Don Wheaton Family YMCA - Main Pool

10211 102 Avenue NW Edmonton AB T5J 0A5 · Aquatic Facility

8 inspections

  1. Risk Management Inspection

    0 infractions

  2. Monitoring Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • This flow meter does not appear to be providing accurate flow due to debris in the flow meter weighing down the float. Service or replace the flow meter so that the flow rate can be accurately measured.
  3. Risk Management Inspection

    0 infractions

  4. Demand Inspection

    1 infraction

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • The microbiological water sample submitted on 25 March 2025 was unsatisfactory: Total Coliform present. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
  5. Risk Management Inspection

    0 infractions

  6. Monitoring Inspection

    2 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow meter appears to have debris built up on the float that is causing errors in the readings. Clean the flow meter and forward the correct flow reading.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • Debris was noted in behind the railing in the middle of the ramp. Clean and remove the debris. Ensure staff are monitoring and checking regularly during maintenance cleaning of the basin.
  7. Monitoring Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Discrepancy noted between manual pH readings and the pH results taken from the BMS controller. Adjust the controller so that they are consistent with manual readings.
  8. Demand Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • The microbiological water sample submitted on 15 August 2023 was unsatisfactory: Pseudomonas aeruginosa isolated, Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Discrepancy noted between manual pH readings and the pH results taken from the BMS controller.