Hampton Inn by Hilton Calgary Airport North - Pool
2000 - 2021 100 Avenue NE Calgary AB T3J 0R3 · Aquatic Facility
23 inspections
- Risk Management Inspection
2 infractions
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The combined chlorines were measured to be 1.79 ppm.REQUIREMENT: Maintain the combined chlorines to the lowest level possible.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The flow meter was not operating properly. It appears that air inside the meter is preventing it from properly operating.REQUIREMENT: Repair or replace the flow meter. Ensure the flow is maintaining the pool between the minimum and maximum flow rate specified.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
4 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- The water sample that was collected on October 16, 2025, was unsatisfactory with the following results: Presence of Total Coliforms.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample that was collected on October 16, 2025, was unsatisfactory with the following results: HPC of >57,000 CFU/mL.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The combined chlorines were measured to be 1.79 ppm.REQUIREMENT: Maintain the combined chlorines to the lowest level possible.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The flow meter was not operating properly. It appears that air inside the meter is preventing it from properly operating.REQUIREMENT: Repair or replace the flow meter. Ensure the flow is maintaining the pool between the minimum and maximum flow rate specified.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
2 infractions
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The combined chlorines were measured to be 1.79 ppm.REQUIREMENT: Maintain the combined chlorines to the lowest level possible.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The flow meter was not operating properly. It appears that air inside the meter is preventing it from properly operating.REQUIREMENT: Repair or replace the flow meter. Ensure the flow is maintaining the pool between the minimum and maximum flow rate specified.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample collected on July 21, 2025 had a HPC count of 150 CFU/mL. **Please resample.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The combined chlorines were measured to be 1.79 ppm.REQUIREMENT: Maintain the combined chlorines to the lowest level possible.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The flow meter was not operating properly. It appears that air inside the meter is preventing it from properly operating.REQUIREMENT: Repair or replace the flow meter. Ensure the flow is maintaining the pool between the minimum and maximum flow rate specified.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Monitoring Inspection
2 infractions
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The combined chlorines were measured to be 1.79 ppm.REQUIREMENT: Maintain the combined chlorines to the lowest level possible.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The flow meter was not operating properly. It appears that air inside the meter is preventing it from properly operating.REQUIREMENT: Repair or replace the flow meter. Ensure the flow is maintaining the pool between the minimum and maximum flow rate specified.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample collected on November 12, 2024, had an HPC Count of 130 CFU/mL in the sample.REQUIREMENT: Review the water chemistry and treat the water. Take a re-sample once treatments are complete and the water chemistry is rebalanced.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample collected on June 05, 2024, had an HPC Count of 11200 CFU/mL in the sample.The water sample collected on June 10, 2024, had an HPC Count of 1860 CFU/mL in the sample.REQUIREMENT: Review the water chemistry and treat the water. Take a re-sample once treatments are complete and the water chemistry is rebalanced.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample collected on June 05, 2024, had an HPC Count of 11200 CFU/mL in the sample.REQUIREMENT: Review the water chemistry and treat the water. Take a re-sample once treatments are complete and the water chemistry is rebalanced.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample collected on May 16, 2024, had an HPC Count of 520 CFU/mL in the sample.REQUIREMENT: Review the water chemistry and treat the water. Take a re-sample once treatments are complete and the water chemistry is rebalanced.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample collected on April 11, 2024, had an HPC Count of 480 CFU/mL in the sample.The water sample collected on April 19, 2024, had an HPC Count of 550 CFU/mL in the sample.REQUIREMENT: Review the water chemistry and treat the water. Take a re-sample once treatments are complete and the water chemistry is rebalanced.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample collected on April 11, 2024, had an HPC Count of 480 CFU/mL in the sample.REQUIREMENT: Review the water chemistry and treat the water. Take a re-sample once treatments are complete and the water chemistry is rebalanced.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Monitoring Inspection
0 infractions
- Risk Management Inspection
2 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The flow meter float appeared to be jammed, causing a reading of approximately 45 USGPM.REQUIREMENT: Repair the flow meter. Maintain the flow of the pool between 76 and 106 USGPM.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- The combined chlorines were not being tested and recorded daily.REQUIREMENT: The combined chlorines must be tested, and the value/result recorded daily. Take appropriate actions when the combined chlorines are too high.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The pool water sample collected on February 8, 2024, had an HPC count of 1740 cfu/ml.REQUIREMENT: review the water chemistry for the swimming pool and conduct any treatment necessary of the water. Collect and send a re-sample immediately after you complete necessary treatment – ensure on the form it’s listed as a resample.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The flow meter float appeared to be jammed, causing a reading of approximately 45 USGPM.REQUIREMENT: Repair the flow meter. Maintain the flow of the pool between 76 and 106 USGPM.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- The combined chlorines were not being tested and recorded daily.REQUIREMENT: The combined chlorines must be tested, and the value/result recorded daily. Take appropriate actions when the combined chlorines are too high.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
2 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The flow meter float appeared to be jammed, causing a reading of approximately 45 USGPM.REQUIREMENT: Repair the flow meter. Maintain the flow of the pool between 76 and 106 USGPM.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- The combined chlorines were not being tested and recorded daily.REQUIREMENT: The combined chlorines must be tested, and the value/result recorded daily. Take appropriate actions when the combined chlorines are too high.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
4 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- The water sample collected on November 09, 2023, has total coliforms detected in the sample.Closure order has been issued for a 2nd consecutive unsatisfactory water sample.REQUIREMENT: Review the water chemistry for the swimming pool and conduct any treatment necessary of the water. Collect and send a re-sample immediately after you complete necessary treatment – ensure on the form it’s listed as a resample.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample collected on November 02, 2023, has HPC detected at 670 CFU/mL.REQUIREMENT: Review the water chemistry for the swimming pool and conduct any treatment necessary of the water. Collect and send a re-sample immediately after you complete necessary treatment – ensure on the form it’s listed as a resample.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The flow meter float appeared to be jammed, causing a reading of approximately 45 USGPM.REQUIREMENT: Repair the flow meter. Maintain the flow of the pool between 76 and 106 USGPM.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- The combined chlorines were not being tested and recorded daily.REQUIREMENT: The combined chlorines must be tested, and the value/result recorded daily. Take appropriate actions when the combined chlorines are too high.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample collected on November 02, 2023, has HPC detected at 670 CFU/mL.REQUIREMENT: review the water chemistry for the swimming pool and conduct any treatment necessary of the water. Collect and send a re-sample immediately after you complete necessary treatment – ensure on the form it’s listed as a resample.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The flow meter float appeared to be jammed, causing a reading of approximately 45 USGPM.REQUIREMENT: Repair the flow meter. Maintain the flow of the pool between 76 and 106 USGPM.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- The combined chlorines were not being tested and recorded daily.REQUIREMENT: The combined chlorines must be tested, and the value/result recorded daily. Take appropriate actions when the combined chlorines are too high.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
2 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The flow meter float appeared to be jammed, causing a reading of approximately 45 USGPM.REQUIREMENT: Repair the flow meter. Maintain the flow of the pool between 76 and 106 USGPM.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- The combined chlorines were not being tested and recorded daily.REQUIREMENT: The combined chlorines must be tested, and the value/result recorded daily. Take appropriate actions when the combined chlorines are too high.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
4 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- The water sample collected on October 18, 2023 had total coliforms detected in the sample.REQUIREMENT: Review the water chemistry for both basins and begin immediate treatment of the water. Collect and send a re-sample immediately after you complete necessary treatments
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample collected on October 12, 2023, had HPC detected at 420 CFU/mL.REQUIREMENT: Review the water chemistry for both basins and begin immediate treatment of the water. Collect and send a re-sample immediately after you complete necessary treatments
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The flow meter float appeared to be jammed, causing a reading of approximately 45 USGPM.REQUIREMENT: Repair the flow meter. Maintain the flow of the pool between 76 and 106 USGPM.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- The combined chlorines were not being tested and recorded daily.REQUIREMENT: The combined chlorines must be tested, and the value/result recorded daily. Take appropriate actions when the combined chlorines are too high.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
4 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- The water sample collected on October 12, 2023 had total coliforms detected in the sample.REQUIREMENT: Review the water chemistry for both basins and begin immediate treatment of the water. Collect and send a re-sample immediately after you complete necessary treatments
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample collected on October 12, 2023, had HPC detected at 420 CFU/mL.REQUIREMENT: Review the water chemistry for both basins and begin immediate treatment of the water. Collect and send a re-sample immediately after you complete necessary treatments
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The flow meter float appeared to be jammed, causing a reading of approximately 45 USGPM.REQUIREMENT: Repair the flow meter. Maintain the flow of the pool between 76 and 106 USGPM.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- The combined chlorines were not being tested and recorded daily.REQUIREMENT: The combined chlorines must be tested, and the value/result recorded daily. Take appropriate actions when the combined chlorines are too high.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
4 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- The water sample collected on August 24, 2023 had total coliforms detected in the sample.REQUIREMENT: Review the water chemistry for both basins and begin immediate treatment of the water. Collect and send a re-sample immediately after you complete necessary treatments
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample collected on August 24, 2023, had HPC detected at 550 CFU/mL.REQUIREMENT: Review the water chemistry for both basins and begin immediate treatment of the water. Collect and send a re-sample immediately after you complete necessary treatments
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The flow meter float appeared to be jammed, causing a reading of approximately 45 USGPM.REQUIREMENT: Repair the flow meter. Maintain the flow of the pool between 76 and 106 USGPM.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- The combined chlorines were not being tested and recorded daily.REQUIREMENT: The combined chlorines must be tested, and the value/result recorded daily. Take appropriate actions when the combined chlorines are too high.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample collected on July 20, 2023, had HPC detected at 140 CFU/mL.REQUIREMENT: . Please review the water chemistry for the pool and balance as needed. An immediate re-sample is not required for the main pool at this time.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The flow meter float appeared to be jammed, causing a reading of approximately 45 USGPM.REQUIREMENT: Repair the flow meter. Maintain the flow of the pool between 76 and 106 USGPM.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- The combined chlorines were not being tested and recorded daily.REQUIREMENT: The combined chlorines must be tested, and the value/result recorded daily. Take appropriate actions when the combined chlorines are too high.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
2 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The flow meter float appeared to be jammed, causing a reading of approximately 45 USGPM.REQUIREMENT: Repair the flow meter. Maintain the flow of the pool between 76 and 106 USGPM.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- The combined chlorines were not being tested and recorded daily.REQUIREMENT: The combined chlorines must be tested, and the value/result recorded daily. Take appropriate actions when the combined chlorines are too high.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?