Holiday Inn & Suites Calgary South - Swimming Pool

8360 Blackfoot Trail SE Calgary AB T2J 7E1 · Aquatic Facility

22 inspections

  1. Demand Inspection

    0 infractions

  2. Risk Management Inspection

    0 infractions

  3. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The water sample collected on June 10, 2026 had 440 CFU/mL on the Heterotrophic Plate Count test. -treat and resample
  4. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The water sample collected on May 5, 2026 had 2,040 CFU/mL on the Heterotrophic Plate Count test. -treat and resample
  5. Risk Management Inspection

    0 infractions

  6. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample collected on April 15, 2026 had an HPC of 8160 cfu/ml.
  7. Risk Management Inspection

    0 infractions

  8. Risk Management Inspection

    1 infraction

    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • 1. The following test kit reagents in the large bottles were expired:- Thiosulfate N10: 02/25 and 11/23- pH indicator: 04/25- TA indicator: 09/24**March 27, 2026: new reagents have been ordered. COMPLETE THE FOLLOWING:1. Please replace the above reagents.
  9. Monitoring Inspection

    2 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • 1. The valve for the main drain was opened at 80%.COMPLETE THE FOLLOWING:1. Please adjust the main drain valves, so they are opened no more than 30% to increase flow of water through the skimmers, as the top portion of pool water contains the highest amount of contaminants.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • 1. The following test kit reagents in the large bottles were expired:- Thiosulfate N10: 02/25 and 11/23- pH indicator: 04/25- TA indicator: 09/24COMPLETE THE FOLLOWING:1. Please replace the above reagents.2. Ensure the smaller bottles that are re-filled are labeled with the correct expiry dates.
  10. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The pool sample collected on August 19, 2025 did not have a collection time on the requisition so it was not processed by the Prov Lab.ID: 25ES-231E00635-resample
  11. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The water sample submitted on Jun 18, 2025 was not processed since there was no date indicated on the requisition.-submit a new water sampleReq ID: 25ES-169E00349
  12. Risk Management Inspection

    0 infractions

  13. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Results of water sample submitted on May 14, 2025 came back with HPC 110.- Resampling advised.
  14. Demand Inspection

    0 infractions

  15. Monitoring Inspection

    0 infractions

  16. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • 1. The sample collected on October 8, 2024 had an HPC count of 780 CFU/ml.2. The sample collected on October 16, 2024 had an HPC count of 200 CFU/ml.Treat the pool and send in a resample.
  17. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The sample collected on October 8, 2024 had an HPC count of 780 CFU/ml.Treat the pool and send in a resample.
  18. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The sample collected on September 10, 2024 had an HPC count of 310 CFU/ml.Treat the pool and send in a resample.
  19. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The sample collected on June 13, 2024 had an HPC count of 240 CFU/ml.Treat the pool and send in a resample.
  20. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The sample collected on May 14, 2024 had an HPC count of 670 CFU/ml.Treat the pool and send in a resample.
  21. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The sample collected on March 22, 2024 had an HPC count of 290 CFU/ml.Treat the pool and send in a resample.
  22. Monitoring Inspection

    0 infractions