 7.04, whereas the inspector tested the pH at 7.44 (a >0.4ppm difference).**Please calibrate the probe. REQUIREMENT: Ensure the manual tests and automated feeder display readings are consistent with each other and investigate and correct any cause for the discrepancy between readings.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample collected on September 18, 2025, was not tested because the sample was received more than 24 hours after the collection. Another water sample is to be submitted.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- **Outstanding **The automated feeder display for pH was not consistent with manual tests; the display for pH 7.04, whereas the inspector tested the pH at 7.44 (a >0.4ppm difference).**Please calibrate the probe. REQUIREMENT: Ensure the manual tests and automated feeder display readings are consistent with each other and investigate and correct any cause for the discrepancy between readings.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- **Outstanding **The automated feeder display for pH was not consistent with manual tests; the display for pH 7.04, whereas the inspector tested the pH at 7.44 (a >0.4ppm difference).**Please calibrate the probe. REQUIREMENT: Ensure the manual tests and automated feeder display readings are consistent with each other and investigate and correct any cause for the discrepancy between readings.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample collected on July 18, 2025, was not tested because the sample was received more than 24 hours after collection.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- **Outstanding **The automated feeder display for pH was not consistent with manual tests; the display for pH 7.04, whereas the inspector tested the pH at 7.44 (a >0.4ppm difference).**Please calibrate the probe. REQUIREMENT: Ensure the manual tests and automated feeder display readings are consistent with each other and investigate and correct any cause for the discrepancy between readings.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- **Outstanding **The automated feeder display for pH was not consistent with manual tests; the display for pH 7.04, whereas the inspector tested the pH at 7.44 (a >0.4ppm difference).**Please calibrate the probe. REQUIREMENT: Ensure the manual tests and automated feeder display readings are consistent with each other and investigate and correct any cause for the discrepancy between readings.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample collected on June 24, 2025, was unsatisfactory with an HPC of 170 CFU/mL.**Please begin treatment for the swimming pool immediately.**Submit a re-sample after the treatment is completed and water chemistry is re-balanced
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample collected on June 20, 2025, was unsatisfactory with an HPC of 1350 CFU/mL.**Please re-sample.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- **Outstanding **The automated feeder display for pH was not consistent with manual tests; the display for pH 7.04, whereas the inspector tested the pH at 7.44 (a >0.4ppm difference).**Please calibrate the probe. REQUIREMENT: Ensure the manual tests and automated feeder display readings are consistent with each other and investigate and correct any cause for the discrepancy between readings.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample collected on June 20, 2025, was unsatisfactory with an HPC of 1350 CFU/mL.**Please re-sample.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- **Outstanding **The automated feeder display for pH was not consistent with manual tests; the display for pH 7.04, whereas the inspector tested the pH at 7.44 (a >0.4ppm difference).**Please calibrate the probe. REQUIREMENT: Ensure the manual tests and automated feeder display readings are consistent with each other and investigate and correct any cause for the discrepancy between readings.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Monitoring Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- **Outstanding **The automated feeder display for pH was not consistent with manual tests; the display for pH 7.04, whereas the inspector tested the pH at 7.44 (a >0.4ppm difference).**Please calibrate the probe. REQUIREMENT: Ensure the manual tests and automated feeder display readings are consistent with each other and investigate and correct any cause for the discrepancy between readings.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
6 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- **Unsatisfactory Water Sample Test Results**The water sample collected on May 30, 2025, was unsatisfactory with an HPC of 1280 CFU/mL.**Treat the pool. **Submit a resample after re-balancing the water chemistry.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- **Unsatisfactory Water Sample Test Results**The water sample collected on June 6, 2025, was unsatisfactory with an HPC of 5880 CFU/mL.**Treat the pool. **Submit a resample after re-balancing the water chemistry.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- **Unsatisfactory Water Sample Test Results**The water sample collected on June 13, 2025, was unsatisfactory with an HPC of 1630 CFU/mL.**Treat the pool. **Submit a resample after re-balancing the water chemistry.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- **Not observed**1) The total alkalinity was measured to be 31 ppm.REQUIREMENT: Maintain the total alkalinity between 60 - 180 ppm.2) The combined chlorines were measured to be 2.08 ppm.REQUIREMENT: Maintain the combined chlorines to the lowest level possible. Treat the water by dilution with fresh water and/or shock chlorinating to breakpoint chlorination.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- **Not observed **1) The automated feeder display for pH was not consistent with manual tests; the display for pH 6.82, whereas the inspector tested the pH at 7.28 (a >0.4ppm difference).The operator was not aware of the age of the probes or when the probes were last calibrated.REQUIREMENT: Ensure the manual tests and automated feeder display readings are consistent with each other and investigate and correct any cause for the discrepancy between readings.2) The flow meter was jammed, and therefore any calculation to determine if turnover period is being achieved is not possible.REQUIREMENT: Repair the flow meter and ensure that the minimum flow specified in the comments is being maintained.
- 15. Has an owner or owner's agent, if any, been identified and is the pool operated and maintained by a qualified pool operator?
- **Not observed**There is no person who is currently certified to operate the swimming pool.A maintenance worker is due to receive the training in later September.REQUIREMENT: The swimming pool must be maintained by a certified pool operator who is readily available to react to any problems.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
5 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- **Unsatisfactory Water Sample Test Results**The water sample collected on June 6, 2025, was unsatisfactory with an HPC of 5880 CFU/mL.**Treat the pool. **Submit a resample after re-balancing the water chemistry.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- **Unsatisfactory Water Sample Test Results**The water sample collected on May 30, 2025, was unsatisfactory with an HPC of 1280 CFU/mL.**Treat the pool. **Submit a resample after re-balancing the water chemistry.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- 1) The total alkalinity was measured to be 31 ppm.REQUIREMENT: Maintain the total alkalinity between 60 - 180 ppm.2) The combined chlorines were measured to be 2.08 ppm.REQUIREMENT: Maintain the combined chlorines to the lowest level possible. Treat the water by dilution with fresh water and/or shock chlorinating to breakpoint chlorination.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- 1) The automated feeder display for pH was not consistent with manual tests; the display for pH 6.82, whereas the inspector tested the pH at 7.28 (a >0.4ppm difference).The operator was not aware of the age of the probes or when the probes were last calibrated.REQUIREMENT: Ensure the manual tests and automated feeder display readings are consistent with each other and investigate and correct any cause for the discrepancy between readings.2) The flow meter was jammed, and therefore any calculation to determine if turnover period is being achieved is not possible.REQUIREMENT: Repair the flow meter and ensure that the minimum flow specified in the comments is being maintained.
- 15. Has an owner or owner's agent, if any, been identified and is the pool operated and maintained by a qualified pool operator?
- There is no person who is currently certified to operate the swimming pool.A maintenance worker is due to receive the training in later September.REQUIREMENT: The swimming pool must be maintained by a certified pool operator who is readily available to react to any problems.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
3 infractions
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- 1) The total alkalinity was measured to be 31 ppm.REQUIREMENT: Maintain the total alkalinity between 60 - 180 ppm.2) The combined chlorines were measured to be 2.08 ppm.REQUIREMENT: Maintain the combined chlorines to the lowest level possible. Treat the water by dilution with fresh water and/or shock chlorinating to breakpoint chlorination.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- 1) The automated feeder display for pH was not consistent with manual tests; the display for pH 6.82, whereas the inspector tested the pH at 7.28 (a >0.4ppm difference).The operator was not aware of the age of the probes or when the probes were last calibrated.REQUIREMENT: Ensure the manual tests and automated feeder display readings are consistent with each other and investigate and correct any cause for the discrepancy between readings.2) The flow meter was jammed, and therefore any calculation to determine if turnover period is being achieved is not possible.REQUIREMENT: Repair the flow meter and ensure that the minimum flow specified in the comments is being maintained.
- 15. Has an owner or owner's agent, if any, been identified and is the pool operated and maintained by a qualified pool operator?
- There is no person who is currently certified to operate the swimming pool.A maintenance worker is due to receive the training in later September.REQUIREMENT: The swimming pool must be maintained by a certified pool operator who is readily available to react to any problems.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
4 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- **UNSATISFACTORY WATER SAMPLE TEST RESULT**The water sample collected on May 30, 2025, was unsatisfactory with an HPC of 1280 CFU/mL.**Treat the pool. **Submit a resample after re-balancing the water chemistry.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- 1) The total alkalinity was measured to be 31 ppm.REQUIREMENT: Maintain the total alkalinity between 60 - 180 ppm.2) The combined chlorines were measured to be 2.08 ppm.REQUIREMENT: Maintain the combined chlorines to the lowest level possible. Treat the water by dilution with fresh water and/or shock chlorinating to breakpoint chlorination.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- 1) The automated feeder display for pH was not consistent with manual tests; the display for pH 6.82, whereas the inspector tested the pH at 7.28 (a >0.4ppm difference).The operator was not aware of the age of the probes or when the probes were last calibrated.REQUIREMENT: Ensure the manual tests and automated feeder display readings are consistent with each other and investigate and correct any cause for the discrepancy between readings.2) The flow meter was jammed, and therefore any calculation to determine if turnover period is being achieved is not possible.REQUIREMENT: Repair the flow meter and ensure that the minimum flow specified in the comments is being maintained.
- 15. Has an owner or owner's agent, if any, been identified and is the pool operated and maintained by a qualified pool operator?
- There is no person who is currently certified to operate the swimming pool.A maintenance worker is due to receive the training in later September.REQUIREMENT: The swimming pool must be maintained by a certified pool operator who is readily available to react to any problems.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
4 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- **UNSATISFACTORY WATER SAMPLE TEST RESULT**1. The water sample collected on May 16, 2025, was unsatisfactory with an HPC of 720 CFU/mL.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- 1) The total alkalinity was measured to be 31 ppm.REQUIREMENT: Maintain the total alkalinity between 60 - 180 ppm.2) The combined chlorines were measured to be 2.08 ppm.REQUIREMENT: Maintain the combined chlorines to the lowest level possible. Treat the water by dilution with fresh water and/or shock chlorinating to breakpoint chlorination.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- 1) The automated feeder display for pH was not consistent with manual tests; the display for pH 6.82, whereas the inspector tested the pH at 7.28 (a >0.4ppm difference).The operator was not aware of the age of the probes or when the probes were last calibrated.REQUIREMENT: Ensure the manual tests and automated feeder display readings are consistent with each other and investigate and correct any cause for the discrepancy between readings.2) The flow meter was jammed, and therefore any calculation to determine if turnover period is being achieved is not possible.REQUIREMENT: Repair the flow meter and ensure that the minimum flow specified in the comments is being maintained.
- 15. Has an owner or owner's agent, if any, been identified and is the pool operated and maintained by a qualified pool operator?
- There is no person who is currently certified to operate the swimming pool.A maintenance worker is due to receive the training in later September.REQUIREMENT: The swimming pool must be maintained by a certified pool operator who is readily available to react to any problems.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
3 infractions
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- 1) The total alkalinity was measured to be 31 ppm.REQUIREMENT: Maintain the total alkalinity between 60 - 180 ppm.2) The combined chlorines were measured to be 2.08 ppm.REQUIREMENT: Maintain the combined chlorines to the lowest level possible. Treat the water by dilution with fresh water and/or shock chlorinating to breakpoint chlorination.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- 1) The automated feeder display for pH was not consistent with manual tests; the display for pH 6.82, whereas the inspector tested the pH at 7.28 (a >0.4ppm difference).The operator was not aware of the age of the probes or when the probes were last calibrated.REQUIREMENT: Ensure the manual tests and automated feeder display readings are consistent with each other and investigate and correct any cause for the discrepancy between readings.2) The flow meter was jammed, and therefore any calculation to determine if turnover period is being achieved is not possible.REQUIREMENT: Repair the flow meter and ensure that the minimum flow specified in the comments is being maintained.
- 15. Has an owner or owner's agent, if any, been identified and is the pool operated and maintained by a qualified pool operator?
- There is no person who is currently certified to operate the swimming pool.A maintenance worker is due to receive the training in later September.REQUIREMENT: The swimming pool must be maintained by a certified pool operator who is readily available to react to any problems.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
4 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- **UNSATISFACTORY WATER SAMPLE**1. The water sample collected on April 4, 2025, had an HPC of 980 CFU/mL.2. The water sample collected on April 25, 2025, had an HPC of 440 CFU/mL.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- 1) The total alkalinity was measured to be 31 ppm.REQUIREMENT: Maintain the total alkalinity between 60 - 180 ppm.2) The combined chlorines were measured to be 2.08 ppm.REQUIREMENT: Maintain the combined chlorines to the lowest level possible. Treat the water by dilution with fresh water and/or shock chlorinating to breakpoint chlorination.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- 1) The automated feeder display for pH was not consistent with manual tests; the display for pH 6.82, whereas the inspector tested the pH at 7.28 (a >0.4ppm difference).The operator was not aware of the age of the probes or when the probes were last calibrated.REQUIREMENT: Ensure the manual tests and automated feeder display readings are consistent with each other and investigate and correct any cause for the discrepancy between readings.2) The flow meter was jammed, and therefore any calculation to determine if turnover period is being achieved is not possible.REQUIREMENT: Repair the flow meter and ensure that the minimum flow specified in the comments is being maintained.
- 15. Has an owner or owner's agent, if any, been identified and is the pool operated and maintained by a qualified pool operator?
- There is no person who is currently certified to operate the swimming pool.A maintenance worker is due to receive the training in later September.REQUIREMENT: The swimming pool must be maintained by a certified pool operator who is readily available to react to any problems.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
4 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample collected on April 4, 2025, had an HPC of 980 CFU/mL.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- 1) The total alkalinity was measured to be 31 ppm.REQUIREMENT: Maintain the total alkalinity between 60 - 180 ppm.2) The combined chlorines were measured to be 2.08 ppm.REQUIREMENT: Maintain the combined chlorines to the lowest level possible. Treat the water by dilution with fresh water and/or shock chlorinating to breakpoint chlorination.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- 1) The automated feeder display for pH was not consistent with manual tests; the display for pH 6.82, whereas the inspector tested the pH at 7.28 (a >0.4ppm difference).The operator was not aware of the age of the probes or when the probes were last calibrated.REQUIREMENT: Ensure the manual tests and automated feeder display readings are consistent with each other and investigate and correct any cause for the discrepancy between readings.2) The flow meter was jammed, and therefore any calculation to determine if turnover period is being achieved is not possible.REQUIREMENT: Repair the flow meter and ensure that the minimum flow specified in the comments is being maintained.
- 15. Has an owner or owner's agent, if any, been identified and is the pool operated and maintained by a qualified pool operator?
- There is no person who is currently certified to operate the swimming pool.A maintenance worker is due to receive the training in later September.REQUIREMENT: The swimming pool must be maintained by a certified pool operator who is readily available to react to any problems.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
3 infractions
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- 1) The total alkalinity was measured to be 31 ppm.REQUIREMENT: Maintain the total alkalinity between 60 - 180 ppm.2) The combined chlorines were measured to be 2.08 ppm.REQUIREMENT: Maintain the combined chlorines to the lowest level possible. Treat the water by dilution with fresh water and/or shock chlorinating to breakpoint chlorination.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- 1) The automated feeder display for pH was not consistent with manual tests; the display for pH 6.82, whereas the inspector tested the pH at 7.28 (a >0.4ppm difference).The operator was not aware of the age of the probes or when the probes were last calibrated.REQUIREMENT: Ensure the manual tests and automated feeder display readings are consistent with each other and investigate and correct any cause for the discrepancy between readings.2) The flow meter was jammed, and therefore any calculation to determine if turnover period is being achieved is not possible.REQUIREMENT: Repair the flow meter and ensure that the minimum flow specified in the comments is being maintained.
- 15. Has an owner or owner's agent, if any, been identified and is the pool operated and maintained by a qualified pool operator?
- There is no person who is currently certified to operate the swimming pool.A maintenance worker is due to receive the training in later September.REQUIREMENT: The swimming pool must be maintained by a certified pool operator who is readily available to react to any problems.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
4 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The bacteriological water sample collected on March 21, 2025, showed an HPC of 790 CFU/mL. The operator was instructed to send another sample immediately.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- 1) The total alkalinity was measured to be 31 ppm.REQUIREMENT: Maintain the total alkalinity between 60 - 180 ppm.2) The combined chlorines were measured to be 2.08 ppm.REQUIREMENT: Maintain the combined chlorines to the lowest level possible. Treat the water by dilution with fresh water and/or shock chlorinating to breakpoint chlorination.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- 1) The automated feeder display for pH was not consistent with manual tests; the display for pH 6.82, whereas the inspector tested the pH at 7.28 (a >0.4ppm difference).The operator was not aware of the age of the probes or when the probes were last calibrated.REQUIREMENT: Ensure the manual tests and automated feeder display readings are consistent with each other and investigate and correct any cause for the discrepancy between readings.2) The flow meter was jammed, and therefore any calculation to determine if turnover period is being achieved is not possible.REQUIREMENT: Repair the flow meter and ensure that the minimum flow specified in the comments is being maintained.
- 15. Has an owner or owner's agent, if any, been identified and is the pool operated and maintained by a qualified pool operator?
- There is no person who is currently certified to operate the swimming pool.A maintenance worker is due to receive the training in later September.REQUIREMENT: The swimming pool must be maintained by a certified pool operator who is readily available to react to any problems.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
3 infractions
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- 1) The total alkalinity was measured to be 31 ppm.REQUIREMENT: Maintain the total alkalinity between 60 - 180 ppm.2) The combined chlorines were measured to be 2.08 ppm.REQUIREMENT: Maintain the combined chlorines to the lowest level possible. Treat the water by dilution with fresh water and/or shock chlorinating to breakpoint chlorination.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- 1) The automated feeder display for pH was not consistent with manual tests; the display for pH 6.82, whereas the inspector tested the pH at 7.28 (a >0.4ppm difference).The operator was not aware of the age of the probes or when the probes were last calibrated.REQUIREMENT: Ensure the manual tests and automated feeder display readings are consistent with each other and investigate and correct any cause for the discrepancy between readings.2) The flow meter was jammed, and therefore any calculation to determine if turnover period is being achieved is not possible.REQUIREMENT: Repair the flow meter and ensure that the minimum flow specified in the comments is being maintained.
- 15. Has an owner or owner's agent, if any, been identified and is the pool operated and maintained by a qualified pool operator?
- There is no person who is currently certified to operate the swimming pool.A maintenance worker is due to receive the training in later September.REQUIREMENT: The swimming pool must be maintained by a certified pool operator who is readily available to react to any problems.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
4 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Pool water sample submitted on December 20, 2024, had HPC (Heterotrophic Plate Count) enumerated at 970 CFU/mL.-Please treat the pool in accordance with the AHS guidelines and submit another water sample. Label as resample.Here is the website for pool treatment: https://www.albertahealthservices.ca/assets/wf/eph/wf-eph-interpret-microbiological-sample-results-pools.pdf
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- 1) The total alkalinity was measured to be 31 ppm.REQUIREMENT: Maintain the total alkalinity between 60 - 180 ppm.2) The combined chlorines were measured to be 2.08 ppm.REQUIREMENT: Maintain the combined chlorines to the lowest level possible. Treat the water by dilution with fresh water and/or shock chlorinating to breakpoint chlorination.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- 1) The automated feeder display for pH was not consistent with manual tests; the display for pH 6.82, whereas the inspector tested the pH at 7.28 (a >0.4ppm difference).The operator was not aware of the age of the probes or when the probes were last calibrated.REQUIREMENT: Ensure the manual tests and automated feeder display readings are consistent with each other and investigate and correct any cause for the discrepancy between readings.2) The flow meter was jammed, and therefore any calculation to determine if turnover period is being achieved is not possible.REQUIREMENT: Repair the flow meter and ensure that the minimum flow specified in the comments is being maintained.
- 15. Has an owner or owner's agent, if any, been identified and is the pool operated and maintained by a qualified pool operator?
- There is no person who is currently certified to operate the swimming pool.A maintenance worker is due to receive the training in later September.REQUIREMENT: The swimming pool must be maintained by a certified pool operator who is readily available to react to any problems.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Initial Inspection
4 infractions
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- 1) The total alkalinity was measured to be 31 ppm.REQUIREMENT: Maintain the total alkalinity between 60 - 180 ppm.2) The combined chlorines were measured to be 2.08 ppm.REQUIREMENT: Maintain the combined chlorines to the lowest level possible. Treat the water by dilution with fresh water and/or shock chlorinating to breakpoint chlorination.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- 1) The automated feeder display for pH was not consistent with manual tests; the display for pH 6.82, whereas the inspector tested the pH at 7.28 (a >0.4ppm difference).The operator was not aware of the age of the probes or when the probes were last calibrated.REQUIREMENT: Ensure the manual tests and automated feeder display readings are consistent with each other and investigate and correct any cause for the discrepancy between readings.2) The flow meter was jammed, and therefore any calculation to determine if turnover period is being achieved is not possible.REQUIREMENT: Repair the flow meter and ensure that the minimum flow specified in the comments is being maintained.
- 09. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Critical)?
- The maintenance person testing the water chemistry was using improper testing methods which would skew or alter the test results.For example, the operator would not properly titrate during a total alkalinity test (i.e. one drop at a time), and would not compare the readings in natural light.These issues were discussed with the operator and will be considered corrected during the inspection in the meantime.
- 15. Has an owner or owner's agent, if any, been identified and is the pool operated and maintained by a qualified pool operator?
- There is no person who is currently certified to operate the swimming pool.A maintenance worker is due to receive the training in later September.REQUIREMENT: The swimming pool must be maintained by a certified pool operator who is readily available to react to any problems.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?