Delta Hotels by Marriott Calgary South - Atrium Whirlpool
135 Southland Drive SE Calgary AB T2J 5X5 · Aquatic Facility
6 inspections
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- 1. The water sample collected on June 16, 2026 not tested, because the time of collection was not provided on the requisition form.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
0 infractions
- Monitoring Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- 1. The flow metre for the recirculation pump measured 32 gpm during the inspection. The minimum flow rate to achieve a recirculation rate of 15 minutes is 39 gpm.COMPLETE THE FOLLOWING:1. Please ensure the whirlpool is meeting the 15 minute recirculation rate.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample collected on July 15, 2025 had 180 CFU/mL on the Heterotrophic Plate Count.-treat and resample-ID 25ES-196E00668
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
1 infraction
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Water sample collected on June 23/24 had Pseudomonas isolated and HPC 130 cfu/ml. - Treat the whirlpool water and resample.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Initial Inspection
0 infractions