Skip to content
Loading map…

Easter Seals Camp Horizon - Spray Park

1 Camp Horizon Road Kananaskis AB T0L 0K0 · Aquatic Facility

11 inspections

  1. Demand Inspection

    4 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Recent bacteriological test result showed TC present. Treat water and resample.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • High heterotrophic plate count of 2960 CFU/mL was measured. Treat water and submit resample.Update (July 9, 2026): heterotrophic plate count of 2660 CFU/mL was measured.
    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • Free available chlorine was measured at 0.35 ppm. Keep chlorine level above 2.0 ppm.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The total alkalinity measured was above 180ppm. Please adjust total alkalinity to between 60-180ppm.Update (July 9, 2026): Total Alkalinity was over 180 ppm, outside of the testing range.
  2. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • High heterotrophic plate count of 2960 CFU/mL was measured. Treat water and submit resample.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The total alkalinity measured was above 180ppm. Please adjust total alkalinity to between 60-180ppm.
  3. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample collected on June 8, 2026, was Unsatisfactory.HPC: 1,120 CFU/mL.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The total alkalinity measured was above 180ppm. Please adjust total alkalinity to between 60-180ppm.
  4. Monitoring Inspection

    2 infractions

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The total alkalinity measured was above 180ppm. Please adjust total alkalinity to between 60-180ppm.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow meter was not operational. Operator adjusted the flow meter.Ensure flow meter is in operation at all times and record readings to monitor operation of recirculation pump.
  5. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample collected on July 14 had a Heterotrophic Plate Count of 110 Colony Forming Units/mL.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • Concrete surface by the Fountain Rock was not in good repair. Please make sure it is repaired before the season starts.
  6. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Unsatisfactory water result was received. Water sample collected on June 9, 2025 was unsatisfactory. HPC: 620 CFU/mL.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • Concrete surface by the Fountain Rock was not in good repair. Please make sure it is repaired before the season starts.
  7. Monitoring Inspection

    1 infraction

    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • Concrete surface by the Fountain Rock was not in good repair. Please make sure it is repaired before the season starts.
  8. Demand Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • The sample collected August 21, 2024, was unsatisfactory due to the presence of Total Coliforms.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water report from August 21, 2024, was unsatisfactory. HPC: 1,230 CFU/mL
  9. Demand Inspection

    3 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • 1. August 21 sample came back positive for total coliforms.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water report from Aug. 12 was unsatisfactory. HPC :570 CFU/ml
    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • 1. Free chlorine measured 0.76ppm - 0.78ppm. COMPLETE THE FOLLOWING:1. Adjust chemistry so free chlorine is maintained above 2.0ppm.
  10. Demand Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • 1. August 21 sample came back positive for total coliforms.
    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • 1. Free chlorine measured 0.76ppm - 0.78ppm. COMPLETE THE FOLLOWING:1. Adjust chemistry so free chlorine is maintained above 2.0ppm.
  11. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • 1. HPC count of 230 CFU/mL.
    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • 1. Free chlorine measured 0.76ppm - 0.78ppm. COMPLETE THE FOLLOWING:1. Adjust chemistry so free chlorine is maintained above 2.0ppm.