Delta by Marriott Grande Prairie Airport - Swimming Pool

11702 99 Avenue Grande Prairie AB T8W 0C7 · Aquatic Facility

15 inspections

  1. Risk Management Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Sample collected on May 19, 2026:Lab results show 300 cfu/mL of HPC.Update on June 01, 2026:Sample collected on May 27, 2026, lab results indicate 180 cfu/mL of HPC.Update on June 8, 2026:Sample collected on June 3, 2026, lab results: HPC: 500 CFU/mL Ensure HPC is less than 100 CFU/mL. Shock chlorinate the swimming pool before submitting another water sample this week.
  2. Monitoring Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Sample collected on May 19, 2026:Lab results show 300 cfu/mL of HPC.Update on June 01, 2026:Sample collected on May 27, 2026, lab results indicate 180 cfu/mL of HPC.
  3. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Sample collected on May 19, 2026:Lab results show 300 cfu/mL of HPC.
  4. Monitoring Inspection

    0 infractions

  5. Risk Management Inspection

    0 infractions

  6. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Unsatisfactory Lab Result received from July 9, 2024: HPC 130 CFU/ml.Update July 22, 2024: Unsatisfactory laboratory result received from July 16, 2024: HPC 220 CFU/ml. Please super chlorinate and submit a resample.Update July 29, 2024: Unsatisfactory laboratory result received from July 24, 2024: HPC 300 CFU/ml. Please ensure to super chlorinate immediately and resample as soon as possible. Operator indicated that super chlorination would happen this afternoon.
  7. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Unsatisfactory Lab Result received from July 9, 2024: HPC 130 CFU/ml.Update July 22, 2024: Unsatisfactory laboratory result received from July 16, 2024: HPC 220 CFU/ml. Please super chlorinate and submit a resample.
    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • The flow rate for the pool is 70 gpm. On the anti-entrapment plan the maximum flow rate for the pool is 60 gpm.Please reduce the flow rate to below 60 gpm.
  8. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Unsatisfactory Lab Result received from July 9, 2024: HPC 130 CFU/ml.Please submit a resample.
    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • The flow rate for the pool is 70 gpm. On the anti-entrapment plan the maximum flow rate for the pool is 60 gpm.Please reduce the flow rate to below 60 gpm.
  9. Risk Management Inspection

    1 infraction

    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • The flow rate for the pool is 70 gpm. On the anti-entrapment plan the maximum flow rate for the pool is 60 gpm.Please reduce the flow rate to below 60 gpm.
  10. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Unsatisfactory water result received May 14, 2024: HPC 150 CFU/ mlPlease resample.
    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • The flow rate for the pool is 70 gpm. On the anti-entrapment plan the maximum flow rate for the pool is 60 gpm.Please reduce the flow rate to below 60 gpm.
  11. Risk Management Inspection

    1 infraction

    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • The flow rate for the pool is 70 gpm. On the anti-entrapment plan the maximum flow rate for the pool is 60 gpm.Please reduce the flow rate to below 60 gpm.
  12. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Unsatisfactory laboratory report received, HPC 1300 CFU/ml.Please resample the pool.
    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • The flow rate for the pool is 70 gpm. On the anti-entrapment plan the maximum flow rate for the pool is 60 gpm.Please reduce the flow rate to below 60 gpm.
  13. Risk Management Inspection

    1 infraction

    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • The flow rate for the pool is 70 gpm. On the anti-entrapment plan the maximum flow rate for the pool is 60 gpm.Please reduce the flow rate to below 60 gpm.
  14. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • HPC is noted at 1010 CFU/ml on the lab report.Please super chlorinate.Raise the FAC- 10 ppmEnsure pH is at or near 7.2. Run the pool water through the circulation system for at least one turnover period.
    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • The flow rate for the pool is 70 gpm. On the anti-entrapment plan the maximum flow rate for the pool is 60 gpm.Please reduce the flow rate to below 60 gpm.
  15. Monitoring Inspection

    1 infraction

    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • The flow rate for the pool is 70 gpm. On the anti-entrapment plan the maximum flow rate for the pool is 60 gpm.Please reduce the flow rate to below 60 gpm.