Eastern Irrigation District Aquatic Centre - Lap Pool

323 1 Street E Brooks AB T1R 1B5 · Aquatic Facility

30 inspections

  1. Risk Management Inspection

    0 infractions

  2. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Heterotrophic Plate Count exceeded 100 CFU.
  3. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Heterotrophic Plate Count is elevated (1,670 CFU/ml).[Sample collected April 22, 2026]
  4. Monitoring Inspection

    0 infractions

  5. Risk Management Inspection

    1 infraction

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Total Alkalinity tested 0ppEnsure total alkalinity is adjusted to the required range of 60-180ppm as soon possible.02-03-2026Total Alkalinity 28 ppm
  6. Risk Management Inspection

    1 infraction

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Total Alkalinity tested 0ppEnsure total alkalinity is adjusted to the required range of 60-180ppm as soon possible.
  7. Risk Management Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • HPC >57,000
  8. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The HPC is moderately high (1250 CFU/mL).Sampling was conducted on October 15, 2025.
  9. Demand Inspection

    1 infraction

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Sample collected on August 20 was unsatisfactory. Operator will increase chlorine overnight and re-adjust and balance chemistry in the morning.
  10. Risk Management Inspection

    0 infractions

  11. Demand Inspection

    1 infraction

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Total coliforms present in the sample collected on Wednesday.
  12. Risk Management Inspection

    0 infractions

  13. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water Sample Taken on April 8, 2025.HPC: 930 CFU
  14. Monitoring Inspection

    0 infractions

  15. Risk Management Inspection

    0 infractions

  16. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The sample was rejected.
  17. Risk Management Inspection

    0 infractions

  18. Demand Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The chlorine motor and pump was working intermittently. The motor was replaced but the pump also needs to be replaced. Part is ordered and is prioritized for install when it arrives. A public swimming pool must be equipped with automated chemical feeding and monitoring equipment for pH and chlorine.*Replace pump and get the system back on automation as soon as the pump arrives. *Increase pool chemistry monitoring and test frequently.
  19. Monitoring Inspection

    1 infraction

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The total alkalinity was measured at 10 ppm. The operator added sodium bicarbonate to the pool water to increase the total alkalinity.
  20. Risk Management Inspection

    0 infractions

  21. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The HPC is high (3520 CFU/mL).
  22. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The water sample collected this week is showing an exceedance in HPC.
  23. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The water sample collected this week is showing an exceedance in HPC.
  24. Risk Management Inspection

    0 infractions

  25. Risk Management Inspection

    0 infractions

  26. Monitoring Inspection

    0 infractions

  27. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The bacteriological sample collected on February 22 reports high HPC which is an unsatisfactory result. Pool is closed to public for scheduled maintenance.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Drain covers in lap pool are yellowing and expired. Temporary management plan is in place.
  28. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The bacteriological sample collected on January 25 reports high HPC which is an unsatisfactory result.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Drain covers in lap pool are yellowing and expired. Temporary management plan in in place.
  29. Demand Inspection

    1 infraction

    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Drain covers in lap pool are yellowing and expired. Replace covers and implement temporary management plan.
  30. Monitoring Inspection

    0 infractions