Hampton Inn - Hot Tub

100 - 950 Emerald Drive Sherwood Park AB T8H 0W6 · Aquatic Facility

13 inspections

  1. Risk Management Inspection

    0 infractions

  2. Monitoring Inspection

    4 infractions

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Total alkalinity measured 42ppm.Operator added Sodium Bicarbonate and Total Alkalinity measured 80ppm.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow rate of the whirlpool measured 80 gpm. To Achieve the minimum required turnover rate of 20 minutes, the whirlpool must operate at 105 gpm minimum. Operator to raise the flow rate of the whirlpool.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • A floating weir for one of the whirlpool skimmers was not functioning properly. This was corrected once noted by operator.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow of the water was not being maximized through the skimmers.This was corrected by limiting the flow to the main drain to 10% and while leaving the skimmer valves fully opened.
  3. Monitoring Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Water Flow was not being maximized through the skimmers. Valves were adjusted to maximize flow through the skimmers and reduce the flow to the main drain.
  4. Risk Management Inspection

    0 infractions

  5. Risk Management Inspection

    1 infraction

    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • The sumps are not as deep as listed in the drawings. They are 4.5” for a 4” pipe for the floor drains which is non complaint with the drain covers.
  6. Risk Management Inspection

    1 infraction

    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • The sumps are not as deep as listed in the drawings. They are 4.5” for a 4” pipe for the floor drains which is non complaint with the drain covers.
  7. Monitoring Inspection

    0 infractions

  8. Risk Management Inspection

    2 infractions

    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • Sand noted on the whirlpool basin floor reported to be from backwashing procedure as per operator. - Vacuum whirlpool basin to remove sand.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • An update copy of the anti-entrapment plan needs to be submitted to AHS- EPH. Safety covers appear to have been replaced on August 26,2024.
  9. Monitoring Inspection

    4 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The whirlpool skimmer drain was turned off in the mechanical room at the time of inspection. - Ensure to maximize the flow of the water through the skimming devices during recirculation. The operated turned on the flow of water at the skimmer drain.
    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • The following submerged suction outlets were expired as per the anti-entrapment plan and have not been recently replaced as per operator: - H-MD1. WGX103213LV2. Installed June 1, 2015. Expired: Installed June 1, 2022.- H-MD2. WGX103213LV2. Installed June 1, 2015. Expired: Installed June 1, 2022.**Replace the submerged suction outlet covers as soon as possible due to expiry. Operator scheduled replacement for Monday, August 26th, 2024 and will close the pool during replacement. No damage, cracking, or screws missing to submerged suction outlets at the time of inspection. Anti-entrapment devices are critical pieces of equipment that must be ANSI/APSP-16 2011 compliant, installed according to manufacturer's specifications, maintained in good working order, be replaced before expiration, and follow all requirements set out in the Pool Standards, July 2014 (Amended January 2018); AR 204/2014 s 23.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • Sand noted on the whirlpool basin floor reported to be from backwashing procedure as per operator. - Vacuum whirlpool basin to remove sand.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • Brown grime build up noted on the underside of whirlpool skimmer lids. - Clean skimmer lids. Operator cleaned skimmer lids with pool cleaner during inspection.
  10. Risk Management Inspection

    0 infractions

  11. Risk Management Inspection

    1 infraction

    • 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
      • Soap for patron shower was not observed. Ensure patrons have access to a cleansing shower before using the pool.
  12. Demand Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Pseudomonas aeruginosa present in hot tub water sample result.Ensure the hot tub is cleaned and disinfected following the procedures on the Pseudomonas aeruginosa information document provided. Pool should remain closed until satisfactory water sample result is received.
    • 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
      • Soap for patron shower was not observed. Ensure patrons have access to a cleansing shower before using the pool.
  13. Monitoring Inspection

    3 infractions

    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • The hot tub PH was measured to be at 7.73. This was adjusted during inspection to 7.3.
    • 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
      • Soap for patron shower was not observed. Ensure patrons have access to a cleansing shower before using the pool.
    • 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
      • The water Free Chlorine level was over range. This was adjusted to 3.41ppm during inspection.