Hampton Inn by Hilton Calgary Airport North - Pool

2000 - 2021 100 Avenue NE Calgary AB T3J 0R3 · Aquatic Facility

Inspection summary

Hampton Inn by Hilton Calgary Airport North - Pool has been inspected 20 times by Alberta Health Services (Environmental Public Health) since October 20, 2023. The most recent inspection, on July 24, 2026, recorded 3 infractions.

1 of 20 inspections on record found no infractions at all. In the past 12 months there were 3 inspections with 9 infractions recorded. The higher-risk findings here relate to: Pool and spa water quality and Chemicals and toxic substances.

The number of infractions per inspection has stayed roughly the same over time.

What these findings mean

Health authorities word their findings differently, so we group them by what they mean for the people using the facility. Higher-risk findings are the ones that could directly cause illness or injury, such as water that is not properly treated.

  • Pool and spa water qualityHigher risk

    For pools, spas and splash pads, inspectors test disinfectant levels, pH and water clarity, and check safety equipment. Water that is not properly treated can spread skin, ear and stomach infections.

    Recorded 29 times across 19 separate inspections, most recently on July 24, 2026. For example: Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?

  • Chemicals and toxic substancesHigher risk

    Pool chemicals such as chlorine and acid must be labelled, stored apart from each other and handled safely. Mixing them by mistake can release toxic gas, so storage and handling problems are treated seriously.

    Recorded 6 times across 6 separate inspections, most recently on July 24, 2026. For example: Is the chemical quality of the water in this pool satisfactory (Non-Critical)?

  • Permits, records and postingLower risk

    Operating permits, water-test logs, posted bather rules and emergency procedures. Daily test logs are how operators show the water was checked and treated between inspections.

    Recorded 7 times across 7 separate inspections, most recently on February 16, 2024. For example: Are proper testing, monitoring, and other records being properly maintained?

About this data

These results come from Alberta Health Services (Environmental Public Health), which inspects food premises and other public facilities in this area. We republish the authority's public disclosure data and refresh it regularly; the official record is the final word.

20 inspections

  1. Demand Inspection

    3 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The water sample collected on July 22, 2026, was unsatisfactory due to the elevated HPC of 380 CFU/mL.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The combined chlorines were measured to be 1.79 ppm.REQUIREMENT: Maintain the combined chlorines to the lowest level possible.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow meter was not operating properly. It appears that air inside the meter is preventing it from properly operating.REQUIREMENT: Repair or replace the flow meter. Ensure the flow is maintaining the pool between the minimum and maximum flow rate specified.
  2. Risk Management Inspection

    2 infractions

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The combined chlorines were measured to be 1.79 ppm.REQUIREMENT: Maintain the combined chlorines to the lowest level possible.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow meter was not operating properly. It appears that air inside the meter is preventing it from properly operating.REQUIREMENT: Repair or replace the flow meter. Ensure the flow is maintaining the pool between the minimum and maximum flow rate specified.
  3. Demand Inspection

    4 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • The water sample that was collected on October 16, 2025, was unsatisfactory with the following results: Presence of Total Coliforms.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The water sample that was collected on October 16, 2025, was unsatisfactory with the following results: HPC of >57,000 CFU/mL.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The combined chlorines were measured to be 1.79 ppm.REQUIREMENT: Maintain the combined chlorines to the lowest level possible.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow meter was not operating properly. It appears that air inside the meter is preventing it from properly operating.REQUIREMENT: Repair or replace the flow meter. Ensure the flow is maintaining the pool between the minimum and maximum flow rate specified.
  4. Risk Management Inspection

    2 infractions

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The combined chlorines were measured to be 1.79 ppm.REQUIREMENT: Maintain the combined chlorines to the lowest level possible.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow meter was not operating properly. It appears that air inside the meter is preventing it from properly operating.REQUIREMENT: Repair or replace the flow meter. Ensure the flow is maintaining the pool between the minimum and maximum flow rate specified.
  5. Demand Inspection

    3 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The water sample collected on July 21, 2025 had a HPC count of 150 CFU/mL. **Please resample.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The combined chlorines were measured to be 1.79 ppm.REQUIREMENT: Maintain the combined chlorines to the lowest level possible.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow meter was not operating properly. It appears that air inside the meter is preventing it from properly operating.REQUIREMENT: Repair or replace the flow meter. Ensure the flow is maintaining the pool between the minimum and maximum flow rate specified.
  6. Monitoring Inspection

    2 infractions

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The combined chlorines were measured to be 1.79 ppm.REQUIREMENT: Maintain the combined chlorines to the lowest level possible.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow meter was not operating properly. It appears that air inside the meter is preventing it from properly operating.REQUIREMENT: Repair or replace the flow meter. Ensure the flow is maintaining the pool between the minimum and maximum flow rate specified.
  7. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The water sample collected on November 12, 2024, had an HPC Count of 130 CFU/mL in the sample.REQUIREMENT: Review the water chemistry and treat the water. Take a re-sample once treatments are complete and the water chemistry is rebalanced.
  8. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The water sample collected on June 05, 2024, had an HPC Count of 11200 CFU/mL in the sample.The water sample collected on June 10, 2024, had an HPC Count of 1860 CFU/mL in the sample.REQUIREMENT: Review the water chemistry and treat the water. Take a re-sample once treatments are complete and the water chemistry is rebalanced.
  9. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The water sample collected on June 05, 2024, had an HPC Count of 11200 CFU/mL in the sample.REQUIREMENT: Review the water chemistry and treat the water. Take a re-sample once treatments are complete and the water chemistry is rebalanced.
  10. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The water sample collected on May 16, 2024, had an HPC Count of 520 CFU/mL in the sample.REQUIREMENT: Review the water chemistry and treat the water. Take a re-sample once treatments are complete and the water chemistry is rebalanced.
  11. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The water sample collected on April 11, 2024, had an HPC Count of 480 CFU/mL in the sample.The water sample collected on April 19, 2024, had an HPC Count of 550 CFU/mL in the sample.REQUIREMENT: Review the water chemistry and treat the water. Take a re-sample once treatments are complete and the water chemistry is rebalanced.
  12. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The water sample collected on April 11, 2024, had an HPC Count of 480 CFU/mL in the sample.REQUIREMENT: Review the water chemistry and treat the water. Take a re-sample once treatments are complete and the water chemistry is rebalanced.
  13. Monitoring Inspection

    0 infractions

  14. Risk Management Inspection

    2 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow meter float appeared to be jammed, causing a reading of approximately 45 USGPM.REQUIREMENT: Repair the flow meter. Maintain the flow of the pool between 76 and 106 USGPM.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • The combined chlorines were not being tested and recorded daily.REQUIREMENT: The combined chlorines must be tested, and the value/result recorded daily. Take appropriate actions when the combined chlorines are too high.
  15. Demand Inspection

    3 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The pool water sample collected on February 8, 2024, had an HPC count of 1740 cfu/ml.REQUIREMENT: review the water chemistry for the swimming pool and conduct any treatment necessary of the water. Collect and send a re-sample immediately after you complete necessary treatment – ensure on the form it’s listed as a resample.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow meter float appeared to be jammed, causing a reading of approximately 45 USGPM.REQUIREMENT: Repair the flow meter. Maintain the flow of the pool between 76 and 106 USGPM.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • The combined chlorines were not being tested and recorded daily.REQUIREMENT: The combined chlorines must be tested, and the value/result recorded daily. Take appropriate actions when the combined chlorines are too high.
  16. Risk Management Inspection

    2 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow meter float appeared to be jammed, causing a reading of approximately 45 USGPM.REQUIREMENT: Repair the flow meter. Maintain the flow of the pool between 76 and 106 USGPM.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • The combined chlorines were not being tested and recorded daily.REQUIREMENT: The combined chlorines must be tested, and the value/result recorded daily. Take appropriate actions when the combined chlorines are too high.
  17. Demand Inspection

    4 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • The water sample collected on November 09, 2023, has total coliforms detected in the sample.Closure order has been issued for a 2nd consecutive unsatisfactory water sample.REQUIREMENT: Review the water chemistry for the swimming pool and conduct any treatment necessary of the water. Collect and send a re-sample immediately after you complete necessary treatment – ensure on the form it’s listed as a resample.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The water sample collected on November 02, 2023, has HPC detected at 670 CFU/mL.REQUIREMENT: Review the water chemistry for the swimming pool and conduct any treatment necessary of the water. Collect and send a re-sample immediately after you complete necessary treatment – ensure on the form it’s listed as a resample.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow meter float appeared to be jammed, causing a reading of approximately 45 USGPM.REQUIREMENT: Repair the flow meter. Maintain the flow of the pool between 76 and 106 USGPM.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • The combined chlorines were not being tested and recorded daily.REQUIREMENT: The combined chlorines must be tested, and the value/result recorded daily. Take appropriate actions when the combined chlorines are too high.
  18. Demand Inspection

    3 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The water sample collected on November 02, 2023, has HPC detected at 670 CFU/mL.REQUIREMENT: review the water chemistry for the swimming pool and conduct any treatment necessary of the water. Collect and send a re-sample immediately after you complete necessary treatment – ensure on the form it’s listed as a resample.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow meter float appeared to be jammed, causing a reading of approximately 45 USGPM.REQUIREMENT: Repair the flow meter. Maintain the flow of the pool between 76 and 106 USGPM.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • The combined chlorines were not being tested and recorded daily.REQUIREMENT: The combined chlorines must be tested, and the value/result recorded daily. Take appropriate actions when the combined chlorines are too high.
  19. Risk Management Inspection

    2 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow meter float appeared to be jammed, causing a reading of approximately 45 USGPM.REQUIREMENT: Repair the flow meter. Maintain the flow of the pool between 76 and 106 USGPM.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • The combined chlorines were not being tested and recorded daily.REQUIREMENT: The combined chlorines must be tested, and the value/result recorded daily. Take appropriate actions when the combined chlorines are too high.
  20. Demand Inspection

    4 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • The water sample collected on October 18, 2023 had total coliforms detected in the sample.REQUIREMENT: Review the water chemistry for both basins and begin immediate treatment of the water. Collect and send a re-sample immediately after you complete necessary treatments
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The water sample collected on October 12, 2023, had HPC detected at 420 CFU/mL.REQUIREMENT: Review the water chemistry for both basins and begin immediate treatment of the water. Collect and send a re-sample immediately after you complete necessary treatments
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow meter float appeared to be jammed, causing a reading of approximately 45 USGPM.REQUIREMENT: Repair the flow meter. Maintain the flow of the pool between 76 and 106 USGPM.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • The combined chlorines were not being tested and recorded daily.REQUIREMENT: The combined chlorines must be tested, and the value/result recorded daily. Take appropriate actions when the combined chlorines are too high.