Holiday Inn Express & Suites Airport - Whirlpool has been inspected 20 times by Alberta Health Services (Environmental Public Health) since October 23, 2023. The most recent inspection, on October 7, 2026, recorded 1 infraction.
3 of 20 inspections on record found no infractions at all. In the past 12 months there were 3 inspections with 6 infractions recorded. The higher-risk findings here relate to: Pool and spa water quality and Chemicals and toxic substances.
Recent inspections have recorded fewer infractions than earlier ones, so the record is improving.
What these findings mean
Health authorities word their findings differently, so we group them by what they mean for the people using the facility. Higher-risk findings are the ones that could directly cause illness or injury, such as water that is not properly treated.
Pool and spa water qualityHigher risk
For pools, spas and splash pads, inspectors test disinfectant levels, pH and water clarity, and check safety equipment. Water that is not properly treated can spread skin, ear and stomach infections.
Recorded 37 times across 17 separate inspections, most recently on October 7, 2026. For example:
Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
Chemicals and toxic substancesHigher risk
Pool chemicals such as chlorine and acid must be labelled, stored apart from each other and handled safely. Mixing them by mistake can release toxic gas, so storage and handling problems are treated seriously.
Recorded 10 times across 6 separate inspections, most recently on January 21, 2026. For example:
Is the chemical quality of the water in this pool satisfactory (Critical)?
About this data
These results come from Alberta Health Services (Environmental Public Health), which inspects food premises and other public facilities in this area. We republish the authority's public disclosure data and refresh it regularly; the official record is the final word.
20 inspections
- Demand Inspection
1 infraction
- 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
- At the time of inspection, one of the eyeball jet diffusers was missing, leaving a pipe opening that could pose a potential physical entrapment hazard. The operator was advised to install the missing eyeball jet diffuser to eliminate the hazard.Please send a photo, once its installed.
- 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
- Monitoring Inspection
2 infractions
- 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
- At the time of inspection, one of the eyeball jet diffusers was missing, leaving a pipe opening that could pose a potential physical entrapment hazard. The operator was advised to install the missing eyeball jet diffuser to eliminate the hazard.
- 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
- Some sand accumulation was observed on the bottom of the pool basin. The operator was advised to vacuum the pool basin to remove the accumulated sand. If sand accumulation reoccurs following cleaning, the operator is advised to inspect the filtration system to determine whether sand is escaping from the filter. Check filter laterals for possible cracking, or deterioration. Appropriate corrective action should be taken based on the condition of the filter.
- 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
- Demand Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample submitted Jan 21, 2024-Time of collection was not indicated. - Sample ID 26ES-021E00307- Resampling advised.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- The Free Available Chlorine (FAC) was measured at 1.80 ppm. The inspector informed the operator to maintain the FAC concentration to at least 2.0 ppm at all times.
- 06. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Critical)?
- The flow meter was missing. The operator mentioned that the flow meter was broken and was removed three (3) weeks ago. The inspector informed the operator that the flow meter is crucial in determining the flow rate, filtration rate, and turnover period, which are all important parameters to confirm that the filtration and circulation of the whirlpool is adequate and within the required ranges.**OUTSTANDING (2025-07-10). The flow meter was still missing. However, a service technician was on site during the inspection to install a flow meter. A re-inspection will be conducted to confirm that the flow meter is functional.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
2 infractions
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- The Free Available Chlorine (FAC) was measured at 1.80 ppm. The inspector informed the operator to maintain the FAC concentration to at least 2.0 ppm at all times.
- 06. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Critical)?
- The flow meter was missing. The operator mentioned that the flow meter was broken and was removed three (3) weeks ago. The inspector informed the operator that the flow meter is crucial in determining the flow rate, filtration rate, and turnover period, which are all important parameters to confirm that the filtration and circulation of the whirlpool is adequate and within the required ranges.**OUTSTANDING (2025-07-10). The flow meter was still missing. However, a service technician was on site during the inspection to install a flow meter. A re-inspection will be conducted to confirm that the flow meter is functional.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Monitoring Inspection
1 infraction
- 06. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Critical)?
- The flow meter was missing. The operator mentioned that the flow meter was broken and was removed three (3) weeks ago. The inspector informed the operator that the flow meter is crucial in determining the flow rate, filtration rate, and turnover period, which are all important parameters to confirm that the filtration and circulation of the whirlpool is adequate and within the required ranges.
- 06. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Critical)?
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample (25ES-120E00398) was not sampled because the sample was received more than 24 hours after collection. Please submit another sample immediately.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- The water sample collected on December 26, 2024, had Pseudomonas aeruginosa isolated per 100mL.REQUIREMENT: Begin treatment for the pool. Collect and send a re-sample after you complete necessary treatments, and the water chemistry is balanced. Indicate on the requisition form that the sample is a ‘resample’.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
0 infractions
- Demand Inspection
5 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample collected on February 07, 2024, was not processed due to the lab receiving the water sample 24 hours after collection.REQUIREMENT: Collect another sample and ensure the sample is received by the lab less than 24 hours from collection time.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Whirlpool water pH and free available chlorine could not be measured/read by AHS pool kit. The kit indicated that the pool pH was too low, below 6.5 and free available chlorine was too high, above 8 milligram per litre.-Please maintain pool water chemical balance as required: pH should be maintained between 6.8 and 7.6.FAC should be above 2 milligrams per litre.Recommendation: Whirlpool water FAC should be maintained below 6 milligrams per litre to protect individuals with skin and respiratory sensitives.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The pool's total alkalinity was measured at 57 milligrams per litre. Pool total alkalinity should be between 60-180 milligrams per litre. in accordance with the pool Standards.-Please adjust water chemical balance to meet with the requiredment.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Last inspection, it was noted that "the automated feeder system displayed a reading of 7.4 where the pH ranged between 6.5-6.6 on the test kits."This inspection, the automated feeder system also displayed a reading of 7.4 where the pH ranged between 6.5-6.6 on the test kits.REQUIREMENT: Ensure the pool chemistry is properly balanced, and that readings from manual testing is consistent with readings from the automated feeder system.The violation was also noted during this inspection.
- 15. Has an owner or owner's agent, if any, been identified and is the pool operated and maintained by a qualified pool operator?
- Manager onsite said they did not have a certified pool operator at this location. Obtain Pool/Spa Operator Certification.Outstanding violation not resolved.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
5 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- The water sample collected on January 18, 2024, had Pseudomonas isolated in the sample.REQUIREMENT: Begin treatment for the whirlpool immediately and send a re-sample for the whirlpool after you complete necessary treatments. Indicate on the requisition form that the sample is a ‘resample’.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Whirlpool water pH and free available chlorine could not be measured/read by AHS pool kit. The kit indicated that the pool pH was too low, below 6.5 and free available chlorine was too high, above 8 milligram per litre.-Please maintain pool water chemical balance as required: pH should be maintained between 6.8 and 7.6.FAC should be above 2 milligrams per litre.Recommendation: Whirlpool water FAC should be maintained below 6 milligrams per litre to protect individuals with skin and respiratory sensitives.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The pool's total alkalinity was measured at 57 milligrams per litre. Pool total alkalinity should be between 60-180 milligrams per litre. in accordance with the pool Standards.-Please adjust water chemical balance to meet with the requiredment.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Last inspection, it was noted that "the automated feeder system displayed a reading of 7.4 where the pH ranged between 6.5-6.6 on the test kits."This inspection, the automated feeder system also displayed a reading of 7.4 where the pH ranged between 6.5-6.6 on the test kits.REQUIREMENT: Ensure the pool chemistry is properly balanced, and that readings from manual testing is consistent with readings from the automated feeder system.The violation was also noted during this inspection.
- 15. Has an owner or owner's agent, if any, been identified and is the pool operated and maintained by a qualified pool operator?
- Manager onsite said they did not have a certified pool operator at this location. Obtain Pool/Spa Operator Certification.Outstanding violation not resolved.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
4 infractions
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Whirlpool water pH and free available chlorine could not be measured/read by AHS pool kit. The kit indicated that the pool pH was too low, below 6.5 and free available chlorine was too high, above 8 milligram per litre.-Please maintain pool water chemical balance as required: pH should be maintained between 6.8 and 7.6.FAC should be above 2 milligrams per litre.Recommendation: Whirlpool water FAC should be maintained below 6 milligrams per litre to protect individuals with skin and respiratory sensitives.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The pool's total alkalinity was measured at 57 milligrams per litre. Pool total alkalinity should be between 60-180 milligrams per litre. in accordance with the pool Standards.-Please adjust water chemical balance to meet with the requiredment.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Last inspection, it was noted that "the automated feeder system displayed a reading of 7.4 where the pH ranged between 6.5-6.6 on the test kits."This inspection, the automated feeder system also displayed a reading of 7.4 where the pH ranged between 6.5-6.6 on the test kits.REQUIREMENT: Ensure the pool chemistry is properly balanced, and that readings from manual testing is consistent with readings from the automated feeder system.The violation was also noted during this inspection.
- 15. Has an owner or owner's agent, if any, been identified and is the pool operated and maintained by a qualified pool operator?
- Manager onsite said they did not have a certified pool operator at this location. Obtain Pool/Spa Operator Certification.Outstanding violation not resolved.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Monitoring Inspection
5 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- The water sample collected on December 21, 2023, had Pseudomonas isolated.REQUIREMENT: Please begin treatment for the whirlpool immediately and send a re-sample for the whirlpool after you complete necessary treatment. UPDATE: The water resample collected on December 28th had pseudomonas isolated. Verbal closure issued.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Whirlpool water pH and free available chlorine could not be measured/read by AHS pool kit. The kit indicated that the pool pH was too low, below 6.5 and free available chlorine was too high, above 8 milligram per litre.-Please maintain pool water chemical balance as required: pH should be maintained between 6.8 and 7.6.FAC should be above 2 milligrams per litre.Recommendation: Whirlpool water FAC should be maintained below 6 milligrams per litre to protect individuals with skin and respiratory sensitives.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The pool's total alkalinity was measured at 57 milligrams per litre. Pool total alkalinity should be between 60-180 milligrams per litre. in accordance with the pool Standards.-Please adjust water chemical balance to meet with the requiredment.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Last inspection, it was noted that "the automated feeder system displayed a reading of 7.4 where the pH ranged between 6.5-6.6 on the test kits."This inspection, the automated feeder system also displayed a reading of 7.4 where the pH ranged between 6.5-6.6 on the test kits.REQUIREMENT: Ensure the pool chemistry is properly balanced, and that readings from manual testing is consistent with readings from the automated feeder system.The violation was also noted during this inspection.
- 15. Has an owner or owner's agent, if any, been identified and is the pool operated and maintained by a qualified pool operator?
- Manager onsite said they did not have a certified pool operator at this location. Obtain Pool/Spa Operator Certification.Outstanding violation not resolved.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
3 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- The water sample collected on December 21, 2023, had Pseudomonas isolated.REQUIREMENT: Please begin treatment for the whirlpool immediately and send a re-sample for the whirlpool after you complete necessary treatment. UPDATE: The water resample collected on December 28th had pseudomonas isolated. Verbal closure issued.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Last inspection, it was noted that "the automated feeder system displayed a reading of 7.4 where the pH ranged between 6.5-6.6 on the test kits."This inspection, the automated feeder system also displayed a reading of 7.4 where the pH ranged between 6.5-6.6 on the test kits.REQUIREMENT: Ensure the pool chemistry is properly balanced, and that readings from manual testing is consistent with readings from the automated feeder system.
- 15. Has an owner or owner's agent, if any, been identified and is the pool operated and maintained by a qualified pool operator?
- Manager onsite said they did not have a certified pool operator at this location. Obtain Pool/Spa Operator Certification.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
3 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- The water sample collected on December 21, 2023, had Pseudomonas isolated.REQUIREMENT: Please begin treatment for the whirlpool immediately and send a re-sample for the whirlpool after you complete necessary treatment.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Last inspection, it was noted that "the automated feeder system displayed a reading of 7.4 where the pH ranged between 6.5-6.6 on the test kits."This inspection, the automated feeder system also displayed a reading of 7.4 where the pH ranged between 6.5-6.6 on the test kits.REQUIREMENT: Ensure the pool chemistry is properly balanced, and that readings from manual testing is consistent with readings from the automated feeder system.
- 15. Has an owner or owner's agent, if any, been identified and is the pool operated and maintained by a qualified pool operator?
- Manager onsite said they did not have a certified pool operator at this location. Obtain Pool/Spa Operator Certification.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
3 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- The water sample collected on November 02, 2023, had Pseudomonas isolated.The subsequent water sample collected on November 07, 2023, had Pseudomonas isolated.REQUIREMENT: Close the basin immediately to the public. Please begin treatment for the whirlpool immediately and send a re-sample for the whirlpool after you complete necessary treatments.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Last inspection, it was noted that "the automated feeder system displayed a reading of 7.4 where the pH ranged between 6.5-6.6 on the test kits."This inspection, the automated feeder system also displayed a reading of 7.4 where the pH ranged between 6.5-6.6 on the test kits.REQUIREMENT: Ensure the pool chemistry is properly balanced, and that readings from manual testing is consistent with readings from the automated feeder system.
- 15. Has an owner or owner's agent, if any, been identified and is the pool operated and maintained by a qualified pool operator?
- Manager onsite said they did not have a certified pool operator at this location. Obtain Pool/Spa Operator Certification.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
2 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- The water sample collected on November 02, 2023, had Pseudomonas isolated.The subsequent water sample collected on November 07, 2023, had Pseudomonas isolated.REQUIREMENT: Close the basin immediately to the public. Please begin treatment for the whirlpool immediately and send a re-sample for the whirlpool after you complete necessary treatments.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Last inspection, it was noted that "the automated feeder system displayed a reading of 7.4 where the pH ranged between 6.5-6.6 on the test kits."This inspection, the automated feeder system also displayed a reading of 7.4 where the pH ranged between 6.5-6.6 on the test kits.REQUIREMENT: Ensure the pool chemistry is properly balanced, and that readings from manual testing is consistent with readings from the automated feeder system.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
3 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- The water sample collected on November 02, 2023, had Pseudomonas isolated.REQUIREMENT: Please begin treatment for the whirlpool immediately and send a re-sample for the whirlpool after you complete necessary treatments.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample collected on November 02, 2023, had an HPC count of > 57000 CFU/mL.REQUIREMENT: Please begin treatment for the whirlpool immediately and send a re-sample for the whirlpool after you complete necessary treatments
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Last inspection, it was noted that "the automated feeder system displayed a reading of 7.4 where the pH ranged between 6.5-6.6 on the test kits."This inspection, the automated feeder system also displayed a reading of 7.4 where the pH ranged between 6.5-6.6 on the test kits.REQUIREMENT: Ensure the pool chemistry is properly balanced, and that readings from manual testing is consistent with readings from the automated feeder system.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
3 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- The water sample collected on October 19, 2023, had Pseudomonas isolated.REQUIREMENT: Please begin treatment for the whirlpool immediately and send a re-sample for the whirlpool after you complete necessary treatments.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample collected on October 19, 2023, had an HPC count of > 57000 CFU/mL.REQUIREMENT: Please begin treatment for the whirlpool immediately and send a re-sample for the whirlpool after you complete necessary treatments
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Last inspection, it was noted that "the automated feeder system displayed a reading of 7.4 where the pH ranged between 6.5-6.6 on the test kits."This inspection, the automated feeder system also displayed a reading of 7.4 where the pH ranged between 6.5-6.6 on the test kits.REQUIREMENT: Ensure the pool chemistry is properly balanced, and that readings from manual testing is consistent with readings from the automated feeder system.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
Nearby inspected facilities
- Holiday Inn Express & Suites Airport - Food
45 Hopewell Way NE Calgary AB T3J 4V7
5 inspections
- Holiday Inn Express & Suites Airport - Common
45 Hopewell Way NE Calgary AB T3J 4V7
5 inspections
- Holiday Inn Express & Suites Airport - Swimming Pool
45 Hopewell Way NE Calgary AB T3J 4V7
16 inspections
- Chop Steakhouse & Bar
33 Hopewell Way NE Calgary AB T3J 4V7
5 inspections
- Candy Cloud Creations - Events
10 - 40 Hopewell Way NE Calgary AB T3J 5H7
3 inspections
- Sandman Hotel Calgary Airport - Whirlpool
25 Hopewell Way NE Calgary AB T3J 4V7
5 inspections
- Sandman Hotel Calgary Airport - Swimming Pool
25 Hopewell Way NE Calgary AB T3J 4V7
36 inspections
- Sandman Hotel Calgary Airport - Common
25 Hopewell Way NE Calgary AB T3J 4V7
2 inspections