Hampton Inn by Hilton Calgary Airport North - Hot Tub

2000 - 2021 100 Avenue NE Calgary AB T3J 0R3 · Aquatic Facility

22 inspections

  1. Risk Management Inspection

    2 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • **Ongoing Violation** The flow meter was jammed at the time of the inspection.REQUIRMENT: Repair or replace the flow meter. Ensure the flow is maintained to it's appropriate range.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • **Ongoing Concern** Two inspections ago, it was noted that: "The temperature of this basin, according to the chlorine generator controller, was reading 106F which is 41.1 C."The last inspection, the temperature was measured to be 41.8C, and this inspection the temperature was measured to be 41C.Operators believe that due to excessive humidity, heat is being trapped inside the hot tub.REQUIREMENT: Ensure the maximum hot water temperature does not exceed 40C. Service all machinery necessary so that this temperature can be successfully lowered.
  2. Demand Inspection

    3 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • The water sample collected on December 9, 2025, was unsatisfactory with the presence of Total Coliforms. Close the whirlpool, then conduct the required treatment, as discussed, then re-submit another water sample for re-testing.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • **Ongoing Violation** The flow meter was jammed at the time of the inspection.REQUIRMENT: Repair or replace the flow meter. Ensure the flow is maintained to it's appropriate range.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • **Ongoing Concern** Two inspections ago, it was noted that: "The temperature of this basin, according to the chlorine generator controller, was reading 106F which is 41.1 C."The last inspection, the temperature was measured to be 41.8C, and this inspection the temperature was measured to be 41C.Operators believe that due to excessive humidity, heat is being trapped inside the hot tub.REQUIREMENT: Ensure the maximum hot water temperature does not exceed 40C. Service all machinery necessary so that this temperature can be successfully lowered.
  3. Risk Management Inspection

    2 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • **Ongoing Violation** The flow meter was jammed at the time of the inspection.REQUIRMENT: Repair or replace the flow meter. Ensure the flow is maintained to it's appropriate range.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • **Ongoing Concern** Two inspections ago, it was noted that: "The temperature of this basin, according to the chlorine generator controller, was reading 106F which is 41.1 C."The last inspection, the temperature was measured to be 41.8C, and this inspection the temperature was measured to be 41C.Operators believe that due to excessive humidity, heat is being trapped inside the hot tub.REQUIREMENT: Ensure the maximum hot water temperature does not exceed 40C. Service all machinery necessary so that this temperature can be successfully lowered.
  4. Demand Inspection

    4 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • An unsatisfactory water sample test result was received with the following test results:- Total coliforms present.- Pseudomonas aeruginosa isolated.Action Required:Please close the whirlpool, do the required treatment, then re-submit another sample.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • An unsatisfactory water sample test result was received with the following test results:- HPC of 140 CFU/mL.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • **Ongoing Violation** The flow meter was jammed at the time of the inspection.REQUIRMENT: Repair or replace the flow meter. Ensure the flow is maintained to it's appropriate range.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • **Ongoing Concern** Two inspections ago, it was noted that: "The temperature of this basin, according to the chlorine generator controller, was reading 106F which is 41.1 C."The last inspection, the temperature was measured to be 41.8C, and this inspection the temperature was measured to be 41C.Operators believe that due to excessive humidity, heat is being trapped inside the hot tub.REQUIREMENT: Ensure the maximum hot water temperature does not exceed 40C. Service all machinery necessary so that this temperature can be successfully lowered.
  5. Risk Management Inspection

    2 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • **Ongoing Violation** The flow meter was jammed at the time of the inspection.REQUIRMENT: Repair or replace the flow meter. Ensure the flow is maintained to it's appropriate range.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • **Ongoing Concern** Two inspections ago, it was noted that: "The temperature of this basin, according to the chlorine generator controller, was reading 106F which is 41.1 C."The last inspection, the temperature was measured to be 41.8C, and this inspection the temperature was measured to be 41C.Operators believe that due to excessive humidity, heat is being trapped inside the hot tub.REQUIREMENT: Ensure the maximum hot water temperature does not exceed 40C. Service all machinery necessary so that this temperature can be successfully lowered.
  6. Demand Inspection

    4 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • The water sample that was collected on October 20, 2025, was unsatisfactory with the following result(s): Presence of Pseudomonas aeruginosa.**OUTSTANDING (2025-10-22). The water sample collected on October 22, 2025, was unsatisfactory, with the following results: Presence of Pseudomonas aeruginosa.**OUTSTANDING (2025-10-28). The water sample collected on October 28, 2025, was not tested because it was unsuitable for testing due to excessive chlorine.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The water sample that was collected on October 20, 2025, was unsatisfactory with the following result(s): HPC of 260 CFU/mL.**OUTSTANDING (2025-10-22). The water sample collected on October 22, 2025, was unsatisfactory, with the following results: HPC of >57,000 CFU/mL.**OUTSTANDING (2025-10-28). The water sample collected on October 28, 2025, was not tested because it was unsuitable for testing due to excessive chlorine.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • **Ongoing Violation** The flow meter was jammed at the time of the inspection.REQUIRMENT: Repair or replace the flow meter. Ensure the flow is maintained to it's appropriate range.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • **Ongoing Concern** Two inspections ago, it was noted that: "The temperature of this basin, according to the chlorine generator controller, was reading 106F which is 41.1 C."The last inspection, the temperature was measured to be 41.8C, and this inspection the temperature was measured to be 41C.Operators believe that due to excessive humidity, heat is being trapped inside the hot tub.REQUIREMENT: Ensure the maximum hot water temperature does not exceed 40C. Service all machinery necessary so that this temperature can be successfully lowered.
  7. Demand Inspection

    4 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • The water sample that was collected on October 20, 2025, was unsatisfactory with the following result(s): Presence of Pseudomonas aeruginosa.**OUTSTANDING (2025-10-22). The water sample collected on October 22, 2025, was unsatisfactory, with the following results: Presence of Pseudomonas aeruginosa.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The water sample that was collected on October 20, 2025, was unsatisfactory with the following result(s): HPC of 260 CFU/mL.**OUTSTANDING (2025-10-22). The water sample collected on October 22, 2025, was unsatisfactory, with the following results: HPC of >57,000 CFU/mL.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • **Ongoing Violation** The flow meter was jammed at the time of the inspection.REQUIRMENT: Repair or replace the flow meter. Ensure the flow is maintained to it's appropriate range.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • **Ongoing Concern** Two inspections ago, it was noted that: "The temperature of this basin, according to the chlorine generator controller, was reading 106F which is 41.1 C."The last inspection, the temperature was measured to be 41.8C, and this inspection the temperature was measured to be 41C.Operators believe that due to excessive humidity, heat is being trapped inside the hot tub.REQUIREMENT: Ensure the maximum hot water temperature does not exceed 40C. Service all machinery necessary so that this temperature can be successfully lowered.
  8. Demand Inspection

    4 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • The water sample that was collected on October 20, 2025, was unsatisfactory with the following result(s): Presence of Pseudomonas aeruginosa.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The water sample that was collected on October 20, 2025, was unsatisfactory with the following result(s): HPC of 260 CFU/mL.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • **Ongoing Violation** The flow meter was jammed at the time of the inspection.REQUIRMENT: Repair or replace the flow meter. Ensure the flow is maintained to it's appropriate range.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • **Ongoing Concern** Two inspections ago, it was noted that: "The temperature of this basin, according to the chlorine generator controller, was reading 106F which is 41.1 C."The last inspection, the temperature was measured to be 41.8C, and this inspection the temperature was measured to be 41C.Operators believe that due to excessive humidity, heat is being trapped inside the hot tub.REQUIREMENT: Ensure the maximum hot water temperature does not exceed 40C. Service all machinery necessary so that this temperature can be successfully lowered.
  9. Risk Management Inspection

    2 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • **Ongoing Violation** The flow meter was jammed at the time of the inspection.REQUIRMENT: Repair or replace the flow meter. Ensure the flow is maintained to it's appropriate range.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • **Ongoing Concern** Two inspections ago, it was noted that: "The temperature of this basin, according to the chlorine generator controller, was reading 106F which is 41.1 C."The last inspection, the temperature was measured to be 41.8C, and this inspection the temperature was measured to be 41C.Operators believe that due to excessive humidity, heat is being trapped inside the hot tub.REQUIREMENT: Ensure the maximum hot water temperature does not exceed 40C. Service all machinery necessary so that this temperature can be successfully lowered.
  10. Demand Inspection

    3 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • The water sample collected on June 2, 2025, had Total Coliforms present in the sample.**Please begin treatment for the swimming pool immediately.**Submit a re-sample after the treatment is completed and water chemistry is re-balanced
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • **Ongoing Violation** The flow meter was jammed at the time of the inspection.REQUIRMENT: Repair or replace the flow meter. Ensure the flow is maintained to it's appropriate range.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • **Ongoing Concern** Two inspections ago, it was noted that: "The temperature of this basin, according to the chlorine generator controller, was reading 106F which is 41.1 C."The last inspection, the temperature was measured to be 41.8C, and this inspection the temperature was measured to be 41C.Operators believe that due to excessive humidity, heat is being trapped inside the hot tub.REQUIREMENT: Ensure the maximum hot water temperature does not exceed 40C. Service all machinery necessary so that this temperature can be successfully lowered.
  11. Monitoring Inspection

    2 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • **Ongoing Violation** The flow meter was jammed at the time of the inspection.REQUIRMENT: Repair or replace the flow meter. Ensure the flow is maintained to it's appropriate range.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • **Ongoing Concern** Two inspections ago, it was noted that: "The temperature of this basin, according to the chlorine generator controller, was reading 106F which is 41.1 C."The last inspection, the temperature was measured to be 41.8C, and this inspection the temperature was measured to be 41C.Operators believe that due to excessive humidity, heat is being trapped inside the hot tub.REQUIREMENT: Ensure the maximum hot water temperature does not exceed 40C. Service all machinery necessary so that this temperature can be successfully lowered.
  12. Demand Inspection

    4 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The water sample collected on June 10, 2024, has an HPC count of 2050 CFU/mL.REQUIREMENT: Review the water chemistry and treat the water. Take a re-sample once treatments are complete and the water chemistry is rebalanced.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow meter was jammed at the time of the inspection.REQUIRMENT: Repair or replace the flow meter. Ensure the flow is maintained to it's appropriate range.
    • 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
      • A pool product 'Bioguard Power Chlor' contains Trichloro-s-Triazinetrione also known as Trichloroisocyanuric acid, which is a stabilised chlorine product.Testing for this product in the water showed it did not appear to be a residual.REQUIREMENT: No cyanuric acid or products containing cyanuric acid may be used or be present in an indoor public swimming pool. Discard this product in accordance with the manufacturer's specifications.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • **Ongoing Concern** Last inspection, it was noted that: "The temperature of this basin, according to the chlorine generator controller, was reading 106F which is 41.1 C."This inspection, the temperature was measured to be 41.8CREQUIREMENT: Ensure the maximum hot water temperature does not exceed 40C.
  13. Monitoring Inspection

    3 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow meter was jammed at the time of the inspection.REQUIRMENT: Repair or replace the flow meter. Ensure the flow is maintained to it's appropriate range.
    • 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
      • A pool product 'Bioguard Power Chlor' contains Trichloro-s-Triazinetrione also known as Trichloroisocyanuric acid, which is a stabilised chlorine product.Testing for this product in the water showed it did not appear to be a residual.REQUIREMENT: No cyanuric acid or products containing cyanuric acid may be used or be present in an indoor public swimming pool. Discard this product in accordance with the manufacturer's specifications.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • **Ongoing Concern** Last inspection, it was noted that: "The temperature of this basin, according to the chlorine generator controller, was reading 106F which is 41.1 C."This inspection, the temperature was measured to be 41.8CREQUIREMENT: Ensure the maximum hot water temperature does not exceed 40C.
  14. Demand Inspection

    4 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The water sample collected on February 22, 2024, had an HPC count of >57000 CFU/mL.REQUIREMENT: Review the water chemistry (consider a shock treatment) and treat/balance as needed. Send in a re-sample when/if the water chemistry appears satisfactory.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Last inspection, it was noted that: "The TA in the whirlpool measured 22 ppm at the time of inspection."This inspection, the TA was measured to be 44 ppm. The operator added sodium bicarbonate to the pool to increase the reading.REQUIREMENT: Increase and maintain the TA to between 60 and 180 ppm. It is strongly recommended to test the TA more frequently to ensure it can be maintained.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • The temperature of this basin, according to the chlorine generator controller, was reading 106F which is 41.1 C.REQUIREMENT: Ensure the maximum hot water temperature does not exceed 40C.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • The combined chlorines were not being tested and recorded daily.REQUIREMENT: The combined chlorines must be tested, and the value/result recorded daily. Take appropriate actions when the combined chlorines are too high.
  15. Risk Management Inspection

    3 infractions

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Last inspection, it was noted that: "The TA in the whirlpool measured 22 ppm at the time of inspection."This inspection, the TA was measured to be 44 ppm. The operator added sodium bicarbonate to the pool to increase the reading.REQUIREMENT: Increase and maintain the TA to between 60 and 180 ppm. It is strongly recommended to test the TA more frequently to ensure it can be maintained.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • The temperature of this basin, according to the chlorine generator controller, was reading 106F which is 41.1 C.REQUIREMENT: Ensure the maximum hot water temperature does not exceed 40C.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • The combined chlorines were not being tested and recorded daily.REQUIREMENT: The combined chlorines must be tested, and the value/result recorded daily. Take appropriate actions when the combined chlorines are too high.
  16. Demand Inspection

    4 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The water sample collected on February 02, 2024, had an HPC count of 890 CFU/mL.REQUIREMENT: Review the water chemistry and begin treatment of the water. Collect and send a re-sample after you complete necessary treatments – ensure on the form it’s listed as a resample.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Last inspection, it was noted that: "The TA in the whirlpool measured 22 ppm at the time of inspection."This inspection, the TA was measured to be 44 ppm. The operator added sodium bicarbonate to the pool to increase the reading.REQUIREMENT: Increase and maintain the TA to between 60 and 180 ppm. It is strongly recommended to test the TA more frequently to ensure it can be maintained.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • The temperature of this basin, according to the chlorine generator controller, was reading 106F which is 41.1 C.REQUIREMENT: Ensure the maximum hot water temperature does not exceed 40C.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • The combined chlorines were not being tested and recorded daily.REQUIREMENT: The combined chlorines must be tested, and the value/result recorded daily. Take appropriate actions when the combined chlorines are too high.
  17. Demand Inspection

    4 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The water sample collected on January 11, 2024, had an HPC count of 190 CFU/mL.REQUIREMENT: Review the water chemistry and begin treatment of the water. Collect and send a re-sample after you complete necessary treatments – ensure on the form it’s listed as a resample.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Last inspection, it was noted that: "The TA in the whirlpool measured 22 ppm at the time of inspection."This inspection, the TA was measured to be 44 ppm. The operator added sodium bicarbonate to the pool to increase the reading.REQUIREMENT: Increase and maintain the TA to between 60 and 180 ppm. It is strongly recommended to test the TA more frequently to ensure it can be maintained.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • The temperature of this basin, according to the chlorine generator controller, was reading 106F which is 41.1 C.REQUIREMENT: Ensure the maximum hot water temperature does not exceed 40C.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • The combined chlorines were not being tested and recorded daily.REQUIREMENT: The combined chlorines must be tested, and the value/result recorded daily. Take appropriate actions when the combined chlorines are too high.
  18. Risk Management Inspection

    3 infractions

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Last inspection, it was noted that: "The TA in the whirlpool measured 22 ppm at the time of inspection."This inspection, the TA was measured to be 44 ppm. The operator added sodium bicarbonate to the pool to increase the reading.REQUIREMENT: Increase and maintain the TA to between 60 and 180 ppm. It is strongly recommended to test the TA more frequently to ensure it can be maintained.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • The temperature of this basin, according to the chlorine generator controller, was reading 106F which is 41.1 C.REQUIREMENT: Ensure the maximum hot water temperature does not exceed 40C.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • The combined chlorines were not being tested and recorded daily.REQUIREMENT: The combined chlorines must be tested, and the value/result recorded daily. Take appropriate actions when the combined chlorines are too high.
  19. Demand Inspection

    4 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • The water sample collected on November 23, 2023 had total coliforms detected in the sample.REQUIREMENT: Review the water chemistry for both basins and begin immediate treatment of the water. Collect and send a re-sample immediately after you complete necessary treatments.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Last inspection, it was noted that: "The TA in the whirlpool measured 22 ppm at the time of inspection."This inspection, the TA was measured to be 44 ppm. The operator added sodium bicarbonate to the pool to increase the reading.REQUIREMENT: Increase and maintain the TA to between 60 and 180 ppm. It is strongly recommended to test the TA more frequently to ensure it can be maintained.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • The temperature of this basin, according to the chlorine generator controller, was reading 106F which is 41.1 C.REQUIREMENT: Ensure the maximum hot water temperature does not exceed 40C.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • The combined chlorines were not being tested and recorded daily.REQUIREMENT: The combined chlorines must be tested, and the value/result recorded daily. Take appropriate actions when the combined chlorines are too high.
  20. Demand Inspection

    5 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • The water sample collected on August 24, 2023 had total coliforms detected in the sample.REQUIREMENT: Review the water chemistry for both basins and begin immediate treatment of the water. Collect and send a re-sample immediately after you complete necessary treatments
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The water sample collected on August 24, 2023, had HPC detected at 550 CFU/mL.REQUIREMENT: Review the water chemistry for both basins and begin immediate treatment of the water. Collect and send a re-sample immediately after you complete necessary treatments.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Last inspection, it was noted that: "The TA in the whirlpool measured 22 ppm at the time of inspection."This inspection, the TA was measured to be 44 ppm. The operator added sodium bicarbonate to the pool to increase the reading.REQUIREMENT: Increase and maintain the TA to between 60 and 180 ppm. It is strongly recommended to test the TA more frequently to ensure it can be maintained.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • The temperature of this basin, according to the chlorine generator controller, was reading 106F which is 41.1 C.REQUIREMENT: Ensure the maximum hot water temperature does not exceed 40C.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • The combined chlorines were not being tested and recorded daily.REQUIREMENT: The combined chlorines must be tested, and the value/result recorded daily. Take appropriate actions when the combined chlorines are too high.
  21. Risk Management Inspection

    3 infractions

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Last inspection, it was noted that: "The TA in the whirlpool measured 22 ppm at the time of inspection."This inspection, the TA was measured to be 44 ppm. The operator added sodium bicarbonate to the pool to increase the reading.REQUIREMENT: Increase and maintain the TA to between 60 and 180 ppm. It is strongly recommended to test the TA more frequently to ensure it can be maintained.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • The temperature of this basin, according to the chlorine generator controller, was reading 106F which is 41.1 C.REQUIREMENT: Ensure the maximum hot water temperature does not exceed 40C.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • The combined chlorines were not being tested and recorded daily.REQUIREMENT: The combined chlorines must be tested, and the value/result recorded daily. Take appropriate actions when the combined chlorines are too high.
  22. Demand Inspection

    5 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • The water sample collected on July 20, 2023, had Total Coliforms detected in the sample.REQUIREMENT: Please review the water chemistry and begin immediate treatment of the water. Collect and send a re-sample immediately after you complete necessary treatments – ensure on the form it’s listed as a resample.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The water sample collected on July 20, 2023, had HPC detected at >57000 CFU/mL.REQUIREMENT: The actions needed are in combination with the detection of Total Coliforms in the water. . Please review the water chemistry and begin immediate treatment of the water. Collect and send a re-sample immediately after you complete necessary treatments – ensure on the form it’s listed as a resample.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Last inspection, it was noted that: "The TA in the whirlpool measured 22 ppm at the time of inspection."This inspection, the TA was measured to be 44 ppm. The operator added sodium bicarbonate to the pool to increase the reading.REQUIREMENT: Increase and maintain the TA to between 60 and 180 ppm. It is strongly recommended to test the TA more frequently to ensure it can be maintained.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • The temperature of this basin, according to the chlorine generator controller, was reading 106F which is 41.1 C.REQUIREMENT: Ensure the maximum hot water temperature does not exceed 40C.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • The combined chlorines were not being tested and recorded daily.REQUIREMENT: The combined chlorines must be tested, and the value/result recorded daily. Take appropriate actions when the combined chlorines are too high.