Don Wheaton Family YMCA - Teach Pool

10211 102 Avenue NW Edmonton AB T5J 0A5 · Aquatic Facility

6 inspections

  1. Monitoring Inspection

    2 infractions

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The alkalinity in the pool was >180ppm. Monitor and adjust to avoid excessive alkalinity which can lead to calcium formation on deck and possible pH drift.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The pH tested at the controller flow cell was not consistent with the controller pH reading. Check the pH and ensure that it is consistent with manual tests.
  2. Risk Management Inspection

    0 infractions

  3. Demand Inspection

    1 infraction

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • The microbiological water sample submitted on 25 March 2025 was unsatisfactory: Total Coliform present. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
  4. Monitoring Inspection

    0 infractions

  5. Demand Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • The microbiological water sample submitted on 25 June 2024 was unsatisfactory: Total Coliform present. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Flow meter indicator was observed to be stuck due to mineral build up. Descale and clean the flow meter during the next backwash.
  6. Monitoring Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Flow meter indicator was observed to be stuck due to mineral build up. Descale and clean the flow meter during the next backwash.