Eastern Irrigation District Aquatic Centre - Whirlpool
323 1 Street E Brooks AB T1R 1B5 · Aquatic Facility
25 inspections
- Monitoring Inspection
0 infractions
- Risk Management Inspection
2 infractions
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Free chlorine 0.44 ppmTotal chlorine 1.05 ppmCombine chlorine 0.61 ppm* Ensure free chlorine is maintained at a minimum of 2 ppm for effective disinfection of the water.02-03-2026FC 1.08 pmmCC 0.12 ppmTC 1.20 ppm
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Total Alkalinity measured at 20 ppm. Ensure total alkalinity is within the range of 60-180 ppm.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
1 infraction
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Free chlorine 0.44 ppmTotal chlorine 1.05 ppmCombine chlorine 0.61 ppm* Ensure free chlorine is maintained at a minimum of 2 ppm for effective disinfection of the water.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Monitoring Inspection
0 infractions
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The sample was rejected.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Received water sample result for pseudomonas. Previous water sample results was satisfactory. Operator had already followed procedures for cleaning and refilling the basin. Operator will resample Tuesday.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
1 infraction
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Pseudomonas was isolated in the water sample from this week. Operator was notified and the protocol was providedOperator will resample Tuesday.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Monitoring Inspection
0 infractions
- Risk Management Inspection
0 infractions
- Risk Management Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample collected this week is showing an exceedance in HPC.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample collected this week is showing an exceedance in HPC.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample collected this week is showing an exceedance in HPC.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
0 infractions
- Risk Management Inspection
0 infractions
- Monitoring Inspection
1 infraction
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Whirlpool drain frames and covers have been replaced. Flow rates have been determined. Operator is finalizing the anti-entrapment plan.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Risk Management Inspection
1 infraction
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Whirlpool drain covers may be expired. Flow rate over drain cover has not been determined. Determine flow rates to size covers. Replace expired covers.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Demand Inspection
2 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Water sample collected February 14 had Pseudomonas aeruginosa isolated.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Whirlpool drain covers may be expired. Flow rate over drain cover has not been determined. Determine flow rates to size covers. Replace expired covers.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample collected on December 28 had HPC count of 880.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Whirlpool drain covers may be expired. Flow rate over drain cover has not been determined. Determine flow rates to size covers. Replace expired covers.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
1 infraction
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Whirlpool drain covers may be expired. Flow rate over drain cover has not been determined. Determine flow rates to size covers. Replace expired covers.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Risk Management Inspection
0 infractions
- Risk Management Inspection
1 infraction
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Sample collected on November 16 reported Psuedomonas isolated. Whirlpool has been closed since Sunday afternoon and chlorine level was brought up to 10 ppm for 18 hours. Whirlpool will be sanitized, drained, refilled and balanced.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
0 infractions
- Monitoring Inspection
0 infractions