Don Wheaton Family YMCA - Women's Hot Tub

10211 102 Avenue NW Edmonton AB T5J 0A5 · Aquatic Facility

6 inspections

  1. Monitoring Inspection

    1 infraction

    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • Daily visual checks of the submerged suction outlet was not documented for the day of the inspection. Ensure staff are visually checking that the submerges suction outlets are secure and in good condition before opening the facility to patrons.
  2. Risk Management Inspection

    0 infractions

  3. Demand Inspection

    1 infraction

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • The microbiological water sample submitted on 17 Dec 2024 was unsatisfactory: Total Coliform present. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
  4. Monitoring Inspection

    0 infractions

  5. Risk Management Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Scum has been cleaned and removed in the skimmer.
  6. Monitoring Inspection

    3 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Discrepancy noted between manual pH readings and the pH results taken from the BMS controller. Check water chemistry and recalibrate the automated controller as required.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Scum was observed above the water line in one of the skimmers (right side of the guardrails). Clean to maintain water quality.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • Staff were not consistently documenting visual checks that the submerged suction outlets are installed and in good repair. Ensure staff are checking and documenting once per day.