Hampton Inn - Swimming Pool

100 - 950 Emerald Drive Sherwood Park AB T8H 0W6 · Aquatic Facility

Inspection summary

Hampton Inn - Swimming Pool has been inspected 10 times by Alberta Health Services (Environmental Public Health) since January 24, 2024. The most recent inspection, on July 13, 2026, found no infractions.

4 of 10 inspections on record found no infractions at all. In the past 12 months there were 3 inspections with 3 infractions recorded. The higher-risk findings here relate to: Pool and spa water quality and Food temperature control.

The number of infractions per inspection has stayed roughly the same over time.

What these findings mean

Health authorities word their findings differently, so we group them by what they mean for the people using the facility. Higher-risk findings are the ones that could directly cause illness or injury, such as water that is not properly treated.

  • Pool and spa water qualityHigher risk

    For pools, spas and splash pads, inspectors test disinfectant levels, pH and water clarity, and check safety equipment. Water that is not properly treated can spread skin, ear and stomach infections.

    Recorded 12 times across 6 separate inspections, most recently on May 29, 2026. For example: Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?

  • Food temperature controlHigher risk

    Inspectors check that anything that has to be kept at a set temperature, such as chilled or hot food, or equipment like sterilizers, stays in its safe range and that accurate thermometers are on hand. With food, temperature problems are one of the most common causes of food poisoning.

    Recorded once on August 21, 2024. For example: Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?

  • Food safety training and certificationLower risk

    Many jurisdictions require trained pool operators and certified lifeguards. These findings mean required training, certification or staffing records were missing at the time of inspection.

    Recorded once on August 27, 2024. For example: Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?

About this data

These results come from Alberta Health Services (Environmental Public Health), which inspects food premises and other public facilities in this area. We republish the authority's public disclosure data and refresh it regularly; the official record is the final word.

10 inspections

  1. Monitoring Inspection

    0 infractions

  2. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • HPC count was 130 on the lab report. Clean and resample.
  3. Monitoring Inspection

    2 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Initial flow rate was observed to be 80 degrees Celsius. Sand filter is a TR100 filter medium surface area 4.91 sq.ft. Max flow rate for filter is 74 gpm. Operator reduced flow rate to 70 gpm.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow of the water was not being maximized through the skimmers. This was corrected by limiting the flow to the main drain to 10% and while leaving the skimmer valves fully opened.The water surface was coming above the internal lip of the skimmers. This was adjusted by lowering the volume of the pool an inch.
  4. Risk Management Inspection

    0 infractions

  5. Monitoring Inspection

    2 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Filter Maximum Flow Rate is 74 GPM.Pool operating at 80 GPM.Reduce flow rate to operator bellow legislative maximum of 74 pgm.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Water Flow was not being maximized through the skimmers. Valves were adjusted to maximize flow through the skimmers and reduce the flow to the main drain.
  6. Monitoring Inspection

    0 infractions

  7. Risk Management Inspection

    3 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • From previous visit: The alarm light was on at the automated controller panel. Operator reported the alarm was on due to high chlorine reading in the swimming pool. Free chlorine was then measured at 3.18 ppm. - Operator reported they will consult pool maintenance services to assess and remedy alarm.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • From previous visit: The filtration rate of the swimming pool was calculated at 16.29 gpm/ft. sq. - Ensure the filtration rate does not exceed the maximum rate of 15 gpm/ft. sq. Adjust the pump to ensure the flow rate of the swimming pool does not exceed 74 GPM to maintain a filtration rate of 15gpm/ft. sq. or less.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • An update copy of the anti-entrapment plan needs to be submitted to AHS- EPH. Safety covers appear to have been replaced on August 26,2024.
  8. Monitoring Inspection

    5 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The filtration rate of the swimming pool was calculated at 16.29 gpm/ft. sq. - Ensure the filtration rate does not exceed the maximum rate of 15 gpm/ft. sq. Adjust the pump to ensure the flow rate of the swimming pool does not exceed 74 GPM to maintain a filtration rate of 15gpm/ft. sq. or less.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The weir door was missing at the swimming pool skimmer inlet adjacent to the shower. - Replace the weir door to ensure proper skimmer function.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The alarm light was on at the automated controller panel. Operator reported the alarm was on due to high chlorine reading in the swimming pool. Free chlorine was then measured at 3.18 ppm. - Operator reported they will consult pool maintenance services to assess and remedy alarm.
    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • The following submerged suction outlets were expired as per the anti-entrapment plan and have not been recently replaced as per operator: - S-MD1. WGX103213LV2. Installed June 1, 2015. Expired: Installed June 1, 2022.- S-MD2. WGX103213LV2. Installed June 1, 2015. Expired: Installed June 1, 2022.**Replace the submerged suction outlet covers as soon as possible due to expiry. Operator scheduled replacement for Monday, August 26th, 2024 and will close the pool during replacement. No damage, cracking, or screws missing to submerged suction outlets at the time of inspection. Anti-entrapment devices are critical pieces of equipment that must be ANSI/APSP-16 2011 compliant, installed according to manufacturer's specifications, maintained in good working order, be replaced before expiration, and follow all requirements set out in the Pool Standards, July 2014 (Amended January 2018); AR 204/2014 s 23.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • The plastic within the swimming pool skimmer devices was separating above the water level leaving gaps that may leak water and/or harbour microbial growth. - Seal, repair, or replace skimmer devices to remove open gaps.
  9. Risk Management Inspection

    0 infractions

  10. Demand Inspection

    1 infraction

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Water sample result; T.C presentIncrease Free Available Chlorine (FAC) level to 10 ppm and maintain pH at or near 7.2.Run the water through the circulation system for at least one turnover. Balance the water, resample as soon as possible.